Omron SYSMAC C200H CPU01-E Installation Manual page 92

Table of Contents

Advertisement

Specifications
Triac Output Unit C200H-OA121-E
Circuit Configuration
Note When the fuse blows F LED lights and bit 08 turns ON. Bits 08 through15 cannot be used as work bits.
Terminal Connections
78
Downloaded from
Elcodis.com
electronic components distributor
All manuals and user guides at all-guides.com
Max. switching capacity
Min. switching capacity
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Internal Current Consumption
Fuse Rating
Power for External Supply
Weight
Dimensions
Output LED
indicator
Internal
circuit
Fuse blowout
detection circuit
F LED
Fuse: 5 A 125 V (5.2-dia.x20) GGS (Nagasawa)
L
L
L
L
120 VAC max
L
(1 A max. 4 A/Unit)
L
L
L
COM
1 A 120 VAC, 50/60 Hz (4 A/Unit)
10 mA (resistive load)/40 mA (inductive load)
10 VAC
3 mA (100 VAC) max.
1.2 V max.
1 ms max.
1/2 of load frequency or less.
1 (8 points/common)
140 mA 5 VDC max.
5 A 125 V (5.2-dia.x20)
N/A
250 g max.
A-shape
OUT
L
OUT
L
Fuse
COM
120 VAC max.
0
A0
1
A1
2
A2
3
A3
4
A4
5
A5
6
A6
7
A7
A8
A9
NC
Appendix B