Maximum Battery Standby Load; 2: Current Draw Worksheet For Idp Slc Devices - Honeywell Farenhyt RPS-1000HV Manual

Intelligent power module
Table of Contents

Advertisement

Calculating Current Draw and Standby Battery

Maximum Battery Standby Load

Table 2.3 shows the maximum battery standby load for the RPS-1000 based on 24 and 60 hours of standby. The numbers below have a built
in 20% derating factor for the battery amp-hour capacity. The standby load calculations of line G in the Current Draw Calculation Worksheet
must be less than the number shown in Table 2.3 for the battery size used and standby hours required.
1
Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT)
NOTE: The maximum battery size for FM (Factory Mutual) installations is 33AH.
2.5.2 Current Draw Worksheet for IDP SLC Devices
For each RPS-1000 in the installation, use this worksheet to determine current requirements during alarm and battery standby operation. See
individual FACP manual for maximum number of devices.
For each device use this formula:
RPS-1000 Intelligent Power Module
(Current draw from battery)
Additional RPS-1000
(Daisy-chained to this module)
Addressable SLC Detectors
IDP-PHOTO
IDP-PHOTO-T
IDP-PHOTO-R
IDP-HEAT
IDP-HEAT-HT
IDP-HEAT-ROR
IDP-ACCLIMATE
IDP-PHOTO-W/-IV
IDP-PHOTO-T-W/-IVIV
IDP-PHOTO-R-W/-IV
IDP-HEAT-W/-IV
IDP-HEAT-HT-W/-IV
IDP-HEAT-ROR-W/-IV
IDP-BEAM (without integral test)
2
IDP-BEAM-T
OSI-RI-FH
3
DNR/DNRW
4
DNR
(with relay)
RPS-1000 Manual — P/N 151153:R 2/15/2022
Rechargeable
Battery Size
7 AH
12 AH
17 AH
33 AH
Table 2.3 Maximum Battery Standby Load
Device
# of Devices
This column
(7 max.)
(with integral test)
(non-relay)
Table 2.4 Current Draw Worksheet for IDP SLC Devices
Max. Load for 24 hrs. Standby,
5 mins. Alarm
270 mA
475 mA
685 mA
1370 mA
Current per Device
X
This column
1
Standby
Alarm:
Standby
Alarm:
Standby:
Alarm:
Standby:
Alarm:
SLC
Standby/Alarm:
Aux. Pwr
Standby:
Alarm:
SLC
Standby/Alarm:
Aux. Pwr
Standby:
Alarm:
SLC
Standby/Alarm:
Aux. Pwr
Standby:
Alarm:
None, included with IDP-PHOTO-R/-W/-IV
None, included with IDP-PHOTO-R/-W/-IV & IDP-RELAY
Before You Begin Installing
1
Max. Load for 60 hrs. Standby,
5 mins. Alarm
105 mA
190 mA
270 mA
540 mA
Standby
Current
= Current per number of devices.
40 mA
40 mA
mA
160
10 mA
mA
mA
10
mA
mA
mA
0.3 mA
mA
1
6.5 mA
mA
mA
mA
mA
mA
mA
0.2 mA
1
4.5 mA
mA
mA
mA
2 mA
mA
2 mA
mA
8.5 mA
2 mA
mA
2 mA
mA
8.5 mA
20 mA
mA
22 mA
mA
20 mA
Alarm Current
160 mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
mA
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Farenhyt rps-1000

Table of Contents