Section 3: Venting

Montigo supplies a variety of direct venting and termination options.
The direct vent termination location MUST be selected such that it is the
highest point in the venting assembly. It should also be selected such
that it provides the shortest vent run possible. Should it be impossible
to ensure that the termination is the highest point or to meet the
venting guidelines laid out below please contact your Montigo dealer
to discuss power venting options.
Notes For Planning Venting:
• Venting can originate from the unit through the top or through the rear
• Venting can terminate through the roof or through an exterior wall.
• Refer to Appendix A - Termination Locations to ensure the planned
termination location is acceptable.
• Once the termination location has been established, refer to the
appropriate section below for installation details
• All fireplaces shipped from the factory are top vent.
• Silicone application is NOT required when joining Montigo vent
pipes and components.
Section 3-1: Converting to Rear Vent
Use the following instructions to convert a unit for Rear Vent use:
1. Remove the rear flue cover and gasket (5" and 8") on the flue
outlet, as shown in Figure 5.
2. Next, remove the top flue collar (5" and 8") on the flue outlet, as
shown in Figure 5.
3. Install the (removed) rear flue cover and gasket material, to the
top vent outlet. Fasten the cover with included hardware, as
illustrated Figure 5.b
4. Install the (5" and 8") collars to the rear vent outlet using the
included hardware, as illustrated Figure 5.b
Flue Gasket
Flue Gasket
Flue Cover Plate
Flue Cover Plate
Figure 5. Flue cover and collar removal, Top Vented fireplace.
12
5" Inner Flue Collar
5'' Outer Flue Collar
8'' Outer Flue Collar
8" Outer Flue Collar
8" Outer Flue Collar
8'' Outer Flue Collar
5" Inner Flue Collar
5'' Outer Flue Collar
Figure 5.b Flue cover and collar installation, Rear Vented fireplace.
Section 3-1-1: Converting to 5"/ 8" Venting
(For P52, PL52)
P52 AND PL52 UNITS CANNOT BE REAR VENTED STRAIGHT THROUGH
THE WALL. REAR VENT APPLICATIONS MUST BE MULTI-ELBOW.
(VERTICAL VENT RUNS OVER 8' FROM TOP OF UNIT ONLY)
1. Use the following instructions to convert a PL52DF* and P52DF*
from 5"/ 10" to 5"/ 8" venting for top vent use figure 6.e on page 13.
2. Remove the 10" outer flue collar on the flue outlet, from the
desired vent start - TOP or REAR
3. Install the separately ordered 8" reducing collar (RVA108) on the
Top or Rear vent outlet.
NOTE: If power venting, vent run must be reduced to 5"/8" or 4"/7".
contact your Montigo dealer to discuss power venting options.
NOTICE
Under no circumstances can Montigo flex venting be cut to
accommodate an installation. Use an alternative length to complete
your vent run.