RPS-1000 installation involves the following steps.
1.
Mount cabinet to wall (Section 3.1).
2.
Connect AC power (Section 3.4) and backup battery (Section 3.5).
3.
Wire the FACP to the controlling RPS-1000 (Section 3.6).
4.
Set an ID for the RPS-1000 (Section 3.6.1).
5.
Install and wire SBUS modules that will be powered by this RPS-1000 (Section 3.7).
6.
Install and wire any outputs (conventional relays, notification appliances, auxiliary power modules, etc.) that will be powered by this
RPS-1000. See Section 3.8.2 for notification appliance wiring information. Refer to the FACP Installation Manual for software
configuration information and other information about installing outputs.

3.1 Cabinet Mounting

1.
Mark and pre-drill hole in the wall for the center top keyhole mounting bolt using the dimensions illustrated below.
2.
Install center top fastener in the wall with the screw head protruding.
3.
Place backbox over the top screw, level and secure.
4.
Mark and drill the left and right lower mounting holes.
5.
Install remaining fasteners and tighten.
chassis
mounting
locations

3.2 058950RPS Replacement Board Installation

CAUTION: REMOVE POWER
!
MAKE CERTAIN ALL POWER (AC AND DC) IS REMOVED BEFORE ANY REPLACEMENT WORK IS PERFORMED.
1.
Disconnect all wiring from the board.
2.
Remove the four nuts which secure the chassis to the cabinet. Refer to Figure 3.1 for mounting locations.
3.
Replace the board assembly and secure with nuts removed in step 2.
4.
Reconnect wiring.
RPS-1000 Manual — P/N 151153:R 2/15/2022

Section 3: Installation

mounting keyholes
11"
N
G
L
3
2
1
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
-
+
A
B
N.O.
C
N.C.
N.O.
C
N.C.
-
+
A
B
-
+
A
B
O
X
O
X
O
X
O
X
O
MAIN SBUS IN OUT
/
RELAY 1
RELAY 2
SBUS IN
SBUS OUT
I/O 1
I/O 2
I/O 3
I/O 4
I/O 5
lower mounting holes
Figure 3.1 RPS-1000 Cabinet Mounting
Note: Board assembly shown without Formex
cover for illustration purposes only. Formex
cover must be used in all installations.
chassis
mounting
locations
6
5
4
X
O
X
I/O 6
27

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt rps-1000

Table of Contents