2 Before Installation
 Before installing PMC-5141, please finish the hardware installation of the
smart power meters, and make sure all wiring connections are accurate (please
refer to the power meter user manual).
 PMC-5141 allows to connect with up to 16 power meters. The Modbus
address range of the power meter is from 1~64, please make sure the Modbus
address you set does not exceed 64.
 Modify PMC-5141's network settings to fit current network environment
settings, and the default network settings of PMC-5141 is as follow:
IP:192.168.255.1
Subnet mask:255.255.0.0
Gateway address:192.168.0.1
DNS Server address:8.8.8.8
system default DNS server, the default IP is "8.8.8.8", the IP can be
modified to other DNS server IP.)
Steps:
(1) Modify the network settings of the PC or Notebook to be the same network
segment as PMC-5141. For example:
IP:192.168.255.2
Subnet mask:255.255.0.0
Gateway address:192.168.0.1
(2) Connect PMC-5141 LAN1 with PC by network cable. (PMC-5141 is capable
of auto-crossover)
(3) Start the browse and input
(4) Input default administrator password "Admin" to login into the page.
(5) After login in PMC-5141 web page, go to System SettingBasic
SettingNetwork Setting, modify the network setting to fit current network
environment.
(6) Save the settings and connect PMC-5141 to the network.
http://www.icpdas.com
(PMC-5141 adopts Google DNS server as
http://192.168.255.1
in the address bar.