Low Coolant Level
Shutdown Switch
If the engine coolant falls below the " safe"range in the
radiator, the generator will automatically shutdown. The
generator set will not run until coolant is added to the
specified level. The Low Coolant Level (LCL) shutdown
switch will not function during the first five seconds after
startup. Location of the LCL shutdown switch is shown in
Figure 2-6.
1. Low Coolant Level Switch
Figure 2-6. Low Coolant Level
Shutdown Switch
2-8 Operation
Accessories
1
1-932
Low Fuel Level
Shutdown Switch
Provisions have been made in the wiring harness for
wiring a Low Fuel Level (LFL) switch to the generator. A
LFL switch will shut the unit down in the event that the
fuel nears empty. ' Running a diesel engine out of fuel
completely results in a dry fuel injection system which
must be completely bled in order to restart the engine
after refilling the fuel tank.'The LFL switch prevents the
fuel system from being run dry, thus allowing immediate
restarting, once the fuel tank has been refilled.
TP-5648 8/93