Fike FCP-75 Manual

Fike FCP-75 Manual

Addressable fire alarm control panel
Hide thumbs Also See for FCP-75:
Table of Contents

Advertisement

Quick Links

Addressable Fire Alarm Control Panel
FCP-75
Manual
Document LS10147-003FK-E
B
6/20/2022
P/N LS10147-003FK-E:B • ECN 00003636

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FCP-75 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Fike FCP-75

  • Page 1 Addressable Fire Alarm Control Panel FCP-75 Manual Document LS10147-003FK-E 6/20/2022 P/N LS10147-003FK-E:B • ECN 00003636...
  • Page 2 Adequate written records of all rise feature of each detector should be tested at least once per year inspections should be kept. by a qualified fire protection specialist. Heat detectors are designed Limit-F-2020 to protect property, not life. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 3 Flexput®, Honeywell®, JumpStart®, and SWIFT® are registered trademarks of Honeywell International Inc.Microsoft® and Windows® are registered trademarks of the Microsoft Corporation. Chrome™ and Google™ are trademarks of Google Inc. Firefox® is a registered trademark of The Mozilla Foundation. ©2022. All rights reserved. Unauthorized use of this document is strictly prohibited. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 4 Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 5: Table Of Contents

    Section 4: Control Panel Installation ..........................20 4.1: Mounting the Control Panel Cabinet ................................20 4.1.1: Preventing Water Damage..................................20 4.1.2: Removing the FCP-75 Assembly from the Housing ..........................20 4.1.3: Dead Front Installation and Removal ..............................20 4.2: Board Assembly Diagram....................................22 4.3: Wiring Specifications.......................................22 4.4: AC Power Connection .....................................23...
  • Page 6 7.4.2: Moving through the Menus ..................................63 7.4.3: Selecting Options and Entering Data..............................63 7.5: Programming Menu Quick Reference ................................63 Section 8: Programming ..............................70 8.1: UL 864 Programming Requirements ................................70 8.2: Modules ...........................................70 8.2.1: Edit Modules......................................70 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 7 9.7: Smoke Alarm Verification ....................................98 9.8: Function Keys .........................................98 9.8.1: Recording an F-Key Macro ..................................98 9.8.2: Aborting an F-Key Macro Recording Session............................98 9.8.3: Erasing an F-Key Macro..................................98 9.8.4: Using a Recorded F-Key Macro ................................99 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 8 9.8.6: F-Key Map Inhibit ....................................99 Section 10: Reporting ..............................100 10.1: Receivers Compatible with the Control Panel.............................100 10.2: SIA / FCP-75 Panels PI Modifier Reporting ...............................109 10.3: SIA– FCP-75 Panel Communicator................................110 Section 11: Testing and Troubleshooting........................111 11.1: Troubleshooting ......................................111 11.2: Troubleshooting Common Problems ................................
  • Page 9: Section 1: Introduction

    • The FCP-75 is capable of outputting 2.5A of output power during an alarm activation through 2 sets of terminals for the notification appliance circuits or an auxiliary application. Each circuit is power-limited and can source up to 2.5A during an alarm activation. The constant auxiliary power load must not exceed 1A for normal standby.
  • Page 10: About This Manual

    About this Manual 1.2 About this Manual This manual is intended to be a complete reference for all installation and operation tasks for the FCP-75. 1.2.1 Terms Used in this Manual The following terminology is used with the FCP-75 system:...
  • Page 11: Related Documentation

    For communication and panel programming with a Windows-based computer. Enables Tool remote viewing of detector status and event history. 7860 Telephone Cord RJ31X cord for connecting phone line to the FCP-75. 7628 UL Listed End-of-line resistor Table 1.2 FCP-75 Compatible Products (Continued) 1.4 Related Documentation...
  • Page 12: Section 2: Agency Listings, Approvals, And Requirements

    14. If your facility has specially wired alarm equipment connected to the telephone line, ensure the installation of this FCP-75 does not disable your alarm equipment. If you have questions about what will disable alarm equipment, consult your Telephone Company or qualified installer.
  • Page 13: Underwriters Laboratories (Ul)

    Use both phone lines. Enable phone line monitors for both lines. You must program a phone number and a test time so that the FCP-75 shall automatically initiate and complete a test signal transmission sequence to its associated receiver at least once every 6-hours, using two phones or one phone line with Ethernet backup.
  • Page 14: 6: Requirements For The Installation Of Carbon Monoxide (Co) Detection And Warning Equipment, Nfpa 720

    Fiber modules Y = YES, N = NO, O = OPTIONAL Note: Y * = You must include the FIK-RPS1000 or FIK-5496 for releasing purposes. Table 2.1 NFPA Requirement for Minimum System Configuration for FCP-75-75 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 15: Section 3: Prerequisites For Installation

    FCP-75 panel for the first time. 3.1 Inventory When the FCP-75 shipment is received, check that all the parts have been included in the shipment. The shipment consists of one of each of the following: •...
  • Page 16: Calculating Current Draw And Standby Battery

    Filling in the Current Draw Worksheet, Table 3.2 For the FCP-75, the worst case current draw is listed for the panel, addressable devices, and SLC expanders. Fill in the number of addressable devices and expanders that will be used in the system and compute the current draw requirements for alarm and standby.
  • Page 17 ISO-6 (6 Fault Isolator Module) Standby: (per circuit) 0.45 mA Isolation: (per circuit) 17 mA Accessories Modules FIK-RA2000 Remote LCD Standby: 27 mA Annunciator Alarm: 53 mA Table 3.2 Current Draw Worksheet for IDP SLC Devices (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 18 However, during normal operation, door holders draw current and must be included in the 1.8 A total current that can be drawn from the panel. Use next size battery with capacity greater than required. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 19 Maximum Battery Standby Load Table 3.3 shows the maximum battery standby load for the FCP-75 based on 24 and 60 hours of standby. The standby load calculations of line G in the Current Draw Calculation Worksheet (Table 3.2) must be less than the number shown in Table 3.3 for the battery size used and standby hours required.
  • Page 20: Section 4: Control Panel Installation

    The FCP-75 cabinet base dimensions are: 12.531” W x 14.875” H. The FCP-75 panel should be located within a secured area, where it is accessible to the main drop wiring runs and where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear alarms and troubles. When you select a location, keep in mind that the panel itself is the main source of alarm and trouble annunciation.
  • Page 21 Remove the two screws and star washers from the bottom of the cabinet. Remove the dead front panel from the control panel cabinet. Reinstall the top two annunciator screws to secure to the board. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 22: Board Assembly Diagram

    High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 23: Ac Power Connection

    POWER BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAMAGED BY REMOVING AND/OR INSERTING CARDS, MODULES OR INTERCONNECTING CABLES WHILE THIS UNIT IS ENERGIZED • AC power for the FCP-75 is rated at 120VAC, 60Hz, 1.5A. AC power for the FCP-75HV is rated at 240VAC, 50/60Hz, 1A. •...
  • Page 24: Battery Power

    Connect the jumper wire provided (P/N 140694) from the positive (+) side of Battery #2 to the (–) negative side of Battery #1. Connect the red wire from the control panel positive (+) terminal to the positive (+) side of Battery #1. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 25: 1: Battery Accessory Cabinet

    • If using the battery cable extenders provided (P/N 140643), mount the RBB cabinet no more than 18" away from the main control panel cabinet. This will ensure that the battery cables reach the battery terminals. cabinet mounting holes Figure 4.7 RBB Cabinet Mounting Holes FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 26: Wiring Specifications

    Figure 4.10 Cover Plate Mounting Keyholes and Cover Mounting Screws Alignment 4.6 Wiring Specifications 4.6.1 Length Limitations This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class A and B). FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 27: 2: Calculating Wiring Distance For Sbus Modules

    * 500 (6000 feet maximum) where: Rpu = Ohms per 1000 feet for various Wire Gauges (see table below) Wire Gauge Ohms per 1000 feet (Rpu) 16.2 Table 4.7 Typical Wire Resistance Per 1,000 ft. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 28: 3: Wiring Configurations

    The optional model FIK-RA100 Remote Annunciator, is shown in Figure 4.12. The FIK-RA100 can be surface or flush mounted. Up to eight FIK-RA100 annunciators can be added to the FCP-75 system in any combination. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 29: 1: Mounting The Fik-Ra100

    Remove knockout holes as needed for wires. There are 10 knockouts available, two on each side and two in the back of the cabinet. Wire the annunciator board to the main control panel. Refer to Figure 4.3. Attach the annunciator and door assembly to backbox as shown below using the supplied screws. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 30 Run wires to the control panel. Refer to Figure 4.3. Place the trim ring over the back box as shown below. Figure 4.15 Installing Trim Ring Attach the door assembly to the backbox using the screws provided. Refer to Figure 4.14. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 31: 2: Fik-Ra100 Connection To The Panel

    Figure 4.16 FIK-RA100 Connection to the Panel 4.8 FIK-RA1000R Remote Annunciator Installation The FIK-RA1000R is an optional remote annunciator. Up to 8 annunciators can be added to the FCP-75 system. FIRE ALARM ANNUNCIATOR Figure 4.17 FIK-RA1000R Remote Annunciator FIK-RA1000R installation involves the following steps: Ensure the power is off at the panel.
  • Page 32 After the annunciator wiring to the panel has been completed (refer to Figure 4.11), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 33 Figure 4.21 FIK-RA1000 Connection to the Panel Replace the electronic assembly in the backbox. Place the bezel over the backbox and tighten the set screws on the bezel. Refer to Figure 4.19 for location of set screws. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 34: Fik-Ra2000 Remote Annunciator Installation

    Remove knockouts as needed for wires. There are 10 knockouts available, two on each side and two in the back of the cabinet. Wire the annunciator board to the main control panel as shown in Figure 4.26. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 35 Run wires to the control panel. Refer to Figure 4.26. Place the trim ring over the back box as shown below. Figure 4.25 Installing Trim Ring Attach the door assembly to the backbox using the screws provided. Refer to Figure 4.24. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 36: 2: Fik-Ra2000 Connection To The Panel

    Select options for the printer and the output port. See below. Printer and Output Port Options From the Main Menu, select 7 for Program Menu. Select 1 for Module. Select 1 for Edit Module. From the list that displays, select the desired FIK-5824 module. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 37: Fik-5880 Led Driver Module

    The FIK-5880 can drive up to 40 LEDs and has one PZT controller. The FIK-5880 also has eight inputs for dry con- tact monitoring. Up to 8 FIK-5880 modules can be added to the FCP-75 System. The following sub-sections describe hardware installation.
  • Page 38: 2: Facp Connection

    NOTE: The circuit connected to “Open Collector Output” (last pin on P1) must be current-limited so that no more than 100 mA of current is allowed to flow into the Open Collector Transistor. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 39: 4: Dry Contact Wiring

    IN - 48 IN - 47 IN - 46 IN - 45 IN - 44 C+ IN - 43 IN - 42 IN - 41 FIK-5880 Figure 4.32 Dry Contact Wiring FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 40: Fik-5865-3/Fik-5865-4 Led Annunciator Installation

    This programming step is described in Section 8. FACP NAC 1 TROUBLE SLCIN SLCOUT SLCPROG SBUS NAC 2 supervised, power-limited FIK-5865 Figure 4.34 FIK-5865 Connection to the FACP FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 41: 2: Fik-5865 Mounting

    ID# to the module. Figure 4.37 shows all possible DIP switch positions and their correlation to a numerical ID. Address 0 is an invalid address and cannot be used. For example, to select ID 2, place DIP switch 2 in the up position. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 42: Telephone Connection

    4.15 Notification Appliance/Auxiliary Power Circuits Two outputs are built-in to the FCP-75 FACP which can be programmed to be used as NACs (Class A or Class B) or as aux power. This sec- tion of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary power.
  • Page 43: 1: Conventional Notification Appliance

    Configure the circuit for Class A in programming (see Section 8.5). SLCOUT SLCPROG NAC 1 SLCIN NAC 2 TROUBLE SBUS supervised, power-limited NAC wiring Class A supervised, regulated NAC circuits shown in alarm condition Figure 4.40 Class A Notification Appliance Circuit Configuration FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 44: 1: Auxiliary Power Installation

    The control panel has two built-in programmable relays and a built-in fixed trouble relay. All relays are Form C rated at 2.5 A @ 27.4 VDC resistive. RELAY 2 RELAY 1 TROUBLE SLC IN SLC OUT SLC PROG SBUS NAC 1 NAC 2 Connect to power-limited sources only. Figure 4.42 Location of Conventional Relay Circuits FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 45: 1: Common Trouble Relay

    • City Box Standby Current: 0 (Notification supervision current counted for in control panel draw.) • Alarm Current: 1Amp for 1 second FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 46: 3: Nfpa 72 Polarity Reversal

    Either NAC and relay circuit can be used. Not suitable for remote station protected premises service where separate transmission circuits are required for fire supervisory (if applicable) and trouble signals. Figure 4.45 Polarity Reversal Connection Using the 5220 Module FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 47: 4: Using A Mr-201/T Control Relay From Air Products

    Program the NAC circuit as a non silence NAC circuit (see Section 8.5.2). NOTE: If you need to transmit supervisory or trouble conditions, additional relay modules must be added. Use relay 1 to transmit supervisory conditions. Use the trouble relay to transmit trouble conditions.. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 48: 5: Transmitter Activated By Dry Contacts

    NAC 1 NAC 2 typical input zone triggers Do not loop wires under terminals. Break wire runs to provide proper supervision of connections. transmitter activated by dry contacts Figure 4.47 Transmitter Activated by Dry Contacts FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 49: Section 5: Networking

    Wiring Options to Connect Networked Panels A networked site is a logical group of FCP-75 panels that behave as though the logical group is one large control panel. Each building is referred to as a “site.” All panels in a site operate as a single panel. The control functions like reset, silence and alarm activation operate across the entire site.
  • Page 50: 1: Fiber Loop Modules

    The 5815RMK includes a small cabinet with locking door and mounting hardware. 5.4 SK-NIC Installation The FIK-NIC is designed to mount on the bracket inside the accessory cabinet. Use the following steps to properly mount the FIK-NIC-KIT. Place the FIK-NIC on the mounting bracket. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 51: 1: Wiring

    SK-NIC Installation Networking Use the 6-pin cable included with FIK-NIC to connect the FCP-75 to the FIK-NIC. The 6-pin cable must be run in conduit between cabinets. Refer to Figure 5.1. LED1 LED2 Figure 5.5 Panel to FIK-NIC Connection Each FIK-NIC has the ability to monitor for earth ground faults on the twisted-pairs connected to Port 1 of its terminal block TB2. Earth fault detection for any wiring at Port 2 of TB2 is done at the next/previous FIK-NIC due to these wiring connections being connected to Port 1 of TB2 at the next/previous FIK-NIC.
  • Page 52 Figure 5.7 Fiber-Optic Wiring Example port 2 last control panel/FIK-NIC Class X wiring port 1 port 2 next control panel/FIK-NIC port 1 port 2 first control panel/FIK-NIC port 1 Figure 5.8 Fiber-Optic Wiring Single-Mode Example FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 53: Setting The Network Id For Each Panel

    OFF position. See the figure below for possible DIP switch settings. Address 0 is an invalid address and cannot be used. Address Address Address Address 4 5 6 4 5 6 4 5 6 4 5 6 Figure 5.10 Network ID Settings FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 54: Section 6: Network Management

    Take into account any future panels that will be added to the network (for example, future wiring of wiring two buildings together). The Net- work Panel ID setting must be assigned a unique ID for each panel on the network. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 55: 4: Computer Access

    A communicator is specified by the panel number. Use the Network communicators to report events according to the Communicator Report table. Communicator Miscellaneous When you use the SIA Reporting Format, the Communicator sends information according to the SIA Reporting Type. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 56: Sync Network Options

    Scroll down through the informational message and press ENTER to view the Select Source screen. Login to the panel. Select 6 to access the Network Programming Menu. Select 8 to access the Sync Network Options. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 57: Network Management Quick Reference

    Report Supervisory Report Troubles Report Events by Point Primary Receiver Primary Account Test Primary Account Secondary Receiver Secondary Account Test Secondary Account Sync Network See Section 6.3 Options Table 6.1 Network Management Quick Reference List FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 58: Section 7: Programming Overview

    Select 7 for the Program Menu. From the next Menu, select 6 for JumpStart. The message, “SLC FAMILY FIKE” appears. press ENTER. A series of messages display for the next several seconds. JumpStart scans the SLC loops for the devices. This process can take several minutes, depending on the number of devices attached.
  • Page 59: Mapping Overview

    Output points are assigned to output groups only. system trbl & special optional system events Figure 7.1 Mapping Overview NOTE: Mapping cannot be programmed through the annunciators. It can only be programmed through the HFSS Software Suite. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 60: 1: Input Point Mapping

    Detector Alarm (heat or smoke detectors) General Fire Supervisory Zone Aux 1 Alarm General Fire Pre-Alarm Zone Aux 2 Alarm Interlock Alert Fire Interlock Release Pre-Alarm Fire Supervisory Status Point CO Alarm CO Supervisory Table 7.2 Event Types FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 61 Show Room 1st floor notification ANSI 3.41 1st floor 1st floor notification detector alarm constant supervisory same floor floor above Figure 7.5 Example of Zone Events Mapped to Output Groups and Patterns floor below FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 62: 4: Mapping Led Points

    When you use HFSS, you can set up the programming options for the panel, save the options in a file, then download the file to the panel. You can connect directly to the control panel using the onboard USB or Ethernet port. Updates are available at www.fike.com.
  • Page 63: 2: Moving Through The Menus

    FIK-5496 NAC Expander FIK-5880 LED I/O Module FIK-5865 LED Annunciator Module FIK-NIC Network Interface Card Delete Module Select Module Section 8.2.3 View Module List Select Module Section 8.2.4 Table 7.4 Programming Quick Reference List FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 64 Select Module NON-LATCH Section 8.5.1 1, 2 SWITCH LATCH ZONE AUX2 NON-LATCH LATCH SYSTEM AUX1 NON-LATCH LATCH SYSTEM AUX2 NON-LATCH DETECTOR LATCH FIRE TAMPER NON-LATCH MANUAL RELEASE INTERLOCK Table 7.4 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 65 Select Sensor I-SdrBa station or Multi DETECTOR (Intelligent station, Silence Sounder Base) or Non-Silence, volume high (default) or low No Accessory PHOTO DUCT DCT RLY 2-WIRE SMOKE Table 7.4 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 66 Single I-SdrBa station or Multi (Intelligent station, Silence Sounder Base) or Non-Silence, volume high (default) or low BEAM LATCH Same function as SUP DET DETECTOR NON-LATCH Table 7.4 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 67 A NOTIF Supervised Edit Name Point # CONTROL Section 8.5.2 External Power Yes or No CIRCUIT CONSTANT AUX RESET AUX PWR Edit Name AUX DOOR AUX SYNC Table 7.4 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 68 Monitor Line Y or *N Answering Machine Bypass Y or *N Phone Line Unused Y or *N IP Address Subnet Mask Edit Ethernet Default Gateway DHCP Enable Table 7.4 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 69 Table 7.4 Programming Quick Reference List (Continued) Available with Fike SLC devices. Available on Internal SLC. Requires wireless gateway. AUX SYNC setting is only applicable for the B200S Intelligent Sounder Base. Only applicable for FIK-RPS1000. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 70: Section 8: Programming

    To edit a module name, press the up or down arrow to select each character for the modules name (or press the right arrow to bypass the name edit). Press the right arrow to move to the next character. NOTE: See Appendix A for instructions on how to edit the names. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 71: 2: Adding Modules

    At the Edit Zone option, you can edit: • zone name • zone properties (zone type and detector sensitivity) • zone accessory options To edit a zone, follow these steps: Login to the panel. Select 7 to access the Program Menu. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 72 If the operator performs a reset within 180 seconds, the alarm will not occur. If the operator does not perform a reset within 180 seconds, an alarm will occur automatically. The P.A.S. feature will be overridden if another alarm occurs. Table 8.2 Alarm Delay Types FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 73 Additionally, the extended label should be modified at this address to include the phrase ‘SPECIAL APPLICATIONS’ or ‘SPECIAL APPS’ for compliance with UL 864 requirements. Please refer to the FACP Programming/Installation Instructions for further instructions on altering the extended labels. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 74: 2: View Zone Points

    The Edit Group menu allows you to select the options for each group for the following items: • Template Override: Y or N • If you select Yes to access Template Override, the Template Override Cadence is available. See Section 8.4.3 for more information. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 75: 2: View Group Points

    To select the type of device, press the up or down arrows keys. Refer to Table 8.4 under the column heading “Type Selection” for a list of choices. Type Latching Function Comments Selection Option UNUSED Table 8.4 Point Programming for Internal SLC Module FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 76 Wireless photoelectric detectors Non Latching ACCLIMATE Wireless acclimate photoelectric detector HEAT Wireless heat detector W-SUP DET Same as Latching Wireless photoelectric detectors W-Detector Non Latching Table 8.4 Point Programming for Internal SLC Module (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 77 DETECT SW STATUS PT Status Point Switch TROUBLE_MON Use this switch type to monitor trouble from external devices. Trouble monitors are used in HVAC operations. Table 8.4 Point Programming for Internal SLC Module (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 78: 2: Point Programming For The Internal Or External Power Module

    To select the Group, press the up or down arrows, then, press ENTER. 10. To edit the Point Name, press the right arrow to skip Point Name Edit. See Section 8.5. 11. Repeat steps 1 through 10 for all circuits. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 79: 3: Point Programming For Fik-5880 And Fik-5865 Modules

    Select 7 to access the Program Menu. Press 4 to enter the Point Menu. Press the up or down arrows to select the desired module. Refer to Section 7.5 for available choices. Press ENTER. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 80: 4: Point Programming For The Fik-5496

    Enter the hour you want the control panel to send an Automatic Test Report (or press the up or down arrow key), then press ENTER. Enter the minutes (or press the up or down arrow key), then press ENTER. Select AM or PM by pressing the up or down arrow key, then press ENTER. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 81 It will continue to alternate between TT and pulse for additional attempts. Table 8.6 Dial Options  Dial Format Press the up or down arrow keys to select the pulse ratio to access the Rotary Dialing option, then press ENTER. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 82 • Old Alarm: 30 minutes (default), 15 minutes, 10 minutes, none, 24 hours,12 hours, 6 hours, 4 hours,2 hours, 1 hour Ethernet: 5 Minutes_ Cellular: 24 Hours_ Old Alarm: 30 Minutes_ <Ethernet Supervise> Figure 8.10 AlarmNet Timers FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 83: 2: Daytime/Nighttime Sensitivity

    Repeat steps 6 and 7 to add any remaining desired holidays. 8.6.4 Time Options Use this programming option to set the following: • water flow delay time • low AC report delay • clock format FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 84 The system resound time period can be modified from the default value 24 hours to 4 hours. This setting adjusts when the FACP will auto- matically resound events after being silenced. Set this option to 4 hours when using SWIFT devices. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 85: 5: Miscellaneous Options

    20 characters each. If you do not create a custom message, the system will use the internal banner. You cannot change the internal banner. To customize the banner display message, do the following. Login to the panel. Select 7 to access the program menu. Select 5 to access System Options. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 86: 8: Slc Family

    Select 7 to access the program menu. Select 5 to access System Options. Select 8 for SLC Family. The type, “Fike” displays. 8.7 JumpStart Auto-Programming The FACP supports an incremental JumpStart. For example, after the initial JumpStart and customization, if you add more devices and per- form JumpStart again, the additional devices are added.
  • Page 87: Section 9: System Operation

    After pressing ENTER, and 1 for the login menu, a screen will prompt for the type of access account, Administrator or User. An administra- tor has the ability to modify user accounts and view the cybersecurity log. The User account has access to panel programming. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 88 Admin Profiles After initial power-up, the FCP-75 requires a password change and user account setup before programming. Only Admin1 will be active. Using the login for Admin1, the default password (0000000) must be changed to a new, unique password. This new password must be 7-dig- its and cannot be sequential or easily guessed.
  • Page 89: 2: Main Menu Overview

    Disable / Enable Point Press 7 to Disable/Enable Point. Select the module. Use the up or down arrow key to choose the point and press ENTER. Press the right arrow to disable or enable the point. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 90: 3: View Event History

    The LCD will display “WALK TEST STOPPED” on Line 1 and “ENTER = start test” on Line 3. By selecting this option, the Central Station reporting is disabled while the test is in progress. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 91: 7: Conduct A Communicator Test

    If the sensitivity for a detector is not in compliance, the panel goes into trouble, generating a CAL TRBLE condition. A detector enters a CAL MAINT state to indicate that it is approaching an out of compliance condition (but is currently still in compliance). FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 92: 12: View Status Of A Point

    9.3.14 View System Information From the Main Menu, press 8 to access the System Information menu. About Panel Press 1 to access About Panel to view the panel model, serial number, system version number, and date. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 93: Operation Mode Behavior

    Send/Receive Firmware Updates The FCP-75 has the ability to be updated in the field. The most recent FCP-75 Firmware Update Utility can be downloaded from the Fike website, www.fike.com. Once a panel has been updated using the Firmware Update Utility, you can use Send/Receive Firmware Updates to forward the firmware to the other panels in the network.
  • Page 94: Panel Operating Modes

    (Message will alternate with the date/time display.) FIRE: ALRM SUPR TRBL If more than 3 categories CO: ALRM SUPR are active at a single time, the screen will SYS: TRBL display as shown. Table 9.4 Panel Operating Modes FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 95 Pressing the right arrow key or Info will display the showing 1 of 1 event location macro, date/time stamp, and site/panel, if All system operations are available in this mode. applicable. Table 9.4 Panel Operating Modes (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 96: 1: Multi-Site Annunciator And Multi-Site User Access

    • The FCP-75 menu system is disabled on a multi-site annunciator. Pressing the right arrow or Enter keys will bring you straight into event history for assigned sites. To get into the menu system, a multi-site user password must be entered and then a site must be selected from the site selection menu.
  • Page 97: 1: Single Interlock Zone Releasing

    (Also refer to Table 9.5.) Conditions Required for a General Alarm Output Activation If two addressable detectors, a manual release switch is activated, or an interlock switch is active, the “Pre-Alert”, and “General Alarm” out- puts will activate. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 98: Smoke Alarm Verification

    9.8 Function Keys The function keys on the FCP-75 (or FIK-RA2000) have multiple features. Their macro key functionality can simplify the disabling, activat- ing, or inhibiting points or groups respectively. They can also be used as a status type activation event and for activating Map Inhibit. Each F-Key macro can hold 50 events.
  • Page 99: 4: Using A Recorded F-Key Macro

    This option is programmable for each output group Map through the HFSS Software Suite. When an F-Key is active and a map in the system is set to be disabled by Map Inhibit, the system will show a trouble event. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 100: Section 10: Reporting

    FTNN002002 F2 Mapping Inhibited Restoral 2002 FJNN002002 F3 Mapping Inhibited 2003 FTNN002003 F3 Mapping Inhibited Restoral 2003 FJNN002003 F4 Mapping Inhibited 2004 FTNN002004 F4 Mapping Inhibited Restoral 2004 FJNN002004 Table 10.2 Reporting Formats Table FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 101 Exp. ID SBUS Class A supervision restore Exp. ID ERNNXX0000 Exp. ID SBUS expander trouble Exp. ID ETNNXX0000 Exp. ID SBUS expander trouble restore Exp. ID ERNNXX0000 Exp. ID Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 102 UJNN000000 trouble restore LOC Mic Activated ECS Alarm QANN000000 LOC Mic Activated ECS Alarm Restore QHNN000000 LOC/Point ECS # Alarm Emergency # QANN0E0000 220 + Emerge ncy # Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 103 Voice Aux ECS 2 Alarm Restore UHNN004000 Voice Aux ECS 3 Alarm UANN005000 Voice Aux ECS 3 Alarm Restore UHNN005000 Voice Aux ECS 4 Alarm UANN006000 Voice Aux ECS 4 Alarm Restore UHNN006000 Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 104 Detector CO Supervisory Alarm pi Exp. ID GS Point # GSNNXXPPPP Exp. ID Point # Detector CO Supervisory Alarm Restore pi Exp. ID GR Point # GRNNXXPPPP Exp. ID Point # Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 105 Point # Release Zone) LOC Mic Activated ECS Alarm pi Exp. ID QA QANNXX0000 Exp. ID LOC Mic Activated ECS Alarm Restore pi Exp. ID QH QHNNXX0000 Exp. ID Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 106 Supervisory/Tamper point enabled pi Exp. ID FU Point # FUNNXXPPPP Exp. ID Point # Supervisory/Tamper point trouble pi Exp. ID FT Point # FTNNXXPPPP Exp. ID Point # Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 107 Water flow switch alarm restore pi Exp. ID SH Point # SHNNXXPPPP Exp. ID Point # Water flow switch disabled pi Exp. ID SB Point # SBNNXXPPPP Exp. ID Point # Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 108 Wireless Gateway Trouble pi Exp. ID UT Point # UTNNXXPPPP Exp. ID Point # Wireless Gateway Trouble restore pi Exp. ID UJ Point # UJNNXXPPPP Exp. ID Point # Table 10.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 109: Sia / Fcp-75 Panels Pi Modifier Reporting

    Fire Trouble Zone EE-Z Fire Trouble-NAC Point NAC Circuit 2 EE-ZZ /EE-Z pi98/FT2Z=Pt. # Fire Trouble-NAC Zone NAC Circuit 2 EE-ZZZ FT98 ZZZ=OP Table 10.3 SIA- FCP-75 Panels - PI Modifier Reporting Examples FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 110: Sia- Fcp-75 Panel Communicator

    FT22970200 Fire Trouble Zone EE-PP-MM-ZZZZ FT22970001 MM = 00 Fire Trouble-NAC Point NAC Circuit 2 EE-PP-MM-ZZZZ FT22980002 ZZZZ=Pt. # Fire Trouble-NAC Zone NAC Circuit 2 EE-PP-MM-ZZZZ FT22980002 ZZZZ=OPG # Table 10.4 SIA Reporting Examples FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 111: Section 11: Testing And Troubleshooting

    If new batteries were installed, wait 48 hours before completing this step. Remove the AC power, activate the initiating device, and check that the following occurs: • The ALARM indicator lights. • All active notification appliances sound. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 112: 2: Event History

    If you select YES, the system will cease normal operation, leaving the premises unprotected. Select the SLC loop. Enter up to eight SLC addresses for the devices you want to locate. The LEDs on the selected devices will start flashing. FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 113: 3: I/O Point Control

    NAC 1 + NAC 2 - NAC 2 + SBUS - SBUS + SBUS A SBUS B SLC IN - SLC IN + SLC OUT - SLC OUT + Table 11.2 Earth Fault Resistance FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 114: Section 12: Installation Records

    Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Onboard Table 12.1 Detector Installation Record FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 115: Appendix A: Editing Text Using The Built-In Programmer

    _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ 1[abc] 2[def] 3[ghi] 7[stu] 8[vwx] 9[yz ] 4[jkl] 5[mno] 6[pqr] 0[Spc] Figure A.1 Edit Name Example FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 116: Appendix B: Expanded Receiver/Panel Relationship

    The available Receiver Number will correspond with the panel number you entered. The Receiver Numbers are populated based on the panel number and they are audited to allow only the four appropriate receivers. See Section 6.2.6. Panel Available Receiver Numbers Table B.1 Receiver/Panel Relationship FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 117: Appendix C: Cadence Patterns

    Disconnected. No voltage at terminals. Temporal 4 0.1 sec on, 0.1 sec off, 0.1 sec on, 0.1 sec off, 0.1 sec on, 0.1 sec off, 0.1 sec on, 5 sec off, Table C.1 Cadence Patterns FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 118: Appendix D: Panel Security

    Ensure the Ethernet cable is removed from the FACP when not being utilized for configuration or for reporting purposes. Security and Data Protection Communication Security - Level 1 Stored Data Security - Level 0 Physical Security - Level 1 Access Control Security - Level 1 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 119: Model Fcp-75 Basic Operating Instructions

    Model FCP-75/FCP-75HV Basic Operating Instructions These instructions must be framed and displayed next to the FCP-75 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the system in accordance to NFPA 72. Operation Task to Perform Silence Alarms and Troubles Press SILENCE and then enter a code if prompted.
  • Page 121 FCP-75 Manual — P/N LS10147-003FK-E:B 6/20/2022...
  • Page 122 Fike World Headquarters 704 SW 10th Street Blue Springs, Missouri 64015 USA Tel: +001 816-229-3405 Toll Free (US Only): 1-800-YES-FIKE (1-800-937-3453) www.Fike.com For a list of contact information for Fike offices around the world, visit the Global Locations section of Fike.com...

Table of Contents