Specifications; Output Ratings / Characteristics - Delta CliQ II DRP024V120W3B Series Technical Data Sheet

Din rail power supply 24 v 120 w 3 phase
Table of Contents

Advertisement

TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 120 W 3 Phase / DRP024V120W3B

Specifications

Input Ratings / Characteristics
Nominal Input Voltage
Input Voltage Range
1)
Nominal Input Frequency
Input Frequency Range
DC Input Voltage Range
2)
Input Current
Efficiency at 100% Load
Max Power Dissipation
Max Inrush Current (Cold Start)
Leakage Current
1) Fulfills test conditions for up to 600 Vac maximum.
2) Fulfills the test conditions for this range.

Output Ratings / Characteristics

Nominal Output Voltage
Factory Set Point Tolerance
Output Voltage Adjustment Range
Output Current
Output Power
Line Regulation
Load Regulation
PARD
4)
(20 MHz)
Rise Time
Start-up Time
Hold-up Time
Dynamic Response
(Overshoot & Undershoot O/P Voltage)
Start-up with Capacitive Loads
3) For power de-rating from 50°C to 80°C, see power de-rating on page 3.
4) PARD is measured with an AC coupling mode, 5cm wires, and in parallel with 0.1 μF ceramic capacitor & 47 μF electrolytic capacitor.
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
2
www.DeltaPSU.com (October 2021, Rev. 07)
0% load
100% load
3)
3 x 400-500 Vac
3 x 320-600 Vac (3-Phase) or 2 x 360-600 Vac (2-Phase)
50-60 Hz
47-63 Hz
450-800 Vdc
< 0.50 A @ 3 x 400 Vac, < 0.40 A @ 3 x 500 Vac
> 88.0% @ 3 x 400 Vac & 3 x 500 Vac
< 3.0 W @ 3 x 400 Vac, < 4.0 W @ 3 x 500 Vac
< 16.3 W @ 3 x 400 Vac & 3 x 500 Vac
< 30 A @ 3 x 400 Vac & 3 x 500 Vac
< 3.5 mA @ 500 Vac
24 Vdc
24 Vdc ± 2%
24-28 Vdc
5.00 A (continuously operating at 24 V)
7.50 A (Power Boost for 5 seconds at 24 V, refer to the details
in the Functions section)
120 W (continuously operating at 24 V)
180 W (Power Boost for 5 seconds at 24 V, refer to the details
in the Functions section)
< 0.5% (@ 3 x 320-600 Vac input, 100% load)
< 1.0% (@ 3 x 320-600 Vac input, 0-100% load)
< 150mVpp
< 100ms @ nominal input (100% load)
< 1,000ms @ nominal input (100% load
> 20 ms @ 3 x 400 Vac,
> 40 ms @ 3 x 500 Vac (100% load
± 5% @ 3 x 320-600 Vac input, 0-100% load
(Slew Rate: 0.1 A/μs, 50% duty cycle @ 5 Hz to 1 KHz)
10,000 µF Max
)
)