Hazard information
Please take the technical data (in particular the
maximum permissible switching capacity of the
relay and the type of load to be connected) into
account before connecting a load! Do not exceed
the capacity specified for the device.
Exceeding this capacity could lead to the de-
struction of the device, fires or electric shocks.
The circuit to the which the device and the load
will be connected has to be secured by a cable
protection switch in accordance with EN60898-1
(tripping characteristic B or C, max. 10 A rated
current, min. 6 kA interrupting rating, energy lim-
iting class 3). Installation regulations according to
VDE 0100 and HD382 or 60364 have to be con-
sidered. Users must be able to easily access the
cable protection switch. This must be marked as
disconnecting device for the actuator.
Before the actuator is connected, remove the
fuse from the fuse box.
Except for configuration, the device may only be
operated with an associated switch cover.
The device has not been designed to support
safety disconnection.