Chapter 13 – The optional remote operators

Connection of the remote operator

Before the optional remote operators DOP, DRW, or OPE-J can be connected the power supply to the
inverter has to be switched off. Then the cable must be plugged into the inverter as shown in the figure. Now
the power supply can be switched on again. The inverter is now in monitor mode and on the remote
operator's LCD display the message FS000.0... is shown.
The parameters that have been configured using L100 series inverters can now be copied to other inverters
using the copy unit DRW-0A2. The old model DRW-0A can not be used for this purpose.
When inverters are operated with a remote operator connected, the following items must be noted:
- The remote operator's cable must not be attached or removed during operation (i.e. if the power supply to
the inverter is switched on).
- The digital operator of the inverter can not be used while the remote operators DOP or DRW are being
connected.
- All remote operator keys are inactive except the STOP/RESET key while the remote operator OPE-J is
being connected (also refer to the description of function b 89 in chapter 8 under "Extended functions of
group B").
Set the dip switches on the back of the remote operator as follows:
ON
1
2
3
4
OFF
When ON, the copy unit cannot be
read out. When the READ key is
pressed, the message RD LOCK
will be displayed
Not used
Setting for L100 and J300:
Position 1: OFF
Position 2: ON
13-1
Chapter 13 – The optional remote operators
DOP, DRW
OPE-J