List Of Displayed Errors - Omron ZN-DPX21-S Series User Manual

Differential pressure station, thermo-humidity station, air thermo logger
Table of Contents

Advertisement

7.2 List of Displayed Errors

Display
Upper/lower
DATA
Failed to write
E1100
measured data
SEN
Sensor error
E2000
NO SD
SD memory card not
E3000
inserted
BATLO
Unable to access SD
E3001
memory card
SDLCK
SD memory card
E3002
write prohibited
SD ER
SD memory card
E3003
recognition error
Air Particle Sensor
PDINT
(ZN-PD□□-S□)
E4000
communication
initialization error
Air Particle Sensor
(ZN-PD□□-S
PD-S
□)measurement
E4001
acquisition error
RESTR
Invalid setting file
E5000
data
BCKUP
Failed to write the
E5001
setting file
RESTR
Failed to read the
E5002
setting file
HARD
Hardware error
E****
Content
Failed to write the recorded data to the SD memory card
due to no free space or card being removed during
writing. Insert the writable SD memory card. Hold the
MODE key for 3 seconds or more to release the error
display.
The sensor Head is not connected. Connect the Sensor
Head properly.
SD memory card is not inserted. Insert the writable SD
memory card.
Hold the MODE key for 3 seconds or more to release the
error display.
Unable to access to the SD memory card due to low
battery voltage. Replace the battery or connect to the AC
adapter.
Hold the MODE key for 3 seconds or more to release the
error display.
Writing to the SD memory card is prohibited. Insert the
writable SD memory card.
Hold the MODE key for 3 seconds or more to release the
error display.
Failed to recognize the SD memory card. Insert an
appropriate SD memory card.
Hold the MODE key for 3 seconds or more to release the
error display.
Air Particle Sensor cannot be initialized. Connect with Air
Particle Sensor properly.
Hold the MODE key for 3 seconds or more to release the
error display.
Failed to obtain the measured value from the Air Particle
Sensor. Connect with the Air Particle Sensor properly.
Hold the MODE key for 3 seconds or more to release the
error display.
The setting data within the SD memory card is invalid due
to invalid model type or setting value.
Hold the MODE key for 3 seconds or more to release the
error display.
Failed to write to the SD memory card of the setting file
due to no free space or writing prohibited. Insert a
writable SD memory card.
Hold the MODE key for 3 seconds or more to release the
error display.
There is not setting file in the SD memory card. Insert the
SD memory card in which the setting file has been
written.
Hold the MODE key for 3 seconds or more to release the
error display.
There may be a hardware error. Please contact the
distributor or OMRON representative office to inform the
displayed error code.
7-7
Action to be taken
7. Appendix

Advertisement

Table of Contents
loading

Table of Contents