Additionally, the following parts may belong to the documentation, if applicable: • EU-type examination certificate • EU declaration of conformity • Attestation of conformity • Certificates • Control drawings • FMEDA report • Assessment report • Additional documents For more information about Pepperl+Fuchs products with functional safety, see www.pepperl-fuchs.com/sil.
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Introduction Safety Information Target Group, Personnel Responsibility for planning, assembly, commissioning, operation, maintenance, and dismounting lies with the plant operator. Only appropriately trained and qualified personnel may carry out mounting, installation, commissioning, operation, maintenance, and dismounting of the product. The personnel must have read and understood the instruction manual and the further documentation.
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Introduction Symbols Used This document contains symbols for the identification of warning messages and of informative messages. Warning Messages You will find warning messages, whenever dangers may arise from your actions. It is mandatory that you observe these warning messages for your personal safety and in order to avoid property damage.
Product Description Validity This manual is only valid for devices with a part number greater than #310000. Contact your Pepperl+Fuchs representative for information about older devices. Function KCD2-STC-1(.SP) This signal conditioner provides the galvanic isolation between field circuits and control circuits.
Safety relevant interfaces: input I, output I • Non-safety relevant interfaces: none The HART communication is not relevant for functional safety. Note For corresponding connections see datasheet. Marking Pepperl+Fuchs Group Lilienthalstraße 200, 68307 Mannheim, Germany Internet: www.pepperl-fuchs.com KCD2-STC-1(.SP) Up to SIL 2 KCD2-STC-Ex1(.SP) HiC2025(A)
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Planning Planning System Structure 3.1.1 Low Demand Mode of Operation If there are two control loops, one for the standard operation and another one for the functional safety, then usually the demand rate for the safety loop is assumed to be less than once per year.
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Planning Assumptions The following assumptions have been made during the FMEDA: • Failure rate based on the Siemens standard SN 29500. • Failure rates are constant, wear is not considered. • External power supply failure rates are not included. •...
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Planning Safety Function and Safe State Safety Function The device transfers analog signals from the input to the output with a tolerance of 2 % related to the full signal range. Use the following DIP switch settings for safety-relevant applications: DIP Switch Settings KCD2-STC-(Ex)1(.SP) Function Current source 4 mA to 20 mA...
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Planning Characteristic Safety Values Parameters Characteristic values Assessment type Full assessment Device type Mode of operation Low demand mode or high demand mode Safety function Transfer of the analog signals 0 FIT 163 FIT 40.9 FIT ...
As noted in DIN EN 61508-2:2011 note N3, appropriate measures taken by the manufacturer and plant operator can extend the useful lifetime. Our experience has shown that the useful lifetime of a Pepperl+Fuchs product can be higher if the ambient conditions support a long life time, for example if the ambient temperature is significantly below 60 °C.
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Mounting and Installation Mounting and Installation Mounting and Installing the Device Observe the safety instructions in the instruction manual. Observe the information in the manual. Observe the requirements for the safety loop. Connect the device only to devices that are suitable for this safety application. Check the safety function to ensure the expected output behavior.
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Operation Operation Danger! Danger to life from missing safety function If the safety loop is put out of service, the safety function is no longer guaranteed. • Do not deactivate the device. • Do not bypass the safety function. •...
Page 17
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Operation Proof Test Procedure Put out of service the entire safety loop. Protect the application by means of other measures. Prepare a test set-up, see figures below. Test the devices. Verify the current values as given in table below. Set back the device to the original settings for the application after the test.
Page 18
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Operation Active Passive input input HiC2025 Input sensor Input sensor (2-wire Tx (4-wire Tx Current output or loop powered) externally Voltage output or powered) Current sink 4 mA to 20 mA Logic 4 mA to 20 mA solver analog input...
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) Maintenance and Repair Maintenance and Repair Danger! Danger to life from missing safety function Changes to the device or a defect of the device can lead to device malfunction. The function of the device and the safety function is no longer guaranteed. Do not repair, modify, or manipulate the device.
Functional Safety KCD2-STC-(Ex)1(.SP), HiC2025(A) List of Abbreviations List of Abbreviations Emergency Shutdown Failure In Time in 10 Failure Mode, Effects, and Diagnostics Analysis FMEDA Probability of safe failure Probability of dangerous detected failure Probability of dangerous undetected failure ...