Compressor Protection
In addition to the external pressure switches, the compressor
also has inherent (internal) protection. If there is an abnormal
temperature rise in a compressor, the protector will open to shut
down the compressor. The UCB incorporates features to
minimize compressor wear and damage. An Anti-Short Cycle
Delay (ASCD) is utilized to prevent operation of a compressor
too soon after its previous run. Additionally, a minimum run time
is imposed any time a compressor is energized.
The ASCD is initiated on unit start-up and on any compressor
reset or lock-out.
Flash Codes or Error Messages
The UCB will initiate flash a code on the Simplicity Lite Control
(see Table 29) or sent error message to the LCD Smart
Equipment™ Control associated with errors within the system.
Reset
Remove the call for cooling, by raising thermostat setting higher
than the conditioned space temperature. This resets any
pressure or freezestat lockouts.

Electric Heating Sequence Of Operations

The following sequence describes the operation of the electric
heat section.
Single-stage heating (applies only to 5, 7 & 10 kW 230V
heaters and to 7, 10, & 15 kW 460V and 575V heaters. All other
heaters MUST use a two-stage thermostat):
a. Upon a call for heat by the thermostat, the heater
sequencer (1S) will be energized. After completing the
specified fan on delay for heating, the UCB will energize
the blower motor.
b The thermostat will cycle the electric heat to satisfy the
heating requirements of the conditioned space.
Two-stage heating (applies only to 15, 20 and 30 kW 230V
heaters and 20 and 30 kW heater 460V and 575V heaters.):
a. Upon a call for first-stage heat by the thermostat, the
heater sequencer (1S) (15, 20, 30 kW 230 volt) and
contactor (2M) (20, 30 kW 460 and 575 volt) will be
energized. After completing the specified fan on delay for
heating, the UCB will energize the blower motor.
If the second stage of heat is required, heater sequencer
(2S) (12, 20, 30 kW 230 volt) or contactor (3M) (20, 30 kW
460 and 575 volt) will be energized. After completing the
specified fan on delay for heating, the UCB will energize
the blower motor.
b The thermostat will cycle the electric heat to satisfy the
heating requirements of the conditioned space.

Electric Heat Operation Errors

Temperature Limit
If the UCB senses zero volts from the high temperature limit,
the indoor blower motor is immediately energized.
Johnson Controls Ducted Systems
This limit is monitored regardless of unit operation status, i.e.
the limit is monitored at all times.
If the temperature limit opens three times within one hour, it will
lock-on the indoor blower motor and a flash a code on the
Simplicity Lite Control (See Table 29) or sent error message to
the LCD Smart Equipment™ Control.
Safety Controls
The UCB monitors the temperature limit switch of electric heat
units.
The control circuit includes the following safety controls:
Temperature Limit Switch (TLS)
This control is located inside the heater compartment and is set
to open at the temperature indicated in the Electric Heat Limit
Setting Table 20. It resets automatically. The limit switch
operates when a high temperature condition, caused by
inadequate supply air flow occurs, thus shutting down the
heater and energizing the blower.
Table 20: Electric Heat Limit Setting
Temperature Limit
Voltage
kW
5
7
10
208-1-60
15
20
30
5
7
10
230-3-60
15
20
30
7
10
460-3-60
15
20
30
10
15
575-3-60
20
30
Flash Codes or Error Messages
The UCB will initiate a flash code associated with errors within
the system. Refer to flash code on the Simplicity Lite Control
(See Table 29) or sent error message to the LCD Smart
Equipment Control.
5188235-YIM-E-0518
Open Temperature
Switch
°F
1
140
1,3
140
1,2,3
140
2,4,6
140
1,2,3,4,5
140
6
150
1,2,3,4,5,6
150
1,2,3
140
1,2,3
140
1,2,3
150
2,4,6
140
1,2,3,4,5,6
150
1,3,5
160
2,4,6
150
2,4,6
140
2,4,6
140
2,4,6
140
3
160
3
150
2,4,6
140
2,4,6
140
5
160
5
150
51