Pepperl+Fuchs HiC5861 System Manual page 39

Isolated barriers and termination boards
Hide thumbs Also See for HiC5861:
Table of Contents

Advertisement

H-System – Isolated Barriers and Termination Boards
Technical Specifications
Mechanical Data
Mounting
Termination boards: Snap-on 35 mm DIN mounting rail according to EN 60715.
Can be mounted horizontally or vertically.
Isolated barriers: mounting on termination board via Quick Lok Bar
Housing Material
Termination boards:
Polycarbonate (PC)
Polycarbonate (PC), glass fiber reinforced
Isolated barriers: Polycarbonate (PC)
Dimensions
Dimension drawings please refer to Dimensions section.
Degree of Protection
Termination boards:
without isolated barriers IP00 according to EN 60529
with isolated barriers plugged IP20 according to EN 60529
Isolated barriers: IP20 according to EN 60529
Connection to Termination Board
Field side:
Screw terminals: 0.25 to 1.5 mm
Observe the tightening torque of the terminal screws. The tightening torque
is 0.5 Nm to 0.6 Nm.
Pluggable screw terminals: 0.25 to 2.5 mm
Observe the tightening torque of the terminal screws. The tightening torque
is 0.5 Nm to 0.6 Nm.
Spring terminals: 0.25 to 1.5 mm
Power supply and fault indication output:
Screw terminals: 0.25 to 1.5 mm
Observe the tightening torque of the terminal screws. The tightening torque is
0.5 Nm to 0.6 Nm.
Spring terminals: 0.25 to 1.5 mm
Control side:
Screw terminals: 0.25 to 1.5 mm
Observe the tightening torque of the terminal screws. The tightening torque is
0.5 Nm to 0.6 Nm.
Spring terminals: 0.25 to 1.5 mm
Control-system specific connector: Sub-D connector
Fire Protection Class
Housing: V2 according to UL 94 standard. Unless stated otherwise all details relate to the
reference conditions.
2
(24 ... 12 AWG)
2
(24 ... 12 AWG)
2
(24 ... 12 AWG)
2
(24 ... 12 AWG)
2
(24 ... 12 AWG)
2
(24 ... 12 AWG)
2
(24 ... 12 AWG)
39