Fire detection & alarm system control panel v3 (74 pages)
Summary of Contents for Fike FCP-75
Page 1
Addressable Fire Alarm Control Panel FCP-75 Manual Document LS10147-003FK-E 6/20/2022 P/N LS10147-003FK-E:B • ECN 00003636...
Page 2
Adequate written records of all rise feature of each detector should be tested at least once per year inspections should be kept. by a qualified fire protection specialist. Heat detectors are designed Limit-F-2020 to protect property, not life. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 4
Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Section 4: Control Panel Installation ..........................20 4.1: Mounting the Control Panel Cabinet ................................20 4.1.1: Preventing Water Damage..................................20 4.1.2: Removing the FCP-75 Assembly from the Housing ..........................20 4.1.3: Dead Front Installation and Removal ..............................20 4.2: Board Assembly Diagram....................................22 4.3: Wiring Specifications.......................................22 4.4: AC Power Connection .....................................23...
Page 6
7.4.2: Moving through the Menus ..................................63 7.4.3: Selecting Options and Entering Data..............................63 7.5: Programming Menu Quick Reference ................................63 Section 8: Programming ..............................70 8.1: UL 864 Programming Requirements ................................70 8.2: Modules ...........................................70 8.2.1: Edit Modules......................................70 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 7
9.7: Smoke Alarm Verification ....................................98 9.8: Function Keys .........................................98 9.8.1: Recording an F-Key Macro ..................................98 9.8.2: Aborting an F-Key Macro Recording Session............................98 9.8.3: Erasing an F-Key Macro..................................98 9.8.4: Using a Recorded F-Key Macro ................................99 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 8
9.8.6: F-Key Map Inhibit ....................................99 Section 10: Reporting ..............................100 10.1: Receivers Compatible with the Control Panel.............................100 10.2: SIA / FCP-75 Panels PI Modifier Reporting ...............................109 10.3: SIA– FCP-75 Panel Communicator................................110 Section 11: Testing and Troubleshooting........................111 11.1: Troubleshooting ......................................111 11.2: Troubleshooting Common Problems ................................
• The FCP-75 is capable of outputting 2.5A of output power during an alarm activation through 2 sets of terminals for the notification appliance circuits or an auxiliary application. Each circuit is power-limited and can source up to 2.5A during an alarm activation. The constant auxiliary power load must not exceed 1A for normal standby.
About this Manual 1.2 About this Manual This manual is intended to be a complete reference for all installation and operation tasks for the FCP-75. 1.2.1 Terms Used in this Manual The following terminology is used with the FCP-75 system:...
For communication and panel programming with a Windows-based computer. Enables Tool remote viewing of detector status and event history. 7860 Telephone Cord RJ31X cord for connecting phone line to the FCP-75. 7628 UL Listed End-of-line resistor Table 1.2 FCP-75 Compatible Products (Continued) 1.4 Related Documentation...
14. If your facility has specially wired alarm equipment connected to the telephone line, ensure the installation of this FCP-75 does not disable your alarm equipment. If you have questions about what will disable alarm equipment, consult your Telephone Company or qualified installer.
Use both phone lines. Enable phone line monitors for both lines. You must program a phone number and a test time so that the FCP-75 shall automatically initiate and complete a test signal transmission sequence to its associated receiver at least once every 6-hours, using two phones or one phone line with Ethernet backup.
Fiber modules Y = YES, N = NO, O = OPTIONAL Note: Y * = You must include the FIK-RPS1000 or FIK-5496 for releasing purposes. Table 2.1 NFPA Requirement for Minimum System Configuration for FCP-75-75 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
FCP-75 panel for the first time. 3.1 Inventory When the FCP-75 shipment is received, check that all the parts have been included in the shipment. The shipment consists of one of each of the following: •...
Filling in the Current Draw Worksheet, Table 3.2 For the FCP-75, the worst case current draw is listed for the panel, addressable devices, and SLC expanders. Fill in the number of addressable devices and expanders that will be used in the system and compute the current draw requirements for alarm and standby.
Page 17
ISO-6 (6 Fault Isolator Module) Standby: (per circuit) 0.45 mA Isolation: (per circuit) 17 mA Accessories Modules FIK-RA2000 Remote LCD Standby: 27 mA Annunciator Alarm: 53 mA Table 3.2 Current Draw Worksheet for IDP SLC Devices (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 18
However, during normal operation, door holders draw current and must be included in the 1.8 A total current that can be drawn from the panel. Use next size battery with capacity greater than required. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 19
Maximum Battery Standby Load Table 3.3 shows the maximum battery standby load for the FCP-75 based on 24 and 60 hours of standby. The standby load calculations of line G in the Current Draw Calculation Worksheet (Table 3.2) must be less than the number shown in Table 3.3 for the battery size used and standby hours required.
The FCP-75 cabinet base dimensions are: 12.531” W x 14.875” H. The FCP-75 panel should be located within a secured area, where it is accessible to the main drop wiring runs and where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear alarms and troubles. When you select a location, keep in mind that the panel itself is the main source of alarm and trouble annunciation.
Page 21
Remove the two screws and star washers from the bottom of the cabinet. Remove the dead front panel from the control panel cabinet. Reinstall the top two annunciator screws to secure to the board. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED • AC power for the FCP-75 is rated at 120VAC, 60Hz, 1.5A. AC power for the FCP-75HV is rated at 240VAC, 50/60Hz, 1A. •...
Connect the jumper wire provided (P/N 140694) from the positive (+) side of Battery #2 to the (–) negative side of Battery #1. Connect the red wire from the control panel positive (+) terminal to the positive (+) side of Battery #1. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
• If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no more than 18" away from the main control panel cabinet. This will ensure that the battery cables reach the battery terminals. cabinet mounting holes Figure 4.7 RBB Cabinet Mounting Holes FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Figure 4.10 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment 4.6 Wiring Specifications 4.6.1 Length Limitations This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class A and B). FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
The optional model FIK-RA100 Remote Annunciator, is shown in Figure 4.12. The FIK-RA100 can be surface or flush mounted. Up to eight FIK-RA100 annunciators can be added to the FCP-75 system in any combination. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Remove knockout holes as needed for wires. There are 10 knockouts available, two on each side and two in the back of the cabinet. Wire the annunciator board to the main control panel. Refer to Figure 4.3. Attach the annunciator and door assembly to backbox as shown below using the supplied screws. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 30
Run wires to the control panel. Refer to Figure 4.3. Place the trim ring over the back box as shown below. Figure 4.15 Installing Trim Ring Attach the door assembly to the backbox using the screws provided. Refer to Figure 4.14. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Figure 4.16 FIK-RA100 Connection to the Panel 4.8 FIK-RA1000R Remote Annunciator Installation The FIK-RA1000R is an optional remote annunciator. Up to 8 annunciators can be added to the FCP-75 system. FIRE ALARM ANNUNCIATOR Figure 4.17 FIK-RA1000R Remote Annunciator FIK-RA1000R installation involves the following steps: Ensure the power is off at the panel.
Page 32
After the annunciator wiring to the panel has been completed (refer to Figure 4.11), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 33
Figure 4.21 FIK-RA1000 Connection to the Panel Replace the electronic assembly in the backbox. Place the bezel over the backbox and tighten the set screws on the bezel. Refer to Figure 4.19 for location of set screws. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Remove knockouts as needed for wires. There are 10 knockouts available, two on each side and two in the back of the cabinet. Wire the annunciator board to the main control panel as shown in Figure 4.26. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 35
Run wires to the control panel. Refer to Figure 4.26. Place the trim ring over the back box as shown below. Figure 4.25 Installing Trim Ring Attach the door assembly to the backbox using the screws provided. Refer to Figure 4.24. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Select options for the printer and the output port. See below. Printer and Output Port Options From the Main Menu, select 7 for Program Menu. Select 1 for Module. Select 1 for Edit Module. From the list that displays, select the desired FIK-5824 module. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
The FIK-5880 can drive up to 40 LEDs and has one PZT controller. The FIK-5880 also has eight inputs for dry con- tact monitoring. Up to 8 FIK-5880 modules can be added to the FCP-75 System. The following sub-sections describe hardware installation.
NOTE: The circuit connected to “Open Collector Output” (last pin on P1) must be current-limited so that no more than 100 mA of current is allowed to flow into the Open Collector Transistor. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
IN - 48 IN - 47 IN - 46 IN - 45 IN - 44 C+ IN - 43 IN - 42 IN - 41 FIK-5880 Figure 4.32 Dry Contact Wiring FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
ID# to the module. Figure 4.37 shows all possible DIP switch positions and their correlation to a numerical ID. Address 0 is an invalid address and cannot be used. For example, to select ID 2, place DIP switch 2 in the up position. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
4.15 Notification Appliance/Auxiliary Power Circuits Two outputs are built-in to the FCP-75 FACP which can be programmed to be used as NACs (Class A or Class B) or as aux power. This sec- tion of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary power.
Configure the circuit for Class A in programming (see Section 8.5). SLCOUT SLCPROG NAC 1 SLCIN NAC 2 TROUBLE SBUS supervised, power-limited NAC wiring Class A supervised, regulated NAC circuits shown in alarm condition Figure 4.40 Class A Notification Appliance Circuit Configuration FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
The control panel has two built-in programmable relays and a built-in fixed trouble relay. All relays are Form C rated at 2.5 A @ 27.4 VDC resistive. RELAY 2 RELAY 1 TROUBLE SLC IN SLC OUT SLC PROG SBUS NAC 1 NAC 2 Connect to power-limited sources only. Figure 4.42 Location of Conventional Relay Circuits FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
• City Box Standby Current: 0 (Notification supervision current counted for in control panel draw.) • Alarm Current: 1Amp for 1 second FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Either NAC and relay circuit can be used. Not suitable for remote station protected premises service where separate transmission circuits are required for fire supervisory (if applicable) and trouble signals. Figure 4.45 Polarity Reversal Connection Using the 5220 Module FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Program the NAC circuit as a non silence NAC circuit (see Section 8.5.2). NOTE: If you need to transmit supervisory or trouble conditions, additional relay modules must be added. Use relay 1 to transmit supervisory conditions. Use the trouble relay to transmit trouble conditions.. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
NAC 1 NAC 2 typical input zone triggers Do not loop wires under terminals. Break wire runs to provide proper supervision of connections. transmitter activated by dry contacts Figure 4.47 Transmitter Activated by Dry Contacts FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Wiring Options to Connect Networked Panels A networked site is a logical group of FCP-75 panels that behave as though the logical group is one large control panel. Each building is referred to as a “site.” All panels in a site operate as a single panel. The control functions like reset, silence and alarm activation operate across the entire site.
The 5815RMK includes a small cabinet with locking door and mounting hardware. 5.4 SK-NIC Installation The FIK-NIC is designed to mount on the bracket inside the accessory cabinet. Use the following steps to properly mount the FIK-NIC-KIT. Place the FIK-NIC on the mounting bracket. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
SK-NIC Installation Networking Use the 6-pin cable included with FIK-NIC to connect the FCP-75 to the FIK-NIC. The 6-pin cable must be run in conduit between cabinets. Refer to Figure 5.1. LED1 LED2 Figure 5.5 Panel to FIK-NIC Connection Each FIK-NIC has the ability to monitor for earth ground faults on the twisted-pairs connected to Port 1 of its terminal block TB2. Earth fault detection for any wiring at Port 2 of TB2 is done at the next/previous FIK-NIC due to these wiring connections being connected to Port 1 of TB2 at the next/previous FIK-NIC.
Page 52
Figure 5.7 Fiber-Optic Wiring Example port 2 last control panel/FIK-NIC Class X wiring port 1 port 2 next control panel/FIK-NIC port 1 port 2 first control panel/FIK-NIC port 1 Figure 5.8 Fiber-Optic Wiring Single-Mode Example FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
OFF position. See the figure below for possible DIP switch settings. Address 0 is an invalid address and cannot be used. Address Address Address Address 4 5 6 4 5 6 4 5 6 4 5 6 Figure 5.10 Network ID Settings FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Take into account any future panels that will be added to the network (for example, future wiring of wiring two buildings together). The Net- work Panel ID setting must be assigned a unique ID for each panel on the network. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
A communicator is specified by the panel number. Use the Network communicators to report events according to the Communicator Report table. Communicator Miscellaneous When you use the SIA Reporting Format, the Communicator sends information according to the SIA Reporting Type. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Scroll down through the informational message and press ENTER to view the Select Source screen. Login to the panel. Select 6 to access the Network Programming Menu. Select 8 to access the Sync Network Options. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Select 7 for the Program Menu. From the next Menu, select 6 for JumpStart. The message, “SLC FAMILY FIKE” appears. press ENTER. A series of messages display for the next several seconds. JumpStart scans the SLC loops for the devices. This process can take several minutes, depending on the number of devices attached.
Output points are assigned to output groups only. system trbl & special optional system events Figure 7.1 Mapping Overview NOTE: Mapping cannot be programmed through the annunciators. It can only be programmed through the HFSS Software Suite. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Detector Alarm (heat or smoke detectors) General Fire Supervisory Zone Aux 1 Alarm General Fire Pre-Alarm Zone Aux 2 Alarm Interlock Alert Fire Interlock Release Pre-Alarm Fire Supervisory Status Point CO Alarm CO Supervisory Table 7.2 Event Types FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 61
Show Room 1st floor notification ANSI 3.41 1st floor 1st floor notification detector alarm constant supervisory same floor floor above Figure 7.5 Example of Zone Events Mapped to Output Groups and Patterns floor below FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
When you use HFSS, you can set up the programming options for the panel, save the options in a file, then download the file to the panel. You can connect directly to the control panel using the onboard USB or Ethernet port. Updates are available at www.fike.com.
FIK-5496 NAC Expander FIK-5880 LED I/O Module FIK-5865 LED Annunciator Module FIK-NIC Network Interface Card Delete Module Select Module Section 8.2.3 View Module List Select Module Section 8.2.4 Table 7.4 Programming Quick Reference List FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 64
Select Module NON-LATCH Section 8.5.1 1, 2 SWITCH LATCH ZONE AUX2 NON-LATCH LATCH SYSTEM AUX1 NON-LATCH LATCH SYSTEM AUX2 NON-LATCH DETECTOR LATCH FIRE TAMPER NON-LATCH MANUAL RELEASE INTERLOCK Table 7.4 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 65
Select Sensor I-SdrBa station or Multi DETECTOR (Intelligent station, Silence Sounder Base) or Non-Silence, volume high (default) or low No Accessory PHOTO DUCT DCT RLY 2-WIRE SMOKE Table 7.4 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 66
Single I-SdrBa station or Multi (Intelligent station, Silence Sounder Base) or Non-Silence, volume high (default) or low BEAM LATCH Same function as SUP DET DETECTOR NON-LATCH Table 7.4 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 67
A NOTIF Supervised Edit Name Point # CONTROL Section 8.5.2 External Power Yes or No CIRCUIT CONSTANT AUX RESET AUX PWR Edit Name AUX DOOR AUX SYNC Table 7.4 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 68
Monitor Line Y or *N Answering Machine Bypass Y or *N Phone Line Unused Y or *N IP Address Subnet Mask Edit Ethernet Default Gateway DHCP Enable Table 7.4 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 69
Table 7.4 Programming Quick Reference List (Continued) Available with Fike SLC devices. Available on Internal SLC. Requires wireless gateway. AUX SYNC setting is only applicable for the B200S Intelligent Sounder Base. Only applicable for FIK-RPS1000. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
To edit a module name, press the up or down arrow to select each character for the modules name (or press the right arrow to bypass the name edit). Press the right arrow to move to the next character. NOTE: See Appendix A for instructions on how to edit the names. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
At the Edit Zone option, you can edit: • zone name • zone properties (zone type and detector sensitivity) • zone accessory options To edit a zone, follow these steps: Login to the panel. Select 7 to access the Program Menu. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 72
If the operator performs a reset within 180 seconds, the alarm will not occur. If the operator does not perform a reset within 180 seconds, an alarm will occur automatically. The P.A.S. feature will be overridden if another alarm occurs. Table 8.2 Alarm Delay Types FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 73
Additionally, the extended label should be modified at this address to include the phrase ‘SPECIAL APPLICATIONS’ or ‘SPECIAL APPS’ for compliance with UL 864 requirements. Please refer to the FACP Programming/Installation Instructions for further instructions on altering the extended labels. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
The Edit Group menu allows you to select the options for each group for the following items: • Template Override: Y or N • If you select Yes to access Template Override, the Template Override Cadence is available. See Section 8.4.3 for more information. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
To select the type of device, press the up or down arrows keys. Refer to Table 8.4 under the column heading “Type Selection” for a list of choices. Type Latching Function Comments Selection Option UNUSED Table 8.4 Point Programming for Internal SLC Module FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 76
Wireless photoelectric detectors Non Latching ACCLIMATE Wireless acclimate photoelectric detector HEAT Wireless heat detector W-SUP DET Same as Latching Wireless photoelectric detectors W-Detector Non Latching Table 8.4 Point Programming for Internal SLC Module (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 77
DETECT SW STATUS PT Status Point Switch TROUBLE_MON Use this switch type to monitor trouble from external devices. Trouble monitors are used in HVAC operations. Table 8.4 Point Programming for Internal SLC Module (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
To select the Group, press the up or down arrows, then, press ENTER. 10. To edit the Point Name, press the right arrow to skip Point Name Edit. See Section 8.5. 11. Repeat steps 1 through 10 for all circuits. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Select 7 to access the Program Menu. Press 4 to enter the Point Menu. Press the up or down arrows to select the desired module. Refer to Section 7.5 for available choices. Press ENTER. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Enter the hour you want the control panel to send an Automatic Test Report (or press the up or down arrow key), then press ENTER. Enter the minutes (or press the up or down arrow key), then press ENTER. Select AM or PM by pressing the up or down arrow key, then press ENTER. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 81
It will continue to alternate between TT and pulse for additional attempts. Table 8.6 Dial Options Dial Format Press the up or down arrow keys to select the pulse ratio to access the Rotary Dialing option, then press ENTER. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Repeat steps 6 and 7 to add any remaining desired holidays. 8.6.4 Time Options Use this programming option to set the following: • water flow delay time • low AC report delay • clock format FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 84
The system resound time period can be modified from the default value 24 hours to 4 hours. This setting adjusts when the FACP will auto- matically resound events after being silenced. Set this option to 4 hours when using SWIFT devices. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
20 characters each. If you do not create a custom message, the system will use the internal banner. You cannot change the internal banner. To customize the banner display message, do the following. Login to the panel. Select 7 to access the program menu. Select 5 to access System Options. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Select 7 to access the program menu. Select 5 to access System Options. Select 8 for SLC Family. The type, “Fike” displays. 8.7 JumpStart Auto-Programming The FACP supports an incremental JumpStart. For example, after the initial JumpStart and customization, if you add more devices and per- form JumpStart again, the additional devices are added.
After pressing ENTER, and 1 for the login menu, a screen will prompt for the type of access account, Administrator or User. An administra- tor has the ability to modify user accounts and view the cybersecurity log. The User account has access to panel programming. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 88
Admin Profiles After initial power-up, the FCP-75 requires a password change and user account setup before programming. Only Admin1 will be active. Using the login for Admin1, the default password (0000000) must be changed to a new, unique password. This new password must be 7-dig- its and cannot be sequential or easily guessed.
Disable / Enable Point Press 7 to Disable/Enable Point. Select the module. Use the up or down arrow key to choose the point and press ENTER. Press the right arrow to disable or enable the point. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
The LCD will display “WALK TEST STOPPED” on Line 1 and “ENTER = start test” on Line 3. By selecting this option, the Central Station reporting is disabled while the test is in progress. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
If the sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a CAL MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance). FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
9.3.14 View System Information From the Main Menu, press 8 to access the System Information menu. About Panel Press 1 to access About Panel to view the panel model, serial number, system version number, and date. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Send/Receive Firmware Updates The FCP-75 has the ability to be updated in the field. The most recent FCP-75 Firmware Update Utility can be downloaded from the Fike website, www.fike.com. Once a panel has been updated using the Firmware Update Utility, you can use Send/Receive Firmware Updates to forward the firmware to the other panels in the network.
(Message will alternate with the date/time display.) FIRE: ALRM SUPR TRBL If more than 3 categories CO: ALRM SUPR are active at a single time, the screen will SYS: TRBL display as shown. Table 9.4 Panel Operating Modes FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 95
Pressing the right arrow key or Info will display the showing 1 of 1 event location macro, date/time stamp, and site/panel, if All system operations are available in this mode. applicable. Table 9.4 Panel Operating Modes (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
• The FCP-75 menu system is disabled on a multi-site annunciator. Pressing the right arrow or Enter keys will bring you straight into event history for assigned sites. To get into the menu system, a multi-site user password must be entered and then a site must be selected from the site selection menu.
(Also refer to Table 9.5.) Conditions Required for a General Alarm Output Activation If two addressable detectors, a manual release switch is activated, or an interlock switch is active, the “Pre-Alert”, and “General Alarm” out- puts will activate. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
9.8 Function Keys The function keys on the FCP-75 (or FIK-RA2000) have multiple features. Their macro key functionality can simplify the disabling, activat- ing, or inhibiting points or groups respectively. They can also be used as a status type activation event and for activating Map Inhibit. Each F-Key macro can hold 50 events.
This option is programmable for each output group Map through the HFSS Software Suite. When an F-Key is active and a map in the system is set to be disabled by Map Inhibit, the system will show a trouble event. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 101
Exp. ID SBUS Class A supervision restore Exp. ID ERNNXX0000 Exp. ID SBUS expander trouble Exp. ID ETNNXX0000 Exp. ID SBUS expander trouble restore Exp. ID ERNNXX0000 Exp. ID Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 103
Voice Aux ECS 2 Alarm Restore UHNN004000 Voice Aux ECS 3 Alarm UANN005000 Voice Aux ECS 3 Alarm Restore UHNN005000 Voice Aux ECS 4 Alarm UANN006000 Voice Aux ECS 4 Alarm Restore UHNN006000 Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 104
Detector CO Supervisory Alarm pi Exp. ID GS Point # GSNNXXPPPP Exp. ID Point # Detector CO Supervisory Alarm Restore pi Exp. ID GR Point # GRNNXXPPPP Exp. ID Point # Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 105
Point # Release Zone) LOC Mic Activated ECS Alarm pi Exp. ID QA QANNXX0000 Exp. ID LOC Mic Activated ECS Alarm Restore pi Exp. ID QH QHNNXX0000 Exp. ID Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 106
Supervisory/Tamper point enabled pi Exp. ID FU Point # FUNNXXPPPP Exp. ID Point # Supervisory/Tamper point trouble pi Exp. ID FT Point # FTNNXXPPPP Exp. ID Point # Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 107
Water flow switch alarm restore pi Exp. ID SH Point # SHNNXXPPPP Exp. ID Point # Water flow switch disabled pi Exp. ID SB Point # SBNNXXPPPP Exp. ID Point # Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Page 108
Wireless Gateway Trouble pi Exp. ID UT Point # UTNNXXPPPP Exp. ID Point # Wireless Gateway Trouble restore pi Exp. ID UJ Point # UJNNXXPPPP Exp. ID Point # Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
FT22970200 Fire Trouble Zone EE-PP-MM-ZZZZ FT22970001 MM = 00 Fire Trouble-NAC Point NAC Circuit 2 EE-PP-MM-ZZZZ FT22980002 ZZZZ=Pt. # Fire Trouble-NAC Zone NAC Circuit 2 EE-PP-MM-ZZZZ FT22980002 ZZZZ=OPG # Table 10.4 SIA Reporting Examples FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
If new batteries were installed, wait 48 hours before completing this step. Remove the AC power, activate the initiating device, and check that the following occurs: • The ALARM indicator lights. • All active notification appliances sound. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
If you select YES, the system will cease normal operation, leaving the premises unprotected. Select the SLC loop. Enter up to eight SLC addresses for the devices you want to locate. The LEDs on the selected devices will start flashing. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
The available Receiver Number will correspond with the panel number you entered. The Receiver Numbers are populated based on the panel number and they are audited to allow only the four appropriate receivers. See Section 6.2.6. Panel Available Receiver Numbers Table B.1 Receiver/Panel Relationship FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Ensure the Ethernet cable is removed from the FACP when not being utilized for configuration or for reporting purposes. Security and Data Protection Communication Security - Level 1 Stored Data Security - Level 0 Physical Security - Level 1 Access Control Security - Level 1 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
Model FCP-75/FCP-75HV Basic Operating Instructions These instructions must be framed and displayed next to the FCP-75 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the system in accordance to NFPA 72. Operation Task to Perform Silence Alarms and Troubles Press SILENCE and then enter a code if prompted.
Page 122
Fike World Headquarters 704 SW 10th Street Blue Springs, Missouri 64015 USA Tel: +001 816-229-3405 Toll Free (US Only): 1-800-YES-FIKE (1-800-937-3453) www.Fike.com For a list of contact information for Fike offices around the world, visit the Global Locations section of Fike.com...
Need help?
Do you have a question about the FCP-75 and is the answer not in the manual?
Questions and answers