Transport And Storage Temperature Limits; Lifting And Handling - MAXA i-290 0106 Installer Manual

Inverter air/water heat pumps with axial fans
Table of Contents

Advertisement

The appliance must be placed outside, in a place without continuously operating ignition sources (e.g. open flames, an oper-
ating gas appliance or an operating electric heater). Refer to Chapter 5.5.
Cable ducts and electrical conduits to the machine must not contain potential ignition sources.
Do not perforate or burn. Do not make mechanical modifications to the unit.
There are some moving parts inside the unit. Use extreme caution when working near them, even if the power supply is
disconnected. In particular, pay attention to the fan blades when removing the front protective grilles. Do not touch or insert
any objects into the moving parts.
The compressor heads and discharge pipework are at quite high temperatures. The pipes on the suction side of the compres-
sor, on the other hand, can reach very low temperatures. Uninsulated pipes can cause burns or freezer burns: only handle
these components when their temperature is close to ambient.
Be particularly careful when working near batteries. Aluminium fins are very sharp and can cause serious injury.
After the maintenance operations, close the panels by fixing them with screws.
After maintenance or replacement of components, reconnect the cables in the same position as in the factory.
Routine maintenance operations can be carried out with the machine charged, while in the case of extraordinary operations,
repairs or replacement of components and heavy work in the vicinity of the machine (e.g. construction sites), drain the ma-
chine of coolant gas and move it to a safe area if necessary (in accordance with Chapter 5.5).
Insulating materials are not self-extinguishing: remove them when working on the unit, if necessary.
Do not remove, replace or make illegible the adhesive labels on the unit and packaging. Do not cover the labels after installa-
tion of the unit.
5.2 TRANSPORT AND STORAGE TEMPERATURE LIMITS
Minimum storage temperature [°C]
Maximum storage temperature [°C]
5.3 LIFTING AND HANDLING
The handling must be performed by qualified personnel, properly equipped with appropriate tools to the weight and the encumbrance of the
unit, in compliance with safety regulations of accident preventing.
It is recommended:
1. check the weight on unit technical label or on table of technical data;
2. check moving the unit there are no disconnected paths, ramps, steps, doors that could affect the movement and damage the unit;
3. check that the unit remains horizontal when moving;
4. during handling, do not carry out abrupt and sudden manoeuvres in order to not destabilise the unit;
5. before handling the unit, check that the equipment is suitable for lifting and preserving the integrity of the unit;
6. perform lifting only by one of the listed procedures;
7. before starting handling make sure, the unit is in stable equilibrium.
Note that the weight of the unit is concentrated more on the side of the refrigeration circuit: take into consideration the weight distribution of
the machine when transporting it manually with ropes, in order not to lift excessive loads and avoid damage or personal injury.
It is recommended to remove the packaging only after the machine has been placed in the actual installation location. Dispose of the different
packaging materials in accordance with national regulations.
14
i-290
Inverter air/water heat pumps with axial fans
-10 °C
+50 °C