Flat Roof Installation; Multiple Installation; Dimensions; Model I-290 0106 / 0109 - MAXA i-290 0106 Installer Manual

Inverter air/water heat pumps with axial fans
Table of Contents

Advertisement

MODEL i-290
0106 / 0109
0112 / 0115 /
0118
5.5.4 Flat roof installation
The installation configuration on a flat roof is similar to that on a free-field ground, although some additional aspects must be considered:
• place the machine at a sufficient distance from side walls and protrusions, which must therefore be beyond the safety zone;
• ensure that the roof structure of the building is solid;
• choose a location where no accumulations of snow, dust or foliage can form;
• pay attention to noise emissions and maintain an adequate distance from surrounding buildings;
• if high air velocities are detected, install the protections listed in the previous chapter.
5.5.5 Multiple installation
When installing several machines side by side, follow the above configurations, maintaining a respect distance of L between each machine.
As an example, see the following respect zones (danger and safety) for the case of a generic number "n" of units installed on open field terrain:
For other types of installation not covered in this manual, contact technical support. If in doubt about the installation of the units, request a
technical assessment by the fire brigade or a fire prevention expert.
5.6 DIMENSIONS
5.6.1 Model i-290 0106 / 0109
IN/OUT: 1" G
E: power supply input.
20
X
Y
X1
mm
1000
1500
2000
mm
1500
2000
2750
MODEL i-290
0106 / 0109
mm
0112 / 0115 /
mm
0118
i-290
Y1
B
C
2500
500
400
3250
500
400
X
Y
L
1000
1500
1000
1500
2000
1000
Inverter air/water heat pumps with axial fans
D
d
400
250
400
250