Kohler 10CCOZ61 Service Manual page 83

Mobile generator sets
Table of Contents

Advertisement

2. Disconnect the 22-pin harness connector from the
stationary connector at the back of the controller.
See Figure 8-2.
2
1. Connector, 22-Pin
2. Controller
Figure 8-2. Disconnecting the 22-Pin Connector
3. Remove the plug caps from the ends of the
bumper studs within the controller. Remove the
nuts securing the controller to the bumpers using a
1/2-inch wrench or nut driver. See Figure 8-3.
2
1. Bumper Nuts
2. Controller
Figure 8-3. Removing the Bumper Nuts
4. Remove any external connections to terminals
labeled GND, ST1, ST2, and BAT on the controller
8-2 Disassembly/Reassembly
1
1. Terminal Board
2. Controller
Figure 8-4. Disconnecting Terminal Strip Leads
5. Remove the slotted screw and disconnect the
1
1. Screw
2. Ground Strap
6. Remove the controller.
7. Disconnect P8 from J8.
chassis. Also disconnect and remove leads from
terminals labeled C0, C1, and C2 on the controller
chassis. See Figure 8-4.
2
ground strap from the controller. See Figure 8-5.
1
Figure 8-5. Disconnecting the Controller
Ground Strap
1
2
TP-5648 8/93

Advertisement

Table of Contents
loading

Table of Contents