7 - CONNECTIONS

7.1 - Condensate drain siphon

■ Connecting the siphon
Position, diameter and type of connector, see dimensional drawing.
Outlet on the front panel: Threaded gas type steel connector.
Outlet in frame: Smooth rubber female sleeve for 32 mm PVC bonding tube.
It is recommended to use mastic to adhere the drain pan.
The siphons and drain pipes must be insulated and protected from frost (heating cable).
The siphons must not be directly connected to the waste water network.
■ Siphon calculation:
H in mm = Pa / 10
Pa = Pressure difference (in Pascal) between the inside and outside of the unit.
■ Assembly with depression :
■ Assembly with several coils in parallel:
OK

7.2 - JUXTAPOSE function SPECIAL FEATURE.

■ Dual condensate drain = 1 siphon per front face.
7.2.1 - Heating/cooling coil
7.2.1.1 - Supplying the coils
Follow the instructions on the labels:
Observe the counter-flow principle
- Fluid inlet downstream of the air flow direction
- Fluid outlet upstream of the air flow direction
32
■ Assembly with pressure:
To sewer system
Inlet
To sewer system
Outlet