installation
Venting Arrangements -
The shaded area in the diagram shows all allowable
combinations of straight vertical and offset to vertical
terminations, using two 90
o
venting systems for propane. Two 45
90
elbow. Maximum of four 45
o
Please note min. 1 foot between 90
elbows is required.
•
Vent must be supported at offsets.
•
Firestops are required at each floor level and
whenever passing through a wall.
•
Maintain clearances to combustibles as listed in
the "Clearances" section.
•
Refer to the "Vent Restrictor Position" section for
details on how to change the vent restrictor from
the factory setting of Set 1 to Set 4 or Set 5
if required.
Note: Must use optional flue adaptor when using
Rigid Pipe (Part # 770-994).
36
Regency Horizon ® HZ54E-11 Gas Fireplace
|
Allowable Vertical Terminations for HZ54E-LP
elbows, with rigid/flex pipe
elbows equal to one
o
elbows allowed.
o
o
2
4
0
40
38
36
34
32
30
Vent Restrictor on Set 5
28
26
24
22
Vent Restrictor on Set 4
20
18
16
14
12
10
8
6
4
2
0
Max. 10' (3m)(centerline to centerline)
Minimum length of pipe
between elbows 12" (305mm)
Horizontal (Feet)
8
6
10
12
Vent Restrictor on Set 1
(factory setting)
14
18
16
20