Function
Display
Digital outputs can be assigned one of 6 different signalling functions. Both outputs may also be assigned to the
same function. The oututs can be programmed either as normally closed contacts or as normally open contacts.
Function of
C 21
digital output 11
Function of
C 22
digital output 12
Function of
C 23
FM terminal
Digital output 11 type
C 31
Digital output 12 type
C 32
Type of
C 33
alarm relay output
Level for overload
C 41
signal
Arrival frequency
C 42
FA2 for acceleration
Arrival frequency
C 43
FA2 for deceleration
Level of PID
C 44
deviation
Function description / parameter setting range
)
*
Programmable digital outputs
One of the following signalling functions can be assigned:
00: RUN signal (signal active during motor run)
01: FA1 signal (frequency arrival)
N
02: FA2 signal (frequency exceeded)
03: OL signal (overload)
04: OD signal (PID-deviation exceeded)
05: AL signal (alarm signal)
N Refer to C 21 for possible parameters
The FM output terminal can be used to output one of the following
values:
00: Output frequency display (analog signal 0–10VDC)
N
01: Motor current display (analog signal 0–10VDC;
100% of the rated current corresponds to 5VDC)
02: Output frequency (digital pulse signal)
N
00: Normally open contact
N Refer to C 31 for possible parameters
N Refer to C 31 for possible parameters
Motor
current
N
OL signal
(Setting range: 0A–2 * Inverter rated current)
f
C 42
N
FA2 signal
(The digital output terminal 11 or 12 configured as FA2 will remain
activated during deceleration as long as the actual frequency is above
N
the frequency entered here (also refer to the figure under C 42).
(Setting range: 0Hz–360Hz)
Actual value
Set value
N
OD signal
8-14
Chapter 8 – Using the digital operator
01: Normally closed contact
If digital output terminals 11
C 41
or 12 have been configured for
output of the overload signal
then the current value entered
here determines when the over-
load signal will be activated.
The digital output terminal 11 or
12 configured as FA2 will be
C 43
activated when the frequency
entered here is exceeded during
acceleration.
(Setting range: 0Hz–360Hz)
The digital output terminal 11 or 12
configured as OD will be activated
C 44
when the difference between the set
C 44
value and actual value exceeds the
value entered here (when PID control
is activated). (Setting range: 0–100%
of the maximum set value).
Standard
setting
01
00
00
01
01
01
Inverter
rated
current
0.0
0.0
3.0