Single flood zone fire suppression system control panel (78 pages)
Summary of Contents for Fike FCP-75
Page 1
Addressable Fire Alarm Control Panel FCP-75 Instruction Manual Document LS10147-003FK-E 3/17/2021 Rev: P/N LS10147-003FK-E:A • ECN 151526...
Page 2
Adequate written records of all rise feature of each detector should be tested at least once per year inspections should be kept. by a qualified fire protection specialist. Heat detectors are designed to Limit-F-2020 protect property, not life. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 4
Electrical and electronic equipment contains materials, parts and substances, which can be dangerous to the environment and harmful to human health if the waste of electrical and electronic equipment (WEEE) is not disposed of correctly. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
3.6: Board Assembly Diagram....................................17 3.7: Calculating Current Draw and Standby Battery ..............................17 3.7.1: Current Draw Worksheet Requirements...............................17 3.7.2: Current Draw Worksheet for Fike IDP SLC Devices ..........................18 Maximum Battery Standby Load................................20 Section 4: Control Panel Installation ..........................21 4.1: Mounting the Control Panel Cabinet ................................21 4.1.1: Preventing Water Damage..................................21...
Page 7
Table of Contents Section 7: Fike IDP and SWIFT SLC Device Installation....................65 7.1: List of Fike IDP SLC Devices ..................................65 7.2: SWIFT Wireless SLC Devices ..................................65 7.3: Maximum Number of Devices ..................................65 7.4: Wiring Requirements for SLC Devices ................................66 7.4.1: Wire Sizing for Internal SLC................................66...
Page 8
10.8: Smoke Alarm Verification ...................................110 10.9: Function Keys ......................................111 10.9.1: Recording an F-Key Macro ................................111 10.9.2: Aborting an F-Key Macro Recording Session..........................111 10.9.3: Erasing an F-Key Macro...................................111 10.9.4: Using a Recorded F-Key Macro ...............................111 FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 9
10.9.6: F-Key Map Inhibit ....................................111 Section 11: Reporting ..............................112 11.1: Receivers Compatible with the Control Panel .............................112 11.2: SIA / FCP-75 Panels PI Modifier Reporting: ..............................119 11.3: SIA– FCP-75 Panel Communicator:................................120 Section 12: Testing and Troubleshooting........................122 12.1: Troubleshooting ......................................122 Table 12.1: Common Problems.....................................122...
1.2 About this Manual This manual is intended to be a complete reference for all installation and operation tasks for the FCP-75. Please let us know if the manual does not meet your needs in any way. We value your feedback! 1.2.1 Terms Used in this Manual...
Provides additional power, six Flexput circuits, and two Form C relays. Max 8 per system. See Supply FIK-RPS1000 Installation Manual (PN LS10259-001FK-E) for more information. FIK-5496 NAC Expander Provides 4 additional Notification Appliance Circuits/Auxiliary power. (Up to 8 per FCP-75 system). FIK-RA100 and 4 x20 Remote LCD annunciator.
Testing and maintenance should be performed according to NFPA 72. 2.1 Federal Communications Commission (FCC) The following information must be provided to the telephone company before the FCP-75 can be connected to the phone lines: Manufacturer: Fike...
The AC Loss Hours option must be set from 1-3 hours. 2.2.5 Requirements for the Installation of Carbon Monoxide (CO) Detection and Warning Equipment, NFPA 720 When using carbon monoxide detection the system must be monitored by a Supervising Station. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Signaling 0067000 Main board FIK-5496 NAC expander 5220 Direct connect module N FIK-NIC Network card FIK-FML/ -FSL Fiber module Y = YES, N = NO, O = OPTIONAL Table 2.1 NFPA Requirements for FCP-75 FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
FCP-75 panel for the first time. 3.1 Inventory When the FCP-75 shipment is received, check that all the parts have been included in the shipment. The shipment consists of one of each of the following: •...
Outputs Outputs Phone Lines SBUS Devices SLC IN/OUT 1/4” spacing must be maintained between each of Battery Battery these circuit types; as well as between power-limited and non-power-limited circuits. Figure 3.1 Wire Routing Example FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
The following steps must be taken when determining FCP-75 current draw and standby battery requirements. For the FCP-75, the worst case current draw is listed for the panel, addressable devices, and all SBUS expanders. Fill in the number of addressable devices that will be used in the system and compute the current draw requirements for alarm and standby. Record this information in the Current Calculation Worksheet at Line A.
Before You Begin Installing Calculating Current Draw and Standby Battery 3.7.2 Current Draw Worksheet for Fike IDP SLC Devices Use Table 3.3 to determine current requirements during alarm/battery standby operation when SLC devices are installed. You can install up to 75 IDP detectors and 75 IDP modules...
Page 19
1.25 Total ampere hours required Table 3.3 Current Calculation Worksheet for Fike IDP Devices (Continued) Total does not include isolator devices or accessory bases. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during that time.
Maximum Battery Standby Load The table below shows the maximum battery standby load for the FCP-75 based on 24 and 60 hours of standby. The standby load calcula- tions of line D in the Current Draw Calculation Worksheet (Table 3.4) must be less than the number shown in the table below for the battery size used and standby hours required.
The FCP-75 cabinet base dimensions are: 12.531” W x 14.875” H. The FCP-75 panel should be located within a secured area, where it is accessible to the main drop wiring runs and where it can be easily tested and serviced. End-users responsible for maintaining the panel should be able to hear alarms and troubles. When you select a location, keep in mind that the panel itself is the main source of alarm and trouble annunciation.
Connect the red wire from the control panel positive (+) terminal to the positive (+) side of Battery #1. Battery Jumper (P/N 140694) Shipped With Panel Black 12V Battery 12V Battery Figure 4.3 Battery Connection FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Figure 4.4 RBB Cabinet Mounting Holes Connect the main control panel battery cables to the battery cable extenders as shown in Figure 4.5. Figure 4.5 Splicing Control panel Battery Cable to RBB Battery Cable Extenders FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
4-conductor bus. The total worst case current draw is calculated by adding the individual worst case currents for each module. The individual worst case values are shown in the table below. NOTE: Total worst case current draw on a single SBUS cannot exceed 1 amp. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 25
Wiring Distance calculation example: Suppose a system is configured with the following SBUS modules: 2 - Module FIK-RA100 LCD Annunciator 1 - FIK-5496 NAC Expander 1 - FIK-5865 LED Fire Annunciator 1 - FIK-5824 Parallel/Serial Interface FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
The optional Model FIK-RA100 Remote Annunciator, is shown in Figure 4.9. The FIK-RA100 can be surface or flush mounted. Up to 8 FIK-RA100s can be added to the FCP-75 system in any combination. Figure 4.9 Model FIK-RA100 Remote Annunciator, Front View...
FIK-RA100 using any of the mounting holes shown in Figure 4.10. Mounting Holes Mounting Holes Figure 4.10 Back Box Mounting Holes Remove knockout holes as needed for wires. See Figure 4.11 for backbox knockout locations FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 28
Wire the Annunciator board to the main control panel. See Figure 4.8. Attach the annunciator and door assembly to back box as shown in Figure 4.12 using the supplied screws. Figure 4.12 Attaching Annunciator/Door Assembly to Backbox FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
After the annunciator wiring to the panel has been completed (described in Section 4.4.2), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Figure 4.15 Model FIK-RA100 Connection to the Panel 4.6 FIK-RA1000R Remote Annunciator Installation The optional Model FIK-RA1000R Remote Annunciator, is shown in Figure 4.16. Up to 8 annunciators can be added to the FCP-75 system. Figure 4.16 Model FIK-RA1000R Remote Annunciator, Front View FIK-RA1000R installation involves the following steps: Make sure the power is off at the panel.
If an electrical box is used, the box must be 1-3/8” back from the face of the wall to accommodate the annunciator. Studs used with an elec- trical box must be two by fours (or larger). FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
After the annunciator wiring to the panel has been completed (described in Section 4), replace the electronic assembly in the back box. Place the bezel over the back box and tighten the set screws on the bezel FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
The back box dimensions are 9¼” W x 8 3/8” H. The minimum depth required is 2". The back box can be mounted prior to the complete installation of the FIK-RA2000 using any of the mounting holes shown in Figure 4.10. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 34
Remove knockout holes as needed for wires. See Figure 4.11 for backbox knockout locations. Wire Knockouts Wire Knockouts Wire Knockouts Figure 4.24 Back Box Knockout Locations Wire the annunciator board to the main control panel. As described in Section 4.7.2. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Place a level on top of the back box, with the back box level insert the rest of the mounting screws Key Shaped Mounting Hole Back Box Mounting Holes Figure 4.26 Back Box Surface Mount Holes Run wires to the control panel. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
NOTE: Four FIK-5824s per panel maximum Use the DIP switches on the back of the FIK-5824 board to assign an ID# to the FIK-5824 (see Section 4.11.1). Configure the FIK-5824 device through programming. See Section 4.8.1. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
The FIK-5880 can drive up to 40 LEDs and has one PZT controller. The FIK-5880 also has eight inputs for dry con- tact monitoring. Up to 8 FIK-5880s can be added to the FCP-75 system. The following sub-sections describe hardware installation. Refer to Section 6 for programming information.
10 mA of current for each LED; no series resistors are required. LED outputs can be mapped to output circuits. See Section 9 for Programming details. Wire the LEDs as shown in Figure 4.33. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
The 8 input circuits on the FIK-5880 board are for monitoring switch inputs-any type of switch supported by the control panel can be used with the FIK-5880. For example, you can use a FIK-5880 to monitor pull stations, water flow, tamper, reset, or silence switches. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Refer to Section 6 for programming information. NOTE: This manual uses “FIK-5865” when referring to aspects of the FIK-5865-3 and FIK-5865-4 that are common to both models. Figure 4.35 FIK-5865-3 and FIK-5865-4 Assembly (front view) FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
The FIK-5865 ships with a set of zone description labels that can be inserted into the FIK-5865 board assembly. These labels can be used in a typewriter or can be written on by hand. Slide the labels under the plexiglass as shown in Figure 4.38. The LEDs will show through the label when illuminated. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
ID# to the module. Figure 4.39 shows all possible DIP switch positions and their correlation to a numerical ID. For example, to select ID 2, place DIP switch 2 in the up position. Figure 4.39 Possible module addresses Refer to Section 9.2 to edit, add, delete, and view module list. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
4.13 Notification Appliance/Auxiliary Power Circuits Two outputs are built-in to the FCP-75 FACP which can be programmed to be used as NACs (Class A or Class B) or as Aux power. This sec- tion of the manual explains how to install conventional notification appliances and how these terminals can be used for auxiliary power.
If AC power is off for more than 15 seconds, the auxiliary door holder power will be disconnected to conserve the battery backup. When AC power is restored, power is immediately restored to the door holder circuits. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
To install one or two programmable relays, follow these steps. Wire Relay 1 and/or Relay 2 as needed for your application. See Figure 4.44 for the location of the relay terminals. Configure the relay through programming (see Figure 9.2). FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Connect earth ground wire to the 5220 chassis with mounting screw. Program the NAC circuit used as a continuous and non-silencing. Refer to Section 9.5 for point programming, Section 9.4 for group settings, and Section 9.3 for zone settings and mapping. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Connect earth ground wire to the 5220 chassis with mounting screw. Program the NAC circuit used as continuous and non-silencing. Refer to Section 9.5 for point programming, Section 9.4 for group settings, and Section 9.3 for zone settings and mapping. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
If an alarm condition occurs, the alarm relay will close, overriding the trouble condition. Current: 15mA max. Operating Voltage: 24VDC nominal; 27.4 VDC max. Resistance: 4KΩ FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 49
Program the NAC circuit for non silence NAC circuit (see Section 9.5.2). NOTE: If you need to transmit supervisories or trouble conditions, additional relay modules must be added. Use relay 1 to transmit supervisory conditions. Use the trouble relay to transmit trouble conditions. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
4.15.5 Transmitter Activated by Dry Contacts This section describes the connection of a UL 864 listed remote station transmitter to the FCP-75 FACP dry contacts. The FACP contacts must be supervised by the Remote Station Transmitter Module using end-of-line resistors (ELRs) with a value determined by the transmitter manufacturer.
5.1.1 Networked Panels A networked site is a logical group of FCP-75 panels that behave as though the logical group is one large control panel. Each building is referred to as a “site.” All panels in a site operate as a single panel. The control functions like reset, silence and alarm activation operate across the entire site.
Each fiber loop module can Transmit (TX) and Receive (RX) fiber-optic cable connecting to the FIK-NIC. Up to two fiber loop cards can be added to the FIK-NIC, and both cards may be combined in the same configuration. See Figure 5.53. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
The FIK-NIC is designed to mount on the bracket inside the accessory cabinet. Use the following steps to properly mount the FIK-NIC-KIT. Place the FIK-NIC on the mounting bracket. Use the 6-pin cable included with FIK-NIC to connect the FCP-75 to the FIK-NIC. The 6-pin cable must be run in conduit. See Figure 5.50.
Unshielded Twisted Pair Wiring between Multiple Panels Unshielded twisted pair wiring between multiple panels is shown in Figure 5.55. Class A wiring is shown with a dotted line. Class A wiring Figure 5.55 Twisted Pair Wiring Configuration FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Fiber Optic Multi-Mode Wiring between Multiple Panels Fiber optic cable between multiple panels is shown in Figure 5.56. Class A is shown with a dotted line. Class A wiring Figure 5.56 Fiber Optic Wiring Example FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 56
Networking Common Communicator List FIK-NIC Wiring Options Class A wiring Figure 5.57 Fiber Optic Wiring Single-Mode Example FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
A mixture of fiber optic cable and twisted pair wiring between multiple panels is shown in Figure 5.58. Class A cabling is shown with dotted line. Class A wiring Figure 5.58 Twisted Pair and Fiber Optic Combination Wiring Example FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
NOTE: It is important that much thought is given when choosing the network IDs for each panel. It is difficult to change the IDs once panel programming has begun. The network ID for each panel is set using DIP switch positions 1 through 5. See Figure 5.59 below for possible DIP switch settings. Figure 5.59 Network ID Settings FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
If the Network Panel ID is changed and valid, the system will ask you to confirm the change. If it is not correct, you can change the dip switches at this time. Press up to select YES and press ENTER to confirm. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
To change an Access Code: Enter the installer code. The panel will automatically go to the Main Menu. Select 6 for Network Programming Menu. Select 5 for Access Codes. The Display reads: Select Profile 01 Fire Fighter’s Key FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Receiver numbers are populated based on panel number and audited to allow only the 4 appropriate receivers. See Appendix C for receiver number. Available reporting format choices are: • Contact ID • SIA500 • SIA8 • SIA20 • Ethernet FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Select 8 for Sync Network Options. Select which panel to source the options from. With the line selected Line 1 scrolls to show the date Scroll down to show checksum Figure 6.2 SYNC Network Options FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Point Functions Disable/Enable Buffer Point Status Set SLC Device Address SLC Single Device Locater SLC Multi-Device Locater I/O Point Control Event History Set Time & Date Network Diagnostics Table 6.2 Network Management Quick Reference List FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 64
Report Troubles Report Events by Point Primary Receiver Primary Account Test Primary Account Secondary Receiver Secondary Account Test Secondary Account Sync Network See Section 6.3 Options Table 6.2 Network Management Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
7.2 SWIFT Wireless SLC Devices The FIK-W-WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on the FCP-75. It is powered by the SLC loop or by a regulated, external 24VDC UL-listed power supply. Available wireless devices include a photo detector, a photo/heat detector, a fixed-temperature heat detector, a rate-of-rise detector, and a monitor module.
7.4.2 Wiring Requirements for IDP Modules The FCP-75 SLC can be programmed to operate in IDP mode. Use Table 7.4 to determine the specific wiring requirements for the SLC. Wire Requirements...
Wiring Requirements for SLC Devices Fike IDP and SWIFT SLC Device Installation Figure 7.2 Calculating Wire Run Length for a T-tap 7.4.3 Wiring SLC in Class A Configuration Figure 7.3 illustrates how to wire the SLC loop for Class A installations.
7.6.1 SLC Connections The FIK-W-WGI Wireless Gateway acts as a bridge between a group of wireless fire devices and a SLC loop on the FCP-75. It is powered by the SLC loops or by a regulated, external 24 VDC UL listed power supply. For details about wireless devices, system setup, and opera- tion, see the SWIFT Smart Wireless Integrated Fire Technology Instruction Manual P/N LS10036-000FK-E.
A series of messages displays for the next several seconds. JumpStart scans the SLC loops for devices. This can take several minutes, depending on the number of devices attached. When the message “Configuring System Done” displays, press any key to continue. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Input points are assigned to input zones. Any input point can be assigned to any input zone. (Input points can be assigned to one zone only. An input point can be designated as “Unused,” which means it has not been assigned to a zone). FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 71
Mapping Overview Programming Overview Figure 8.2 Input Point Assignment Example FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
SLC Loop Trouble AC Loss Trouble F1 Key Active Battery Trouble F2 Key Active Advisory Ground Fault Trouble F3 Key Active Phone Line Trouble F4 Key Active Reporting Account Trouble Table 8.1 Event Types FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 73
Mapping Overview Programming Overview Figure 8.4 Example of Zone Events Mapped to Output Groups and Patterns FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 74
Zone 2 Show Room Floor 2 Show Room Floor 2 Zone 1 Show Zone 1 Room Show Floor 1 Room Floor 1 Figure 8.5 Example of Zone Events Mapped to Output Groups and Patterns FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Mapping. When using HFSS, you can set up the programming options for the panel, save the options in a file, then download the file to the panel. You can connect to the control panel directly using the onboard USB or Ethernet. Updates are available at www.fike.com.
Select from a scrolling list. Use the up and down arrow to move through a list of available options. When the option you want to select is displayed, press ENTER. Table 8.2 Menu Options FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Select Group Dynamic Group Properties Group Act/Template 00-23 Section 9.4.1 Override Cadence View Group Points Select Group Edit OPG Template Select template Modify name and which OPG’s are in template Table 8.3 Programming Quick Reference List FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 78
NON-LATCH Section 9.5.1 1,2,3 Internal SLC SWITCH LATCH ZONE AUX2 NON-LATCH LATCH SYSTEM AUX1 NON-LATCH LATCH SYSTEM AUX2 NON-LATCH DETECTOR LATCH FIRE TAMPER NON-LATCH MANUAL RELEASE INTERLOCK Table 8.3 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 79
1,2,3 Select Sensor Section 9.5.1 SDR BAS Internal SLC RLY BAS ACCLIMATE I-SdrBa (Intelligent Sounder Base) No Accessory SDR base RLY base HEAT HT I-SdrBa (Intelligent Sounder Base) Table 8.3 Programming Quick Reference List (Continued) FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 80
W-SUP DET Detector UNUSED Internal Power and NOTIF OUTPUT Select Group, Point # Section 9.5.2 External Power B NOTIF Supervised Edit Name CONTROL Yes or No CIRCUIT Table 8.3 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 81
CO 4 WIRE DET Latch CO 4 WIRE SUP Non-Latch *Only applicable for FIK-RPS1000 UNUSED Point NOTIF OUTPUT FIK-5880/FIK-5865 Enter Point # Select Group (cont.) NOTIF CONTROL Edit Name CIRCUIT Table 8.3 Programming Quick Reference List (Continued) FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 82
Sensitivity Night Start Enter time *6:00PM Days of the Week Select days *-MTWTF- Holidays 1 to 18 Enter dates *01/01, 07/04, Section 9.6.3 Holiday Days 12/24, 12/25 Table 8.3 Programming Quick Reference List (Continued) FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 83
Table 8.3 Programming Quick Reference List (Continued) 1. Available on Internal SLC. 3. Available with SLC Family as IDP 4. Requires wireless gateway. 6. AUX SYNC setting is only applicable for the B200S/IV Sounder Base. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
To edit a module name, press the up or down arrow to select each character for the modules name (or press the right arrow to bypass the name edit). Press the right arrow to move to the next character. NOTE: See Appendix B to edit Names. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Features that can be edited through the edit zone option are zone name, zone properties (which includes, zone type, and detector sensitivity), and zone accessory options. To edit a zone, follow these steps: Enter the Installer Code. Select 7 for Program Menu. Press 2 to enter Zone Menu. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Figure 9.2 Edit Zone Properties NOTE: You only see smoke sensitivity on the FCP-75 if the daytime/nighttime sensitivity is off under System Options. (See Section “Daytime/Nighttime Sensitivity” on page 95). Otherwise if you have Daytime/Nighttime sensitivity on, this will bring up a Smoke Sens Day and Night, 2 separate widgets with sensitivity selection being either low, med, or high for each.
To view the points in a zone, follow these steps: Enter the Installer Code. The panel will automatically go to the Main Menu. Select 7 for Panel Programming. Press 2 to enter Zone Menu. Press 2 to view zone points. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
9.4.2 View Group Points Enter the Installer Code. The panel will automatically go to the Main Menu. Select 7 for Panel Programming. Press 3 to enter group Menu. Press 2 to view group points. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Supervisory switches can be latching or non-latching. DETECTOR Non Latching SUP SMOKE PHOTO SUP SMOKE ION SUP HEAT SUP ACCLIMATE SUP HEAT HT SUP SMOKE PHOTO/HEAT SUP SMOKE BEAM Table 9.4 Point Programming for Internal SLC Module FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 90
Manual release switch, typically a pull station. ILOCK Interlock release switch input. CO DETECT SW CO Detector Switch CO SUPERVISORY CO Supervisory Detector Switch DETECT SW STATUS PT Status Point Switch Table 9.4 Point Programming for Internal SLC Module (Continued) FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
To select the Group, press the up or down arrows, then press ENTER. 10. To edit the Point Name, press the right arrow to skip point name edit. See Section 9.5. 11. Repeat Steps 1 through 10 for all circuits. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Press the up or down arrows to select the desired module. Refer to Section 8.5 for available choices. Press ENTER. Figure 9.6 Programming Points Screen for FIK-5880 and FIK-5865 Modules Enter the Point Number, then press ENTER. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Star key on the telephone Comma (character for 2-second pause) Use the number buttons on the annunciator or the up- and down-arrow keys to select special characters. Characters begin displaying after “9”. See Figure 9.9 for an example. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Edit Ethernet Enter the Installer Code. The panel will automatically go to the Main Menu. Select 7 for Panel Programming. Select 5 for System Options. From the next Menu, select 1 for Communication Options. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Figure 9.10 Phone Line Gains 9.6.2 Daytime/Nighttime Sensitivity If you need to change the time that sensitivity levels take effect (that is, the time that “Day” and “Night” begin), follow these steps. Enter the Installer Code. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
All water flow switches on the system will use the same delay period. To access the screen for programming water flow delay, follow these steps: Enter the Installer Code. Select 7 for Program Menu. Select 5 for System Options. Select 4 for Time Options. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
To edit miscellaneous options, do the following. Enter the Installer Code. Select 7 for Program Menu. Select 5 for System Options. Select 5 for Miscellaneous Options. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Select each character of a word by pressing the up or down arrow, then press the right arrow key to move the cursor to the next character. When the word or sentence is complete, press ENTER to move the cursor to line two of the custom banner. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
JumpStart Autoprogramming Programming 9.6.8 SLC Family The FCP-75 supports Intelligent Device Protocol (IDP) SLC devices. Enter the Installer Code. Select 7 for Program Menu. Select 5 for System Options. Select 8 for SLC Family. Press UP arrow to select the desired SLC device type.
This feature allows the user to press the ACK key and display the oldest un-acknowledged event in the system. Pressing ACK key again will acknowledge the event, then display the next oldest un-acknowledged event without pressing the arrow keys. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Inhibiting an Output Group prevents the group from being used by System Mapping. While inhibited, no event in the system can activate the Output Group. Press 8 to inhibit the Output Group (OPG). Use the up or down arrow key to select the group to be inhibited. Press the right arrow to inhibit the group. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
NOTE: The panel does not do a full 30 second reset on resettable power outputs. As soon as the device is back to normal, the panel is ready to go to the next device. 10.4.7 Conduct a Communicator Test From the Main Menu, press 1 for System Tests. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
From the Main Menu, press 2 for Point Functions. Press 2 for Point Status. Select the module where the point you want to check is located. Enter the number of the point you want to check and press ENTER. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Send/Receive firmware updates The FCP-75 has the ability to be updated in the field. The latest FCP-75 Firmware Update Utility can be downloaded from the Fike web site. Once a panel has been updated using the Firmware Update Utility, you can use Send/Receive firmware updates to propagate the firmware to the other panels in the network.
(fire and CO). Auto Display Event activates after two minutes of annunciator inactivity. Figure 10.5 Highest Priority Event Display Figure 10.6 This Screen will display when more that 3 event types are active FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
(or activate the key) to restore the panel to normal. Alarm CO detector goes into alarm. If more than 3 categories are active at a single time screen will display as shown. Table 10.1 Panel Modes FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 107
Press SILENCE and enter an Access Code (or activate the key) to silence the annunciator. Trouble Once the trouble condition has been fixed, the system will restore itself automatically. A trouble condition with a CO detector Table 10.1 Panel Modes (Continued) FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
The FCP-75 Menu system is disabled on a multi-site annunciator. Pressing the Right or Enter keys will bring you straight into event history for assigned sites. To get into the Menu system, a multi-site user password must be entered and then a site must be selected from the site selection Menu.
If two or more addressable detectors, or a manual release switch activate, the “Alarm” and the “Release” outputs will activate. (Also refer to Table 10.4). Output Results Inputs Normal Pre-Alert Release and General Alarm 1st Addressable Detector 2nd Addressable Detector Manual Release Station Table 10.3 Input Conditions and Output Results FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
10.8 Smoke Alarm Verification Figure 10.2 illustrates how the Smoke Alarm Verification cycle operates. Figure 10.2 Smoke Verification Cycle During the Confirmation Period, if there is no alarm indication, then the system will return to normal operation. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
10.9 Function Keys The function keys (on FIK-RA2000 only) FCP-75 have multiple features. Their macro key functionality can simplify the disabling, activat- ing, or inhibiting points or groups respectively. They can also be used as a status type activation event and used for activating the Map Inhibit.
F3 Mapping Inhibited Restoral 2003 FJNN002003 F4 Mapping Inhibited 2004 FTNN002004 F4 Mapping Inhibited Restoral 2004 FJNN002004 Fire Reset ORNN000000 Fire System Overridden FSNN000000 Fire System Override Restore FRNN000000 Table 11.2 Reporting Formats Table FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 113
SLC programming started, system shut down TSNN000000 SLC short circuit trouble Exp. ID ETNNXX0000 Exp. ID SLC short circuit trouble restore Exp. ID ERNNXX0000 Exp. ID Time changed event JTNN000000 Table 11.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 114
Group # + 1000 FJNN001GGG Group # Positive Alarm Sequence acknowledge Zone # FTNN000ZZZ Zone # switch trouble Positive Alarm Sequence acknowledge Zone # FJNN000ZZZ Zone # switch trouble restore Table 11.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 115
Zone # + 2000 UHNN002ZZZ Zone # Zone-based AUX2 switch trouble Zone # + 2000 UTNN002ZZZ Zone # Zone-based AUX2 switch trouble restore Zone # + 2000 UJNN002ZZZ Zone # Table 11.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 116
ECS NAC Trouble pi Exp. ID QT Point # QTNNXXPPPP Exp. ID Point # ECS NAC Trouble Restored pi Exp. ID QJ Point # QJNNXXPPPP Exp. ID Point # Table 11.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 117
Manual release switch trouble restore (Water pi Exp. ID FJ Point # FJNNXXPPPP Exp. ID Point # Release Zone) Notification output point disabled pi Exp. ID FB Point # FBNNXXPPPP Exp. ID Point # Table 11.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 118
Exp. ID UU Point # UUNNXXPPPP Exp. ID Point # Voice Aux Status 1 Switch is Trouble pi Exp. ID UT Point # UTNNXXPPPP Exp. ID Point # Table 11.2 Reporting Formats Table (Continued) FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
UJNNXXPPPP Exp. ID Point # Table 11.2 Reporting Formats Table (Continued) 11.2 SIA / FCP-75 Panels PI Modifier Reporting: Events are sent to the central station as a variable length string: The Event Format is: EEZZZZ Where the Event Format is defined as follows:...
NAC Circuit EE-ZZZ FT400 ZZZ=OPG# Table 11.3 SIA: FCP-75 Panels - PI Modifier Reporting Examples 11.3 SIA– FCP-75 Panel Communicator: (Differences/additional features are underlined). The Events are sent to the Central Station Receiver as a fixed length string: The Event Format is:...
Page 121
Fire Trouble Point EE-PP-MM-ZZZZ FT22970200 Fire Trouble Zone EE-PP-MM-ZZZZ FT22970001MM = 00 Fire Trouble-NAC Point NAC Circuit 7 EE-PP-MM-ZZZZ FT22980007ZZZZ=Pt. # Fire Trouble-NAC Zone NAC Circuit 7 EE-PP-MM-ZZZZ FT22980007ZZZZ=OPG # Table 11.4 SIA REPORTING EXAMPLES (Continued) FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
• the ALARM indicator lights. • all active Notification Appliances sound. Measure battery voltage while the Notification Appliances are sounding. Replace any battery with terminal voltage less than 85% of rating. Reapply AC power and RESET system. FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Select the SLC loop. Enter up to 8 SLC addresses for the devices you wish to locate. The LEDs on the selected devices will start flashing. Press the left arrow key to exit SLC multi-locater function. FCP-75 Manual — P/N:LS10147-003FK-E:A 3/17/2021...
Page 126
Installation Records IDP SLC Device Point Record Zone / Detector Addr Description Detector Addr Zone/ Group Description Group Table 13.3 IDP Detector Installation Record (Continued) FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Page 134
• Do not mix detectors of different models unless the system is specifically intended to be installed in that configuration. • Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum reset time of the smoke detector FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
A.6 Compatible 520Hz Low Frequency Bases Model Number Description B200S-LF-WH / IV Low Frequency Intelligent Sounder Base B200SR-LF-WH / IV Low Frequency Intelligent Sounder Base Color Guide: -IV = Ivory color, -WH = White Table A.7 Low Frequency Bases FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Press 0 to space, then continue to next word using the same process. Press ENTER to accept. NOTE: After three seconds of no change, letter will automatically be accepted. Also pressing next number will automatically accept previous choice Figure B.1 Edit Name Example FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
The available receiver number will correspond with what panel number you entered. Receiver numbers are populated based on panel number and audited to allow only the 4 appropriate receivers. See Section 6.2.6. Panel Available receiver numbers Table C.1 Receiver/panel relationship FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Appendix D: Cadence Patterns The cadence patterns shown below are available for use with the control panel. Figure D.1 Cadence Patterns FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Ensure the Ethernet cable is removed from the FACP when not being utilized for configuration or for reporting purposes. Security and Data Protection Communication Security - Level 1 Stored Data Security - Level 0 Physical Security - Level 1 Access Control Security - Level 1 FCP-75 Manual — P/N LS10147-003FK-E:A 3/17/2021...
Model FCP-75 Basic Operating Instructions These Instructions must be framed and displayed next to the FCP-75 panel in accordance with NFPA 72 fire code for Local Protected Fire Alarm Systems. Test the system in accordance to NFPA 72. Operation Task to Perform Silence Alarms and Press SILENCE then enter a code if prompted.
Need help?
Do you have a question about the FCP-75 and is the answer not in the manual?
Questions and answers