F013-P FLOWRATE MONITOR / TOTALIZER WITH HIGH / LOW FLOWRATE ALARMS Signal input flowmeter: pulse, namur and coil. Alarm output: one flowrate alarm. Options: Intrinsically Safe. F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries...
Compatibility). Do connect a proper grounding to the aluminum casing as indicated if the F013-P has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back-casing and removable terminal-block may never be removed.
This operation manual describes the standard unit as well as most of the options available. For additional information, please contact your supplier. A hazardous situation may occur if the F013-P is not used for the purpose it was designed for or is used incorrectly. Please carefully note the information in this operating manual indicated by the pictograms: A "warning"...
Safety rules and precautionary measures ....................... 2 About the operation manual ..........................3 Contents manual .............................. 4 Introduction ..........................5 1.1. System description of the F013-P ..................5 Operational ..........................6 2.1. General ..........................6 2.2. Control panel .......................... 6 2.3.
Fig. 1: Typical application for the F013-P. Configuration of the unit The F013-P has been designed to be implemented in many types of applications. For that reason, a SETUP-level is available to configure your F013-P according to your specific requirements.
Take careful notice of the " Safety rules, instructions and precautionary measures " in the front of this manual. This chapter describes the daily use of the F013-P. This instruction is meant for users / operators. 2.2. CONTROL PANEL The following keys are available: Fig.
SETUP-settings. The signal generated by the connected flowmeter is measured by the F013-P in the background, whichever screen refresh rate setting is chosen. After pressing a key, the display will be updated very quickly during a 30 second period, after which it will slow-down again.
Page 8
Page 8 • Programming the flowrate alarm values Note: This function might not be accessible due to a configuration setting. When the SELECT-key is pressed a few times, following flowrate alarm values are displayed: low flowrate alarm: enter here 40 L/min for example, high flowrate alarm: enter here 200 L/min for example, To change the alarm value, the following procedure must be executed: press PROG: the word "PROGRAM"...
Operating Manual before carrying out its instructions. The F013-P may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
Page 10
Page 10 Matrix structure SETUP-level: SCROLLING THROUGH SETUP-LEVEL Selection of function-group and function: SETUP is divided into several function groups and functions. Each function has a unique number, which is displayed below the word "SETUP" at the bottom of the display. The number is a combination of two figures. The first figure indicates the function-group and the second figure the sub-function.
Page 11
Page 11 To change or select a value: To change a value, use to select the digits and to increase that value. If the new value is invalid, the increase sign or decrease-sign will be displayed while you are programming.
Page 13 3.2.3. EXPLANATION OF SETUP-FUNCTIONS 1 - TOTAL SETUP - 11 determines the measurement unit for total and accumulated MEASUREMENT UNIT total. The following units can be selected: L - m3 - kg - lb. - GAL - USGAL - bbl - _ (no unit). Alteration of the measurement unit will have consequences for operator and SETUP-level values.
Page 14 2 - FLOWRATE The settings for total and flowrate are entirely separate. In this way, different units of measurement can be used for each e.g. cubic meters for total and liters for flowrate. The display update time for flowrate is one second or more. Note: these settings also influence the alarm output functions.
If a LED backlight has been supplied, the color can be selected. BACKLIGHT Following selections are available: (OPTION) OFF - GREEN - AMBER In case the F013-P generates a flowrate alarm, the backlight can be set to BACKLIGHT ALARM change to red. Following selections are available: (OPTION) OFF: during flowrate alarm the color is according to setting 43 during flowrate alarm the color is red.
When used with the internal battery option, the user can expect reliable measurement over a long period of time. The F013-P has several smart power management functions to extend the battery life time significantly. Two of these functions can be set:...
For support and maintenance it is important to have information about the TYPE OF MODEL characteristics of the F013-P. Your supplier will ask for this information in the case of a serious breakdown or to assess the suitability of your model for upgrade considerations.
Operating Manual before carrying out its instructions. The F013-P may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
• This unit must be installed in accordance with the EMC guidelines (Electro Magnetic Compatibility). • Do ground the aluminum casing properly as indicated, if the F013-P has been supplied with the 115-230V AC power-supply type PM. The green / yellow wire between the back-casing and removable terminal-block may never be removed.
The input signal type has to be selected with the correct SETUP-function (read par. 3.2.3.) The F013-P is suitable for use with flowmeters which have a coil output signal. Two sensitivity levels can be selected with the SETUP-function: COIL LO: sensitivity from about 90mVp-p.
Page 23
Page 23 Pulse-signal NPN / NPN-LP: The F013-P is suitable for use with flowmeters which have a NPN output signal. For reliable pulse detection, the pulse amplitude has to go below 1.2V. Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input frequency - read par. 3.2.3.
Page 24
Common ground unit NAMUR-signal: The F013-P is suitable for flowmeters with an Namur signal. The standard F013-P is not able to power the Namur sensor, as an external power supply for the sensor is required. However, a 8.2V sensor supply voltage (terminal 6) can be provided with type PD.
For Intrinsically Safe applications: read chapter 5. The following terminal connectors are available: POWER SUPPLY ALARM OUTPUT SENSOR SIGNAL TYPE: TYPE: TYPE: P: PF / PM OA-OR-OT PULSE INPUT SIGNAL Fig. 10: Overview of terminal connectors F013-P-(PF / PM) and options. HF013PEN_v0402_03 Atex_IECEx_CSA_FM...
Page 26
Page 26 SENSOR SUPPLY Type PF-PM: Sensor supply: 1.2, 3.2V, 8.2V, 12V or 24 V: With this option, a real power supply for the sensor is available. The flowmeter can be powered with 1.2, 3.2, 8.2, 12 or 24 V DC (max. 400mA@24V). The voltage is selected with the three switches inside the enclosure.
Page 27
The input signal type has to be selected with the correct SETUP-function (read par. 3.2.3.) Coil-signal: The F013-P is suitable for use with flowmeters which have a coil output signal. Two sensitivity levels can be selected with the SETUP-function: COIL LO: sensitivity from about 90mVp-p.
Page 28
Common ground unit Pulse-signal NPN / NPN-LP: The F013-P is suitable for use with flowmeters which have a NPN output signal. For reliable pulse detection, the pulse amplitude has to go below 1.2V. Signal setting NPN-LP employs a low-pass signal noise filter, which limits the maximum input frequency - read par. 3.2.3.
Page 29
Common ground unit Reed-switch: The F013-P is suitable for use with flowmeters which have a reed-switch. To avoid pulse bounce from the reed-switch, it is advised to select REED LP - low-pass filter (read par. 3.2.3.) Reed - switch signal input...
Safety Instructions Certificates, safety values, control drawing and declaration of compliance can be found in the document named: “Fluidwell F0..-P-XI - Documentation for Intrinsic Safety”. For installation under ATEX directive: this intrinsically safe device must be installed in accordance with the Atex directive 94/9/EC and the product certificate KEMA 05ATEX1168 X.
FWCD-0003. Tamb CSA Certificate nr: CSA.08.2059461 – FM Project ID: 3033306 -40°C ... +70°C Made in Veghel, The Netherlands by Fluidwell bv -40°F ... +158°F KEMA 05ATEX1168 X Battery powered applications: II 1 G Ex ia IIC T4 Replace with certified II 1 D Ex iaD 20 IP 65 / 67 T 100°C...
PX will power the unit; the battery will be disabled automatically till power is disconnected. Fig. 15: Configuration example Intrinsically Safe. Configuration example no. 2 Configuration example IIA - IIB and IIC application - F013-P-OT-PX-XI-(ZB) HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS...
Page 33
Page 33 Configuration example no. 3 Configuration example IIA - IIB and IIC application - F013-P-OT-PX-XI-ZB HAZARDOUS AREA SAFE AREA TERMINAL CONNECTORS F0-series = max. 30 V Power supply Supply backlight = max. 200 mA Backlight option: type ZB For example = max.
Operating Manual before carrying out its instructions. The F013-P may only be operated by personnel who are authorized and trained by the operator of the facility. All instructions in this manual are to be observed.
Page 36 APPENDIX A: TECHNICAL SPECIFICATION GENERAL Display Type High intensity reflective numeric and alphanumeric LCD, UV-resistant. Digits Seven 17mm (0.67") and eleven 8mm (0.31"). Various symbols and measuring units. Refresh rate User definable: 8 times/sec - 30 secs. Type ZB (option) Tri-color configurable LED-backlight - green, amber with red flashing during alarm.
Page 37
Page 37 Sensor excitation Type PB / PC / PX Sensor supply voltage: 3.2V DC for pulse signals and 1.2V DC for coil pick-up. Please note: this is not a real sensor supply. Only suitable for sensors with a very low power consumption like coils (sine wave) and reed-switches.
Page 38
Page 38 OUTPUT Alarm output Function high, low or high and low flowrate alarm. Type OT One passive transistor output - not isolated. Load max. 50V DC - 300mA. Type OA One active 24V DC transistor output; max. 400mA per output (requires type PF or PM). Type OR One mechanic relay output;...
Page 39 APPENDIX B: PROBLEM SOLVING In this appendix, several problems are included that can occur when the F013-P is going to be installed or while it is in operation. Flowmeter does not generate pulses: Check: Signal selection SETUP - 61, ...
Page 40 INDEX OF THIS MANUAL accumulated total hardware version active pulse signal 24, 29 high alarm output actual settings installation alarm intrinsic safety alarm output function Intrinsic safety alarm values IP classification delay time alarm keys display flow zero low-battery set alarm operator level main-function...
Page 43
Page 43 NOTES LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE : DATE : 1 - TOTAL Enter your settings here 11 unit 12 decimals 0000000 13 K-factor 0000001 14 decimals K-factor HF013PEN_v0402_03 Atex_IECEx_CSA_FM...
Page 44
74 pass code 0000 75 tagnumber 0000000 Fluidwell bv HF013PEN_v0402_03 Atex_IECEx_CSA_FM PO box 6 Voltaweg 23 Website: www.fluidwell.com 5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives The Netherlands The Netherlands Copyright Fluidwell bv - 2012 - HF110AEN_v0501_03...