3. Communication setting (Auto setting)
Setup procedure
(1) Turn on indoor units first, and then turn on outdoor units.
(2) Set the rotary switch of the interface P.C. board on the outdoor unit to SW01=[2], SW02=[16] and SW03=[2].
(3) The 7-segment display switches between "c.c. b p s" and "c.c. 0" at 1-second intervals.
(4) Push and hold SW04 for more than 5 seconds.
(5) The 7-segment display flashes "c.c.i n".
(6) The 7-segment display switches between "c.c. i n" and "c.c. ***" at 1-second intervals.
Check the number of connected indoor units [***].
(When the number of the connected indoor units differs from the number of indoor units displayed on the
7-segment display, clear the communication type setting to eliminate the cause.
To clear the communication type setting, push and hold the SW05 for 5 seconds or more.
The 7-segment display flashes "c.c.r S t".
After a while, the 7-segment display switches between "c.c. b p s" and "c.c. 0".
Set the rotary switch back to SW01 to [1], SW02 to [1], SW03 to [1].)
(7) Push and hold SW06 for more than 5 seconds.
(8) The 7-segment display flashes "c.c.b p s".
After that, the setting is complete when the 7-segment display changes to "c.c F i n".
(If the 7-segment display changes to "c.c. E r r ", try again.)
(9) After a while, the 7-segment display switches between "c.c. b p s" and "c.c. 1" (or "c.c. o") at 1-second intervals.
(10) Set the rotary switch on the interface P.C. board of the outdoor unit back to SW01=[1], SW02=[1], SW03=[1].
Interface P.C. board on the outdoor unit
4
SW04
SW05
SW01
SW02
7
SW06
3, 5, 6
8, 9
2, 10
SW03