4.5 REFRIGERANT SAFETY DATA SHEET
Name:
Main hazards:
Specifi c hazards:
General informati on:
Inhalati on:
Eye contact:
Skin contact:
Exti nguishing media:
Specifi c hazards:
Specifi c methods:
Personal precauti ons:
Environmental precauti ons:
Cleaning methods:
Handling:
Technical measures/precauti ons:
Advice for safe use:
Storage:
Control parameters:
Respiratory protecti on:
Eye protecti on:
Hand protecti on:
Hygienic measures:
Colour:
Odour:
Boiling point:
Flash point:
Relati ve gas density (air=1)
Relati ve liquid density (water=1)
Solubility in water:
Stability:
Materials to avoid:
Decompositi on products
hazardous:
Acute toxicity:
Local eff ects:
Long term toxicity:
Global warming potenti al
GWP (R744=1):
Ozone Depleti on Potenti al ODP
(R11=1):
Disposal considerati on:
R290
HAZARDS IDENTIFICATION
Highly fl ammable gas.
Vapours are heavier than air and can cause asphyxiati on due to reduced oxygen levels.
Contact with the liquid can cause frost burns.
FIRST AID MEASURES
In high concentrati ons it can cause asphyxia. Symptoms may include loss of mobility and/or consciousness.
In low concentrati ons it may have a narcoti c eff ect.
Move the victi m to an uncontaminated area while wearing self-contained breathing apparatus. Use oxygen or arti fi cial
respirati on arti fi cial respirati on if necessary. Keep the pati ent lying down and warm. Call a doctor.
Carefully rinse with plenty of water for at least 15 minutes.
Wash immediately with plenty of water for at least 15 minutes.
Immediately remove contaminated clothing.
FIRE FIGHTING MEASURES
Water spray, dry powder.
Exposure to fl ames may cause the vessel to rupture or explode.
Cool down the containers with a water spray from a safe positi on. Stop the product leakage if possible. Use water spray,
if possible, to abate the fumes. Move the vessels away from the area of the fi re if this can be done without posing any
risks.
ACCIDENTAL RELEASE MEASURES
Try to stop the leak.
Evacuate personnel to safety areas.
Eliminate the igniti on sources.
Ensure proper venti lati on.
Avoid entering sewers, basements, excavati ons and areas where accumulati on can be dangerous.
Use personal protecti ve equipment.
Remain upwind.
Try to stop the leak.
Venti late the area.
HANDLING AND STORAGE
Ensure suffi cient air exchange and/or sucti on in the working area. Do not smoke.
Keep away from sources of igniti on (including electrostati c charges).
Use only appropriate equipment, suitable for the product.
Do not inhale the gas.
Close carefully and store in a cool, dry and well venti lated area.
Storage containers should be checked periodically. Do not store with other oxidants in general or other combusti ble
substances.
All electrical equipment in the storage area are compliant with the risk of explosive atmospheres formati on.
EXPOSURE CONTROLS/PERSONAL PROTECTION
OEL: data not available.
DNEL: data not available.
PNEC: data not available.
Filter masks can be used if the ambient conditi ons and durati on of use are known.
Safety goggles.
Work gloves.
No smoking.
PHYSICAL AND CHIMICAL PROPERTIES
Colourless.
Odourless.
-42,1 °C at atm press
470°C
1,50
0,58
75 mg/l.
STABILITY AND REACTIVITY
Stable under normal conditi ons.
Air, oxidising agents . Keep away from heat sources/sparks/open fl ames/heated surfaces.
Under normal conditi ons of storage and use, dangerous decompositi on products should not be generated.
TOXICOLOGICAL INFORMATION
CL50/inhalati on/4 hours/on rat = 20000 ppm.
No known eff ect.
No known eff ect.
ENVIRONMENTAL INFORMATION
3
0
Refer to the supplier's gas recovery programme. Avoid direct discharge into the atmosphere. Do not discharge where
accumulati on can be dangerous. Ensure that the emissions limits required by local regulati ons or specifi ed in authoriza-
ti ons are not exceeded.
i-290
Inverter air/water heat pumps with axial fans
11

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

I-290 0109I-290 0112I-290 0115I-290 0118

Table of Contents