d. Photocell (safety beam) Setting
NOTE: Make sure the photocell has been correctly installed and has been
connected to the Normally Closed contact terminals on the opener.
Also note that the photocell function must be disabled if a photocell is
not in use, otherwise the opener will not be able to close the door, and
the LED display will show the letter "r" as an indication.
a) Press and hold the SET Button until "1" appears on the display, then
release the button.
b) Press the UP button until "d" shows on the display.
c) Press SET to enter this setting sub-menu. You're now in the photocell
setting adjustment mode. A "0" will be shown on the display.
d) Press the UP or DOWN button to turn the photocell function on or off.
The setting can be set between "0" and "1" on the display. "0" is the
factory setting.
"0" means the photocell function is off.
"1" means the photocell function is on.
e) Press SET to confirm your selection. The display will return to "I I".
53