Reliability Data - Delta CliQ II DRP024V120W3B Series Technical Data Sheet

Din rail power supply 24 v 120 w 3 phase
Table of Contents

Advertisement

TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 120 W 3 Phase / DRP024V120W3B
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Transient Surge Voltage Protection
Internal Fuse
Degree of Protection
Protection Against Shock
1) PE: Primary Earth

Reliability Data

MTBF
Expected Cap Life Time
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
4
www.DeltaPSU.com (October 2021, Rev. 07)
32 V ±10%, SELV Output, Hiccup Mode,
Non-Latching (Auto-Recovery)
> 150% of rated load current, Hiccup Mode,
Non-Latching (Auto-Recovery)
< 80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
MOV (Metal Oxide Varistor)
T 3.15 A
IP20
Class I with PE
1)
connection
> 800,000 hrs. as per Telcordia SR-332
I/P: 3 x 400 Vac, O/P: 100% load, Ta: 25°C
10 years (3 x 400 Vac & 3 x 500 Vac, 50% load @ 40°C)