Toshiba MCY-MUG0401HSW-E Service Manual page 237

Hide thumbs Also See for MCY-MUG0401HSW-E:
Table of Contents

Advertisement

No.
Component
16
Power supply wires
and Indoor / Outdoor
connecting wires
Procedure
1. Detachment
1)Remove the Power wire and Indoor / Outdoor
communication wire from the power supply
terminal block and communication terminal block.
[Step1]
2)Cut the banding bands which fix Indoor / Outdoor
connecting wires and Power supply wires to the
Valve fixing plate. (Fig. 16-1)
2. Attachment
1) Connect the Indoor / Outdoor connection wires
and Power supply wires to the terminal.
WARNING
Make sure the ground wire is connected.
Incomplete earthing may lead to electric shock.
2) Fix each wire tightly to the Valve fixing plate with
the banding bands.(Fig. 16-2)
CAUTION
Measure the diameter of the wire to be fixed,
and fasten the wire with the supplied banding
band (T50-RHSW from HellermannTyton),
so that length A of the surplus portion of the
tie satisfies the following expression.
(Fig. 16-2,16-3)
A=183-L
L= Diameter of wire D (mm) x π
A: Minimum length of surplus portion of
banding band (mm)
L: Circumferential length of wire (mm)
Banding band specifications:
Flame
Model Material
retardant
grade
T50R-
Nylon 66
UL94V-2
HSW
3)Cut off the surplus portion(A) of the
banding band.
4)Mount the Front panel by reversing the
detachment procedure.
Valve fixing plate
Banding band of
Power supply wires
manufacture
r
Hellermann
Tyton
236
Remarks
Fig. 16-1
Fig. 16-2
Banding band
Valve fixing plate
Wire
Fig. 16-3
Banding
band of
Indoor /
Outdoor
connectin
g wires
A