The position of volume restriction Q also depends on how the signal pressure is routed at the
actuator in SAMSON actuators:
'SIDE' inscription
For actuators with a signal pressure connection at the side, e.g. Type 3271-5
For actuators from other manufacturers
'BACK' inscription
− For actuators with a signal pressure connection at the back, e.g. Type 3277-5
The following applies to positioners with optional analog input x: the MIN SIDE setting
must always be used for actuators with an air volume of less than one liter.
NOTICE
!
Malfunction due to changed start-up settings.
Initialize an initialized positioner again after the position of the volume restriction has been
changed.

7.3 Adapting the display direction

To adapt the reading on the display to the mounting situation of the actuator, the display
contents can be turned by 180°. If the displayed data appear upside down, proceed as
follows:
1. Turn
until Code 2 appears.
2. Press
, the code number 2 blinks.
3. Turn
and select the required reading di-
rection.
4. Press
to confirm.
EB 8384-3 EN
Operating the positioner
Reading direction for
right attachment of
pneumatic connections
Reading direction
for left attachment of
pneumatic connections
97