APP 411 Installation, Operation, and Maintenance manual
Terminal
TERM
USB
MASTER, SLAVE
AI
AO
DI
HMI
• Flygt FOP 315
RS-485
24 VDC
DO3
DO4
DO1
DO2
PUMP
Description
Backplane termination switch
Standard type A USB socket
MASTER/SLAVE switch
+
Isolated analog input, 4–20 mA
Maximum 24 VDC
Scaling: 0–100%
Offset: 0–16 mA with 0.1 mA resolution
+
Analog output, 4–20 mA
Maximum 24 VDC
1
Digital inputs
Maximum 24 VDC
2
3
4
GND
Common ground (earth)
1
Ground
2
CAN low
3
Shield
4
CAN high
5
+ 24 VDC output
A
Modbus RTU
B
GND
+
24 VDC
Tolerance: 21.5–28.5 VDC
The power supply unit must fulfill isolation class
II.
< 700 mA. Typical: 150 mA
Fuse: 1 A
NO
Digital outputs
Potential free relay output
COM
Maximum 250 VAC, or 30 VDC, 5 A
NO
External fuse required, 5 A
COM
NO
COM
NO
COM
T4
Pump communication
T3
GND
Not used