Before commissioning, carefully inspect the unit and packaging for damage or refrigerant leakage.
Do not proceed with the start-up of the unit if damage was found during transport. Immediately inform the Company of the
problem.
The company is not liable for any damage to the product caused by handling and transporting the unit in a manner not in
accordance with this manual and the regulations in force.
5.3.1 Lifting mode
Following lifting modes are allowed:
• forklift truck;
• ropes / bands.
Make sure to tension the lifting ropes gradually and check their correct positioning.
5.4 POSITIONING AND MINIMUM TECHNICAL CLEARANCES
All models of i-290 are designed and constructed for outdoor installations. The company is not liable for any damage to property, animals and/
or persons resulting from failure to comply with the instructions on installing the unit described in this manual.
It is advisable to create an adequately sized support base for the unit. The units transmit a small amount of vibrations to the ground: however,
it is advisable to place anti-vibration mounts between the base frame and the supporting surface. It is preferable to install the unit away from
places sensitive to noise and vibration (e.g. windows and glass panes).
Always make an environmental impact assessment based on the power and sound pressure data in chapter "12. TECHNICAL DATA" and the
sound emission limits according to the installation area of the unit, with reference to the DPCM of 14/11/1997. An assessment must also be
made if the unit is installed near workers, according to D. LGS. 81/2008 Art. 189 and following. To reduce vibrations and noise, the use of rubber
seals is recommended for wall installation.
In case of hanging installation, it is necessary to make sure that the wall has been made with solid bricks, concrete or similar.
The wall capacity needs to be enough to support al least four times the weight of the unit. The maximum installation height
is 800 mm.
The support plane must have enough capacity to support the unit weight, which can be checked both on the technical label
on the unit and on this technical manual under "Technical data" chapter.
The support plane must not be inclined to ensure the unit works properly and avoid a possible overturning.
The support plane must not be smooth, to avoid water/ice deposit as potential sources of danger.
i-290
Inverter air/water heat pumps with axial fans
Lifting through forklift truck.
Lifting with ropes / bands.