Certain consumable items in a PC (such as fuses, Relays, or batteries) need occasional replacement. This Appen-
dix explains how to replace each of these items. Refer to Appendix B for the specifications of individual consum-
able items. Always keep spare items on hand so that they can be used as immediate replacements when needed.
CPU and Power Supply Fuses
Output Unit Fuses
Downloaded from
Elcodis.com
electronic components distributor
All manuals and user guides at all-guides.com
Appendix A
Inspection and Maintenance
Turn counterclockwise
to remove, clockwise to
attach
Standard
screwdriver
To replace a fuse, follow the steps below:
1, 2, 3...
1. Turn OFF the power to the PC.
2. Remove the fuse holder by turning it approximately 50° counterclockwise
with a standard screwdriver.
3. Remove the fuse from the holder.
4. Insert a new fuse.
5. Reattach the fuse holder by turning it approximately 50° clockwise with a
standard screwdriver.
To replace a fuse, follow the steps below. Use only UL/CSA certified replace-
ment fuses.
Fuse Specifications (5.2-dia. x 20)
Model
C200H-OD411
C200H-OD211
C200H-OD212
C200H-OD213
C200H-OA121-E
C200H-OA122-E
C200H-OA222V
C200H-OA223
C200H-OA224
F indicator (fuse blowout
detection circuit)
Yes
No
No
Yes
Yes
Yes
No
Yes
No
Rating
5 A 125 V
8 A 125 V
5 A 125 V
3 A 250 V
5 A 250 V
3.15 A 250 V