Following items do not need, generally, any further adjustment:
A - Servomotor
B - Pump
C - Motor overload relay
A - SERVOMOTOR
5
4
Fig. 2
The servomotor controls contemporaneously the air delivery and pressure and the fuel delivery.
It is provided with three adjustable cams, controlling the corresponding switches.
st
1
cam :
it controls the stroke of the servomotor at the position of 0° . When the burner is off the air damper is
completely closed.
nd
2
cam:
it controls the stroke of the servomotor at the position of 130°.
rd
3
cam:
it controls the minimum modulating output, leaves the factory set at 20°.
5480

BURNERS ITEMS SET AT THE FACTORY

1
st
1 - 1
Cam (blue)
2
nd
2 - 2
Cam (red)
3
rd
3 - 3
Cam (black)
6
4 - Pointer
5 - Clamp
6 - Motor reset lever
D1999