H-System – Isolated Barriers and Termination Boards

Commissioning

4
Commissioning
4.1

Configuration of the Isolated Barriers

Danger!
Explosion hazard from sparking when using operating elements
Using operating elements in a potentially explosive atmosphere can cause sparks
that can ignite the surrounding atmosphere.
Only use operating elements (e. g., switch, slider, button, etc.) in the absence of a potentially
explosive atmosphere.
Caution!
Fault in the plant
Changing the device data changes the device function.
Before entering new device data, make sure the plant is not endangered by changing
the device data.
The devices are configured using DIP switches.
Configuring the Isolated Barrier
Set the DIP switches on the device side as follows:
1.
Remove the isolated barriers from the termination board as described in the Dismounting
section.
2.
Set the DIP switches as described in the Configuration section of the datasheet.
3.
Mount the device as described in the Mounting section.
Note
See corresponding datasheets for further information.