Siemens RUGGEDCOM RSG2488F Installation Manual page 56

Hide thumbs Also See for RUGGEDCOM RSG2488F:
Table of Contents

Advertisement

Chapter 6
Certification
Test
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-10
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 61000-4-18
IEC 61000-4-29
46
Description
Radiated RFI
Burst (Fast Transient)
Surge
Induced (Conducted) RFI
Magnetic Field
Damped Oscillating
Magnetic Field
Voltage Dips
and Interrupts
Damped Oscillatory
Mains Frequency Voltage
Ripple on DC
Power Supply
Damped Oscillatory Wave
Voltage Dips
and Interrupts
Enclosure Air
Enclosure Ports
Signal Ports
± 4 kV @ 2.5 and 5 kHz
DC Power Ports
± 4 kV @ 2.5 and 5 kHz
AC Power Ports
Earth Ground Ports
Signal Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
DC Power Ports
± 2 kV Line-to-Earth,
± 1 kV Line-to-Line
AC Power Ports
± 4 kV Line-to-Earth
± 2 kV Line-to-Line
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Enclosure Ports
100 A/m for 3 min
Enclosure Ports
100 A/m for 1 s (100
AC Power Ports
60% for 50 periods
100% for 5 periods
100% for 50 periods
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
DC Power Ports
Signal Ports
2.5 kV Common Mode
1.0 kV Differential Mode
DC Power Ports
2.5 kV Common Mode
AC Power Ports
DC Power Ports
Test Levels
Severity Levels
± 15 kV
20 V/m
± 4 kV @ 5 kHz
10 V
1000 A/m for 3 s
kHz and 1 MHz)
30% for 1 period
2.5 kV Common
1 kV Differential
Mode @ 1 MHz
30 V for 60 s
300 V for 1 s
10%
30% for 0.1 s
60% for 0.1 s
EMC and Environmental Type Tests
RUGGEDCOM RSG2488F
Installation Guide
a
Note
4
3
4
3
5
5
3
4
3
3

Advertisement

Table of Contents
loading

Table of Contents