Operating Modes; Automatic And Manual Modes - Samson 3730-3 Mounting And Operating Instructions

Electropneumatic positioner with hart communication
Table of Contents

Advertisement

Operating the positioner

7.11 Operating modes

7.11.1 Automatic and manual modes

After initialization has been completed suc-
cessfully, the positioner is in
(AUTO).
Switching to
manual mode (MAN):
1. Turn
until Code 0 appears.
2. Press
, reading: AUtO, the code number
0 blinks.
3. Turn
until MAN appears.
4. Press
. The positioner changes to the
manual mode ( ).
The manual mode starts using the last set
point of the automatic mode, ensuring a
bumpless changeover. The current position
is displayed in %.
Adjusting the manual set point:
1. Turn
until Code 1 appears.
2. Press
, the code number 1 blinks.
3. Turn
until sufficient pressure has been
built up in the positioner and the control
valve moves to the required position.
116
automatic mode
Automatic mode
%
Automatic mode
Manual mode
%
%
EB 8384-3 EN

Advertisement

Table of Contents
loading

Table of Contents