Fan - Carrier 39CP Installation, Operation And Maintenance Instructions

Air handling unit
Table of Contents

Advertisement

9 - SYSTEM START-UP
Activity
Check for unacceptable contamination, damage (leaks) and odours
Check the pressure differential
Maximum interval before replacement of the first filtration stage
Maximum interval before replacement of the second filtration stage

9.4 - Fan

9.4.1 - Mains voltage
■ Make sure the network voltage matches that shown on the data plate, and that it is within the permissible tolerances.
■ For a 400 V/50 Hz network, voltage tolerance +-10%.
■ The phase unbalance must not exceed 2% for voltage and 10% for current.
9.4.2 - Pre-commissioning check
Warning!
Follow the safety instructions (see § 2 - SAFETY INSTRUCTIONS).
When working inside the unit, make sure that the motors are switched off and the fans are not running.
■ Before starting up the fans, make sure that the fan block is clean and free from foreign objects.
■ Clean if necessary, paying attention to production residue, e.g. oils and cleaning agents.
■ Remove all the shipping safety devices (1, chocks, etc.)
■ Be sure to thoroughly clean the area around the mounting shims removed after transport.
■ Replace the bolts with the hex bolts supplied with the fan.
■ Manually check to ensure that the fan rotates correctly without friction or abnormal noises.
■ Make sure that the wheel is centred on the intake section. Check the spacing "A". This spacing must be the same around the entire
wheel. The value "B" (coverage of the inlet by the wheel) must be approximately 1% of the wheel diameter.
■ Make sure that the impeller is correctly balanced
■ Check the tightness of the mountings (AC motors)
■ Check the mounting of the fans on the partition (M8 screw, 20 Nm tightening for EC motors)
■ Make sure that each outlet and inlet on the block is not obstructed, and that the dampers are open.
■ Check the condition and mounting of the protection accessories (e.g. grille option)
■ Check the suspension mounts (AC motors)
Action, if required
Replace the corresponding
filter
Replace the filtration stage
B
1
3
month
months
X
B
6
12
24
months
months
months
X
X
X
51

Advertisement

Table of Contents
loading

Table of Contents