Page 1
User Manual F011-P TOTALIZER Signal input: pulse, NAMUR or coil flowmeter signal Options: intrinsically safe backlight F-Series - Field mounted indicators for safe and hazardous areas More info: www.fluidwell.com/fseries...
User Manual F011-P TABLE OF CONTENTS ABOUT THIS MANUAL......................How to use this manual ....................Use of pictograms ......................Warranty and technical support ..................Model Reference ......................SAFETY ............................ Personal safety ....................... End-user responsibilities....................Potential equipment damage ..................Disposal of electronic waste ................... INTRODUCTION........................
Page 3
F011-P User Manual INTRINSICALLY SAFE APPLICATIONS ................33 Identification........................33 Electrical installation in hazardous areas................ 34 7.2.1 Installations based on FM or CSA Certificate ..............34 7.2.2 Electrical data - Control drawing..................35 7.2.3 Installations based on ATEX or IECEx Certificate ............36 7.2.4 Electrical data - Annex 1....................
● incorrect functioning of the unit or connected instruments. A note informs you of important information. WARRANTY AND TECHNICAL SUPPORT For warranty and technical support on your Fluidwell products, visit our internet site www.fluidwell.com or contact us at support@fluidwell.com. MODEL REFERENCE Hardware version: 03.03.xx...
F011-P User Manual SAFETY PERSONAL SAFETY ● Explosion hazard: Never open the unit when explosive atmosphere is present, and the unit is connected to a power supply or consuming device like the internal battery supply. ● Risk of electric shock: Only open the unit if all leads are free of potential electrical energy. ●...
User Manual F011-P INTRODUCTION SYSTEM DESCRIPTION The totalizer model F011-P is a microprocessor-driven instrument designed to show a resettable total and a non-resettable accumulated total. Fig. 1: The F011 This manual describes the daily use, configuration and installation of the F011-P with pulse input from a flowmeter and its available options.
F011-P User Manual Options ● Intrinsic safety (Type XI) ● Power and sensor supply (Types PB, PC, PD, PF, PM, PX, in various combinations) ● Panel mount enclosure (Types HB, HC) ● Flame-proof enclosure (Type XF) ● Display backlight (Type ZB). INSTALLATION EXAMPLE Following parts can be recognized in below installation example.
User Manual F011-P OPERATION This unit may only be operated by authorized and trained personnel who have read and understood this manual, particularly Section 2: Safety [»5] INTRODUCTION This chapter describes the daily use and operation of the F011-P. For this, the F-Series is equipped with a control panel that provides the operator with various functions, information and operating modes.
F011-P User Manual Normally, the display is updated depending on the refresh rate selected in the configuration settings. By pressing any key, the display switches to refreshing the information 8 times per second. After 30 seconds of key inactivity, the display returns to the configured refresh rate. ACC.TOTAL Fig. 4: Example of display information during process...
User Manual F011-P CONFIGURATION INTRODUCTION This chapter describes how technicians can use configuration settings to configure the F-Series for optimal functionality. Configuration of the F011-P can be done in SETUP mode, using the front keys. CONFIGURING USING SETUP MODE For an overview of Operating modes, see Section 4.1.1: Operating modes [»8] Changing settings may influence current operation In SETUP mode the unit remains fully operational.
F011-P User Manual 5.2.3 CHANGING CONFIGURATION SETTINGS A menu item either contains a value (a number with optionally a decimal point and sign, e.g. -123.45) or a selection list (e.g. L – m - USGAL). After a menu item is selected in the SETUP menu, a new value can be programmed by performing the following steps.
User Manual F011-P SETUP MENU OVERVIEW TOTAL DEFAULT UNIT L - m3 - kg - lb - GAL - USGAL - bbl - no unit DECIMALS 0 - 3 0.000010 - 9,999,999 K-FACTOR DECIMALS K-FACTOR 0 - 6 DISPLAY DEFAULT BACKLIGHT off - on BACKLIGHT...
F011-P User Manual TOTAL DECIMALS Determines for Total and Accumulated Total the number of decimals. The following can be selected: 0000000 – 111111.1 – 22222.22 – 3333.333 K-FACTOR This value is used to convert the flowmeter pulse signals into a Total. The K-Factor is based on the number of pulses generated by the flowmeter per measurement unit selected in 1.1: TOTAL >...
User Manual F011-P 5.4.4 MENU 4: FLOWMETER FLOWMETER SIGNAL Selects the type of input sensor pickup / signal. The F011-P can process several types of input signal. The settings with LP are used to apply a built-in low-pass filter. FLOWMETER SELECTION CHARACTERISTICS TYPE OF SIGNAL EXPLANATION RESISTANCE...
F011-P User Manual INSTALLATION ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
User Manual F011-P HANDLING THE F011-P ENCLOSURE 6.2.1 IDENTIFICATION The F-Series can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model Type XI. Refer to for identification and installation labels Section 7: Intrinsically safe applications [»33] for Intrinsically Safe applications.
F011-P User Manual Fig. 9: Example of F0-Series installation label (Safe Area - Type PM or PF) Serial number and year of production The serial number can be reviewed on the identification label, the installation label, or in . The production SETUP 5.3: OTHERS >...
Page 18
User Manual F011-P Closing / replacing the cover 1. Re-insert all terminals to their original position. 2. Carefully position the front cover onto the back cover, making sure that the gasket falls nicely into the gutter of the back cover. 3.
F011-P User Manual MECHANICAL INSTALLATION 6.3.1 MECHANICAL DIMENSIONS Aluminum and stainless steel enclosures Note: _B_ type enclosure (extended back) not available under CSA or FM certification for intrinsically safe installation 75 mm (2.95") 90 mm (3.54") 130 mm (5.12") 112 mm (4.40") 12mm 12mm 30 mm 30 mm 30mm 30mm...
Page 20
User Manual F011-P Non-metallic enclosures 75 mm (2.95") 130 mm (5.12") 112 mm (4.40") HK back box: (flat bottom) 75 mm (2.95") 118 mm (4.65”) 25mm 25mm D=20mm D=20mm 12mm 12mm 30mm 30mm 24mm 24mm D=12mm D=16mm D=16mm D=20mm 36mm 36mm 0.12”...
F011-P User Manual 6.3.2 MOUNTING THE F-SERIES The enclosure can be installed by itself or with the aid of a mounting plate in the configurations shown below. When the product is installed on a wall or onto a meter, please use components and installation techniques that are suitable for the used materials.
User Manual F011-P ELECTRICAL INSTALLATION Hazardous area installations The following chapter gives general information regarding the electrical installation of the F011-P. gives additional specific information Section 7: Intrinsically safe applications [»33] regarding intrinsically safe installation and has priority over the information given in this chapter.
F011-P User Manual Connecting Protective Earth to a non-metallic enclosure When the F011-P is supplied with a non-metal enclosure (e.g. plastic), the field mount enclosure meets the requirements of class 2 (double insulated). Therefore any incoming PE conductor can be terminated with an insulating end cap.
User Manual F011-P All field wiring enters the F011-P through the bottom of the enclosure and connects to the circuit assembly inside the enclosure. Wiring is routed through cable glands. Please make sure to order the F011-P with the correct drilling pattern and thread (metal) or hole (plastic) sizes. The wire screens (shield) are meant to prevent electromagnetic interference and shall be terminated at one side to prevent ground loops.
F011-P User Manual Fig. 14: Jumper positions sensor supply voltage selection (Type PF or PM) Jumper setting External sensor supply voltage 1.2 / 3.2V DC 8.2V DC 12V DC 24V DC TERMINAL CONNECTORS SAFE AREA APPLICATIONS - TYPE PX, PD Hazardous area installations The following chapter gives general information regarding the electrical installation of the F011-P.
Page 26
User Manual F011-P ● COIL LO: sensitivity from about 90mV p-p ● COIL HI: sensitivity from about 20mV p-p With Type ZF or ZG still higher sensitivities are available: ● Type ZF: COIL HI sensitivity from about 10mV p-p ● Type ZG: COIL HI sensitivity from about 5mV p-p. Vref 1.2 V DC 3 Coil 2 Coil...
Page 27
F011-P User Manual With Type PD a sensor supply voltage of 8.1V DC can be taken from terminal 6. 6 Type PD: 8.1 V DC 3 +3.2 V DC Selectable low-pass filter 2 Signal Resistance value: 1 Shield see signal selection table Common ground unit Fig. 18: Terminals 1 - 3 (6): PNP signal input...
User Manual F011-P NAMUR signal The F011-P is suitable for use with flowmeters with NAMUR signal. The F011-P with Type PD can offer a sensor supply voltage of 8.2V at terminal 6. 6 Type PD sensor supply +8.1 V DC NAMUR 2 Signal Shield...
F011-P User Manual TERMINAL CONNECTORS SAFE AREA APPLICATIONS - TYPE PF, PM Hazardous area installations This chapter applies to electrical installation of the F011-P with Type PM or PF. These Types are not fit for use in Hazardous Areas! gives specific information regarding intrinsically Section 7: Intrinsically safe applications [»33] safe installation.
User Manual F011-P 6.6.2 TERMINALS 5-7: FLOWMETER INPUT Three basic types of flowmeter signals can be connected to the F011-P: pulse, active pulse or coil. The screen of the signal wire can be connected to the common ground terminal (see Section 6.4.3: Field wiring connections [»23] The input signal type has to be selected with the correct SETUP-function (...
Page 31
F011-P User Manual A sensor supply voltage can be taken from terminal 7. 7 Sensor supply Selectable low-pass filter 6 Signal Shield Resistance value: 5 GND see signal selection table Common ground unit Fig. 27: Terminals 5 -7: PNP signal input Active signal The F011-P is suitable for flowmeters with an Active signal output.
Page 32
User Manual F011-P NAMUR signal The F011-P is suitable for use with flowmeters with NAMUR signal. Terminal 7 provides a selectable sensor supply ( Section 6.4.5: Sensor supply [»24] 7 Sensor supply NAMUR 6 Signal Shield 820 Ω 5 GND Common ground unit Fig. 30: Terminals 5 -7: Namur signal Page 32...
F011-P User Manual INTRINSICALLY SAFE APPLICATIONS IDENTIFICATION The F011-P can be supplied as suitable for Safe Area or Hazardous Area. Suitability for Intrinsic Safety is indicated in the model Type XI. If Type XI is not indicated your unit is not suitable for Intrinsically Safe applications! Identification label To identify your F0-Series device, all field mount enclosures have a waterproof identification label placed on the outside of the product.
User Manual F011-P ELECTRICAL INSTALLATION IN HAZARDOUS AREAS ● shows general information regarding the electrical Section 6.4: Electrical installation [»22] installation of your F011-P. The following sections give additional specific information regarding Intrinsically Safe installation, and overrules information given in other sections. ●...
F011-P User Manual 7.2.2 ELECTRICAL DATA - CONTROL DRAWING trol Dr ing F -P-XI Ce t r ific t a ion F0-SERIES – Type -XI T RMINAL CONNE CTORS F0 ERIE c mm on ground Ce tif r ica e number: CSA.08.2059461 Intr ins call S y afe for Class I/II/III, Division 1...
User Manual F011-P 7.2.3 INSTALLATIONS BASED ON ATEX OR IECEX CERTIFICATE Installation instructions ● For installation under ATEX directive: this Intrinsically Safe device must be installed in accordance with ATEX directive 2014/34/EU and product certificate KEMA 05ATEX1168 X. ● For installation under IECEx scheme: this Intrinsically Safe device must be installed in accordance with product certificate IECEx KEM 08.0006X.
F011-P User Manual 7.2.4 ELECTRICAL DATA - ANNEX 1 Annex 1 ( mo el p s eci fic) to prod uct certif c i ates KEMA 0 ATEX1168 X, IECEx 00 6 Model F0..-P-XI Int nal supply for use w ith he cert ified replaceable battery type FW -Li A...
User Manual F011-P 7.2.5 POWER SUPPLY The F011-P can be powered from an external power supply. For Types PX or PD, an optional internal power supply is also available in the form of an intrinsically safe lithium primary battery (Type PC). When both external and internal power supplies are available, the internal power supply is interrupted and will serve as a backup supply.
F011-P User Manual Optional battery – Type PC With Type PC your product is equipped with an intrinsically safe, certified long-life Lithium primary battery. The battery will power the F011 when external power is not available, and may be exchanged in hazardous areas. For further information please see Section 8.3: Battery replacement [»43] All electrical connections made to the terminals of the intrinsically safe product (Type XI) must follow...
User Manual F011-P 7.4.2 F011-P-PX-XI-(ZB) - EX IA IIC/IIIC Fig. 35: F011-P-PX-XI-(ZB) - Ex ia IIC/IIIC - Intrinsically Safe application Sensor supply voltage on Terminal 3: 1.2-3.2V DC. Please note: Type PX may be used in combination with the battery (Type PC). PX will power the F011-P, the battery will be disabled automatically until the power is disconnected 7.4.3 F011-P-PX-XI-ZB - EX IA IIC/IIIC...
F011-P User Manual 7.4.4 F011-P-PD-XI-ZB - EX IA IIC/IIIC Fig. 37: F011-P-PD-XI-ZB - Ex ia IIC/IIIC - Intrinsically Safe application Sensor supply voltage on Terminal 3: 1.2-3.2 V DC, Terminal 6: 8.2 V DC. Please note: Type PD may be used in combination with the battery (Type PC). PD will power the F011-P, the battery will be disabled automatically until the power is disconnected FW_F011-P_M_v0501-03_EN Page 41...
User Manual F011-P MAINTENANCE GENERAL DIRECTIONS ● Mounting, electrical installation, start-up and maintenance of this instrument may only be carried out by trained personnel authorized by the operator of the facility. Personnel must read and understand this Operating Manual before carrying out its instructions. ●...
User Manual F011-P 8.3.2 BATTERY REPLACEMENT PROCEDURE Before starting the battery replacement procedure, make sure that the marking on the new battery corresponds with the type of installation, as shown in Section 8.3.1: Safety instructions [»43] When used in Intrinsically Safe applications - Type PC: The hook-and-loop fastener that holds the battery is antistatic and thus fit for Hazardous Area use.
F011-P User Manual APPENDIX A - TECHNICAL SPECIFICATION GENERAL DISPLAY Type High intensity reflective numeric and alphanumeric LCD, UV-resistant Digits 7 with height 17mm (0.67”) and 11 with height 8mm (0.31”). Various symbols and measuring units. Dimensions 90 x 40 mm (3.5” x 1.6”) Refresh rate User definable: fast - 1 sec - 3 sec - 15 sec - 30 sec - off Type ZB (option)
Page 46
User Manual F011-P OPERATING TEMPERATURE Safe area -40 °C to +80 °C, -40 °F to +176 °F Intrinsically safe -40 °C to +70 °C, -40 °F to +158 °F For EPL Da -40 °C to +50 °C, -40 °F to +122 °F POWER REQUIREMENTS Type PB SAFE AREA ONLY - Standard lithium primary battery.
F011-P User Manual HAZARDOUS AREA (TYPE XI OR XF) Intrinsically safe ATEX appr. KEMA 05ATEX1168 X IECEx appr. IECEx KEM 08.0006X Type XI II 1 G Ex ia IIC T4 Ga Ex ia IIC T4 Ga II 1 D Ex ia IIIC T 100ºC Da Ex ia IIIC T 100ºC Da...
User Manual F011-P APPENDIX B - TROUBLESHOOTING Table 1 lists and describes how to troubleshoot problems that can occur when installing or operating the F011-P. Table 2 lists internal alarm codes and conditions signaled by a blinking ALARM flag on the display ).
DECLARATIONS OF CONFORMITY EU De cla tio n of Conformi Fluidwell F0‒Series indicators he , February 2022 We, Fluidwell BV, declare under our s e ol respons ibility that the F0 ‒Series indicators are de igne d and will operate conform the following applicable European...
Page 50
User Manual F011-P LIST OF CONFIGURATION SETTINGS SETTING DEFAULT DATE: DATE: TOTAL UNIT DECIMALS K-FACTOR DECIMALS K-FACTOR DISPLAY BACKLIGHT BACKLIGHT BRIGHTNESS POWER MANAGEMENT LCD UPDATE 1 sec BATTERY MODE operational FLOWMETER SIGNAL coil_lo OTHERS TYPE / MODEL F011-P SOFTWARE VERSION 03.xx.xx SERIAL NUMBER xxxxxxx...
Page 51
F011-P User Manual NOTES FW_F011-P_M_v0501-03_EN Page 51...