To insure continued satisfactory operation, the following
items should be checked before each startup.

Prestart Checklist

OIL LEVEL: Should be at or near full mark (not over).
AIR INLETS: Must be clear and unobstructed.
COMPARTMENT: Interior must be clean. Check the
condition of fuel system, exhaust piping, hoses, and
muffler. If fuel leaks, fumes, exhaust gases, or electrical
sparks are noted, contact a qualified service technician
before operating generator set.
AIR CLEANER: Must be clean and properly installed to
prevent unfiltered air from entering the engine.
ELECTRICAL: All connections (including battery) must
be tight.
FUEL LEVELS: Make sure the fuel tank(s) are full and
the fuel system primed for operation.
COOLING: If the cooling system is equipped with a
coolant recovery tank, check coolant level (and refill
coolant as necessary) at tank. Maintain level according
to markings on the tank. Coolant level should be just
TP-5648 8/93

Section 2. Operation

below the filler neck [approx. 3/4 to 1 1/2 in. (19.38 mm)]
when the engine is cold.
BATTERY: Check connections and level of battery
electrolyte.
DRIVE BELTS: Check radiator fan, water pump, and the
battery charging belt to make sure it is properly
tensioned and in good condition. Exhaust gas must be
vented safely outside.
OPERATING AREA:
obstructions that could block the flow of cooling air.
Make sure the area is clean. Rags, tools, or debris must
not be left on or near the generator set.
EXHAUST SYSTEM: Exhaust outlet must be clear;
silencer and piping must be tight and in good condition.
Exhaust gas must be vented safely outside.

Exercising the Generator

Run the generator set once a week for one hour (under
load). The operator should be in attendance during this
period. Be sure to make all " Prestart Checks" before
starting the exercise procedure. Start the generator set
according to the procedure given for the generator
controller.
Make sure there are no
Operation 2-1