1.1 RPS-1000 Description

The RPS-1000 Intelligent Power Module provides additional power and circuits to the IFP-2100, IFP-2100ECS, IFP-2000, IFP-2000ECS,
IFP-1000, IFP-1000ECS, IFP-300, IFP-300ECS, IFP-100, IFP-100ECS or IFP-75 FACPs. The RPS-1000 can power all compatible mod-
ules, including SLC devices (via a 5815XL or 6815 SLC Expander), remote annunciators, notification appliances, auxiliary power modules,
and all other compatible modules. The RPS-1000 is available in a black cabinet as P/N RPS-1000B and with a 240VAC input as P/N RPS-
1000HV.
NOTE: All references to RPS-1000 within this manual are applicable to the RPS-1000B and RPS-1000HV unless otherwise indicated.
NOTE: The IFP-100 and IFP-75 do not use 5815XL or 6815 SLC expanders.
The RPS-1000 has six Flexput circuits and two programmable relays. Outputs are rated 3.0 A (6.0 A total for each RPS-1000). Relays are
Form C rated at 2.5 A @ 24 VDC. Outputs and relays are fully programmable.
The RPS-1000 is optically isolated, providing ground loop isolation and transient protection. It functions as an SBUS repeater which condi-
tions the RS-485 signal and allows the module to drive up to 6,000 feet of additional SBUS wiring.
The RPS-1000 is housed in a metal cabinet that is identical in size to the IFP-1000/IFP-1000ECS FACP cabinet. This cabinet is large enough
to house two 17 AH batteries. The RPS-1000 cabinet provides mounting studs for two Model 5815XL or 6815 SLC Expander modules.
The RPS-1000 communicates to the main FACP via the SBUS. Each RPS-1000 provides an additional 6,000 feet of SBUS wiring length to
the main panel. As the drawings on the next pages illustrate, this allows for the distribution of modules, SLC devices, and outputs throughout
an extremely large facility.
As well as expanding the wiring length capabilities of the FACP, the RPS-1000 also expands the power capabilities by an additional 6.0 A of
current.
1.1.1 Maximum Number of SBUS Modules
The chart below shows the maximum number of compatible modules that can be used in an Intelligent installation. Modules can be distrib-
uted among the main panel SBUS and each additional RPS-1000 SBUS in virtually any combination.
RPS-1000 Intelligent Power Module
RA-100 or RA-1000 Remote Annunciator
RA-2000 Remote Annunciator
6815 SLC Expander
5815XL SLC Expander
5824 Serial/Parallel Modules
Outputs
Conventional Relays
6

Section 1: Overview

Module or Device
8 per IFP-50, IFP-75, IFP-100/ECS, IFP-1000/ECS installation
16 per IFP-300/ECS installation
63 per IFP-2100/ECS or IFP-2000/ECS installation
8 per IFP-50 or IFP-75 installation
12 per IFP-100/ECS or IFP-1000/ECS installation
16 per IFP-300/ECS installation
31 per IFP-2100/ECS installation
63 per IFP-2100/ECS or IFP-2000/ECS installation
63 per IFP-300/ECS or IFP-2100/ECS installation
7 per IFP-1000/ECS installation
63 per IFP-300/ECS, IFP-2000/ECS or IFP-2100/ECS installation
4 per IFP-1000/ECS, IFP-300/ECS, IFP-2000/ECS or IFP-2100/ECS installation
6 per IFP-1000, IFP-1000ECS, or RPS-1000
2 per IFP-1000, IFP-1000ECS, or RPS-1000