Pepperl+Fuchs HiC5861 System Manual page 38

Isolated barriers and termination boards
Hide thumbs Also See for HiC5861:
Table of Contents

Advertisement

H-System – Isolated Barriers and Termination Boards
Technical Specifications
Conformity
General
Isolated barriers with explosion protection, preferably Ex ia IIC/Class I, Div. 1,
international approvals
EMV according to
EN 61326-1
EN 61326-3-2, only for devices with SIL rating, where the datasheet mentions
this standard.
If you operate the device with a DC supply voltage, you must ensure that the bridging
of the 20 ms voltage interruption is realized by the power supply.
NAMUR NE 21
If you operate the device with a DC supply voltage, you must ensure that the bridging
of the 20 ms voltage interruption is realized by the power supply.
RoHS, refer to declaration of conformity of the respective device
LEDs according to NAMUR NE 44
Software according to NAMUR NE 53
Digital Inputs and Outputs according to NAMUR
IEC/EN 60947-5-6: Low voltage switch gear and control gear – part 5 and 6:
Control devices and switching elements – DC interface for proximity sensors
and switch amplifiers (NAMUR), 1999
Ambient Conditions
Ambient Temperature
-20 °C to 60 °C (-4 °F to 140 °F), exceptions see datasheets
Storage Temperature
-40 °C to 85 °C (-40 °F to 185 °F), exceptions see datasheets
Reference Conditions for Adjustment
20 °C (68 °F)
Relative Humidity
max. 95 % without moisture condensation
Corrosive gas durability
according to ISA-S71.04, group A, severity level G3 (harsh)
Altitude
max. 2000 m
Vibration Resistance
according to EN 60068-2-6, 10 Hz to 150 Hz, 1 g, high crossover frequency
Shock Resistance
according to EN 60068-2-27, 15 g, 11 ms, half-sine