Pepperl+Fuchs KCD2-SR-1.LB Safety Manual

Pepperl+Fuchs KCD2-SR-1.LB Safety Manual

Switch amplifier
Hide thumbs Also See for KCD2-SR-1.LB:

Advertisement

PROCESS AUTOMATION
SAFETY MANUAL SIL
Switch Amplifier
KCD2-SR-(Ex)*(.LB)(.SP),
HiC282*
ISO9001
2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the KCD2-SR-1.LB and is the answer not in the manual?

Questions and answers

Summary of Contents for Pepperl+Fuchs KCD2-SR-1.LB

  • Page 1 PROCESS AUTOMATION SAFETY MANUAL SIL Switch Amplifier KCD2-SR-(Ex)*(.LB)(.SP), HiC282* ISO9001...
  • Page 2 Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* With regard to the supply of products, the current issue of the following document is applicable: The General Terms of Delivery for Products and Services of the Electrical Industry, published by the Central Association of the Electrical Industry (Zentralverband Elektrotechnik und Elektroindustrie (ZVEI) e.V.) in its most recent version as well as the supplementary clause: "Expanded reservation of proprietorship"...
  • Page 3: Table Of Contents

    Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Contents 1 Introduction ................ 4 General Information ..................4 Intended Use ....................4 Manufacturer Information................5 Relevant Standards and Directives...............5 2 Planning ................6 System Structure ..................6 2.1.1 Low Demand Mode of Operation .............6 2.1.2 High Demand or Continuous Mode of Operation........6 2.1.3 Safe Failure Fraction ................6 Assumptions ....................7 Safety Function and Safe State..............8...
  • Page 4: Introduction

    (causing disturbances or impairment of safety functions) may cause damage to property, environment or persons for which Pepperl+Fuchs GmbH will not be liable. The devices are developed, manufactured and tested according to the relevant safety standards.
  • Page 5: Manufacturer Information

    KC-devices with spring terminals has the extension ".SP". The KCD2-SR-(Ex)*(.LB)(.SP) is a single device for DIN rail mounting while the HiC282* is a plug-in device to be inserted into a specific Termination Board. Manufacturer Information Pepperl+Fuchs GmbH Lilienthalstrasse 200, 68307 Mannheim, Germany KCD2-SR-1.LB(.SP) KCD2-SR-Ex1.LB(.SP) KCD2-SR-2(.SP) KCD2-SR-Ex2(.SP)
  • Page 6: Planning

    Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Planning Planning System Structure 2.1.1 Low Demand Mode of Operation If there are two loops, one for the standard operation and another one for the functional safety, then usually the demand rate for the safety loop is assumed to be less than once per year.
  • Page 7: Assumptions

    Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Planning Assumptions The following assumptions have been made during the FMEDA analysis: Only one input and one output are part of the considered safety function  (only 2-channel version). The device shall claim less than 10 % of the total failure budget for a SIL2 ...
  • Page 8: Safety Function And Safe State

    Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Planning Safety Function and Safe State The safe state of each channel is "output de-energized", independent of the mode of operation. The safety function has two modes of operation: normal operation (output follows input)  inverted operation (output inverts input) ...
  • Page 9: Characteristic Safety Values

    Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Planning Note! The failure outputs are not safety relevant. Reaction Time The reaction time for all safety functions is < 20 ms. Characteristic Safety Values Parameters acc. to IEC 61508 Values Assessment type and Full assessment documentation Device type Mode of operation...
  • Page 10: Safety Recommendation

    Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Safety Recommendation Safety Recommendation Interfaces The device has the following interfaces. For corresponding terminals see data sheet. Safety relevant interfaces:  KCD2-SR-(Ex)1.LB(.SP), HiC2821: input I, output I, output II KCD2-SR-(Ex)2(.SP), HiC2822: input I, input II, output I, output II Non-safety relevant interfaces: output ERR ...
  • Page 11 Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Safety Recommendation Our experience has shown that the useful life time of a Pepperl+Fuchs product can be higher if there are no components with reduced life time in the safety path (like  electrolytic capacitors, relays, flash memory, opto coupler) which can produce dangerous undetected failures and if the ambient temperature is significantly below 60 °C.
  • Page 12: Installation And Commissioning

    Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Safety Recommendation Installation and Commissioning During installation all aspects regarding the SIL level of the loop must be considered. The safety function must be tested to ensure the expected outputs are given. When replacing a device, the loop must be shut down. In all cases, devices must be replaced by the same type.
  • Page 13: Proof Test

    Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Proof Test Proof Test Proof Test Procedure According to IEC 61508-2 a recurring proof test shall be undertaken to reveal potential dangerous fails that are otherwise not detected by diagnostic test. The functionality of the subsystem must be verified at periodic intervals depending on the applied PFD in accordance with the data provided in this manual.
  • Page 14 Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Proof Test Multimeter KCD2-SR-Ex1.LB (mA) 240 R / 2.5 W 24 V DC Multimeter (mA) 240 R / 2.5 W 24 V DC Multimeter (mA) Multimeter (mA) 24 V DC Zone 0, 1, 2 Zone 2 Power I supply Supply...
  • Page 15 Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Proof Test Termination Board Multimeter HiC2822 ( mA ) 240 R / 2.5 W 24 V DC Multimeter (mA) Multimeter ( mA ) 240 R / 2.5 W 24 V DC Multimeter ( mA ) Multimeter (mA) Supply +...
  • Page 16: Abbreviations

    Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Abbreviations Abbreviations Distributed Control System Emergency Shutdown Failure In Time in 10 FMEDA Failure Mode, Effects and Diagnostics Analysis Probability of safe failure  Probability of dangerous detected failure  Probability of dangerous undetected failure ...
  • Page 17 Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Notes...
  • Page 18 Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Notes...
  • Page 19 Safety Manual SIL KCD2-SR-(Ex)*(.LB)(.SP), HiC282* Notes...
  • Page 20 PROCESS AUTOMATION – PROTECTING YOUR PROCESS Worldwide Headquarters Pepperl+Fuchs GmbH 68307 Mannheim · Germany Tel. +49 621 776-0 E-mail: info@de.pepperl-fuchs.com For the Pepperl+Fuchs representative closest to you check www.pepperl-fuchs.com/contact www.pepperl-fuchs.com Subject to modifications Copyright PEPPERL+FUCHS • Printed in Germany DOCT-1595H 09/2014...