Adequate written records of all rise feature of each detector should be tested at least once per year inspections should be kept. by a qualified fire protection specialist. Heat detectors are designed to Limit-F-2020 protect property, not life. FIK-5496 Manual — P/N LS10253-001FK-E:A 03/02/2021...
Page 4
• Brief description of content you think should be improved or corrected • Your suggestion for how to correct/improve documentation Send email messages to: FikeElectSupport@fike.com or call (800)979-3453, x21 in US or (816)229-3405 international FIK-5496 Manual — P/N LS10253-001FK-E:A 03/02/2021...
The FIK-5496 is capable of performing single or dual interlocking operations for the Pre-action and Deluge Releasing Systems. See Section 8.6 of this FACP installation Manual. • The FIK-5496 has four output circuits that can be configured as notification or auxiliary power circuits. Outputs are rated 3.0 A (6.0 A total for each FIK-5496). •...
Do not mount the panel in areas with humidity-generating equipment (such as dryers, production machinery). When you select a location to mount the FIK-5496, the unit should be mounted where it will NOT be exposed to temperatures outside the range of 0°C-49°C (32°F-120°F) or humidity outside the range of 10%-93% at 30°C (86°F) non-condensing.
Use this Section to determine the current draw and the standby battery needs for your installation. 2.6.1 Worksheet Requirements Follow the steps below to determine the FIK-5496 current draw and the standby battery requirements. Filling in the Current Draw Worksheet Refer to Table 2.4 in Section Figure 2.6.2 on page 9 to complete the following steps.
Maximum Battery Standby Load Table 2.3 shows the maximum battery standby load for the FIK-5496 based on 24 and 60 hours of standby. The standby load calculations of line J in the Current Draw Calculation Worksheet Table 2.4 must be less than the number shown in Table 2.3 for the battery size used and standby hours required.
Maintain one-quarter inch spacing between the power-limited and the non-power limited circuits. • Separate the high and the low voltage circuits. To AC Power FIK-5496 Board To SBUS Terminals To NACs To Battery Figure 2.2 Wire Routing Example FIK-5496 Manual — P/N LS10253-001FK-E:A 03/02/2021...
Determine the correct AH rating per your current load calculation (see “: Current Draw Calculation Worksheet” on page 6). NOTE: If you require the power of the back-up batteries that are too large for the FIK-5496, you can use the FIK-RBB cabinet. The FIK-RBB Remote Battery Box, holds batteries up to the 35 AH size.
3.4 Setting the Device ID All SBUS modules in the System must have a unique number (1-31) to identify them to the FACP. Use the DIP switch on the FIK-5496 board to set the module ID number. Figure 2-1 on page 2 shows the location of the dipswitch on the board. Figure 3.4 on page 12 shows dip- switch setting and the corresponding module ID numbers.
Figure 3.6 on page 13 shows how to wire for the Class B output supervision. Use the In/Out wiring methods for the proper supervision. To identify which notification appliances to be used with the FIK-5496, refer to Appendix A. 3.5.4 Class B Output Notification Circuits Figure 3.6 on page 13 shows four, 1.5 amp devices wired as Class B circuits.
Resettable, 24-volt power is always present at the terminals unless a System Reset occurs. If a System Reset occurs, the power is removed from the terminals for 30 seconds, then re-applied. 3.6 Sounder Sync Power The Sounder Sync Power continuously outputs the System Sensor synchronization pattern and is intended for use with B200S sounder bases. FIK-5496 Manual — P/N LS10253-001FK-E:A 03/02/2021...
The FIK-5496 is capable of performing single or dual interlocking operations for the Pre-action and Deluge Releasing Systems. See Section 8.6 of this FACP installation Manual. • The FIK-5496 has four output circuits that can be configured as notification or auxiliary power circuits. Outputs are rated 3.0 A (6.0 A total for each FIK-5496). •...
Page 16
FIKE CORPORATION 704 SW 10th Street Blue Springs, MO 64015 Telephone: +1-816-229-3405 www.fike.com...