GENERAL

YORK Model DCE units are single package air conditioners
designed for outdoor installation on a rooftop or a slab. Electric
heaters are available as field-installed accessories.
The units are completely assembled on rigid, permanently
attached base rails. All piping, refrigerant charge, and electrical
wiring is factory-installed and tested. The units require only
electric power and duct connections at the point of installation.
The electric heaters have nickel-chrome elements and utilize
single point power connection.

INSPECTION

As soon as a unit is received, it should be inspected for possible
damage during transit. If damage is evident, the extent of the
damage should be noted on the carrier's freight bill. A separate
request for inspection by the carrier's agent should be made in
writing. See Local Distributor for additional information.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING . Notes are intended to clarify or
make the installation easier. Cautions are given to prevent equipment damage. Warnings are given to alert installer that per-
sonal injury and/or equipment damage may result if installation procedure is not handled properly.
®
SINGLE PACKAGE AIR CONDITIONERS
Supersedes: Nothing
MODELS D3CE 036 & 048
MODEL D3CE 060 & 076 BELT DRIVE
(WORLD 50 HZ)
THIS PRODUCT M UST BE INSTALLED IN STRICT COMPLIANCE W ITH
THE ENCLOSED INSTALLATION INSTRUCTIONS AND ANY APPLICABLE
LOCAL, STATE, AND NATIONAL CODES INCLUDING, BUT NOT LIMITED
TO, BUILDING, ELECTRICAL, AND MECHANICAL CODES.
WARNING
INCORRECT INSTALLATION MAY CREATE A CONDITION WHERE THE
OPERATION OF THE PRODUCT COULD CAUSE PERSONAL INJURY
O R P R O P E R T Y D A M A G E .
SUNLINE 2000™
ELECTRIC / ELECTRIC

REFERENCE

Additional information on the design, installation, operation and
service of this equipment is available in the following reference
forms:
55.70-N1
- General Installation
55.70-N2
- Pre-start & Post-start Check List
530.18-N1.2V - Economizer Accessory
530.18-N1.4V - Fixed Outdoor Air Damper Accessory
530.18-N1.6V - Motorized Outdoor Air Damper Accy.
530.18-N1.8V
- Coil Guard
530.18-N7.1V
- Electric Heater Accessory
530.18-N7.2V
- Fuse Block Accessory
Renewal Parts:
Refer to Parts Manual for complete listing of replacement
parts on this equipment.
All forms referenced in this instruction may be ordered from:
Publications Distribution Center
Unitary Products Group
P.O. Box 1592, York, PA 17405
CAUTION
530.26-N1YI (994)
035-12135

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SUNLINE 2000 D3CE 036 and is the answer not in the manual?

Questions and answers

Summary of Contents for York SUNLINE 2000 D3CE 036

  • Page 1: General

    GENERAL REFERENCE Additional information on the design, installation, operation and YORK Model DCE units are single package air conditioners service of this equipment is available in the following reference designed for outdoor installation on a rooftop or a slab. Electric forms: heaters are available as field-installed accessories.
  • Page 2: Table Of Contents

    530.26-N1YI TABLE OF CONTENTS General ................1 MAINTENANCE Inspection................1 Normal Maintenance............14 Reference ................1 Nomenclature............... 2 TABLES INSTALLATION Description Page Limitations................3 Unit Application Data ........Location ................3 Physical Data..........Rigging and Handling ............3 Blower Perf. - 036 & 048 w/Direct-Drive..Clearances................
  • Page 3: Installation

    CAUTION: If a unit is to be installed on a roof curb or special supply and return air duct connections at the unit should be frame other than a YORK roof curb, gasketing must made with flexible joints to minimize the transmission of noise.
  • Page 4: Condensate Drain

    530.26-N1YI CONDENSATE DRAIN POWER AND CONTROL WIRING Plumbing must conform to local codes. Use a sealing Field wiring to the unit must conform to the applicable national and compound on male pipe threads. Install a condensate drain line local or municipal codes. ⁄...
  • Page 5: Optional Economizer Rain Hood

    530.26-N1YI (C) on unit top cover. Then slip flange of hood cover in under OPTIONAL ECONOMIZER RAIN HOOD flange of unit top cover, replace screw (C), engaging hole The following procedure should be used when assembling an (E) in hood flange and tighten. Attach the two side plates to economizer rain hood onto a unit.
  • Page 6: Disconnect Switch Bracket For Optional Belt-Drive

    530.26-N1YI Install the bracket on the left hand side of the unit as shown in DISCONNECT SWITCH BRACKET Figure 5. Several existing screws at the top of the unit and one FOR UNITS WITH BELT-DRIVE BLOWER screw approximately midway down from the top will be used for mounting the bracket.
  • Page 7: Front View

    530.26-N1YI (Direct-Drive Units) BLOWER FIELD-SUPPLIED ACCESS DISCONNECT SWITCH LOCATION CONTROL FILTER ACCESS BOX ACCESS OUTDOOR COIL COMPRESSOR ACCESS OPENING FOR OPENING FOR PRESSURE CHECK PRESSURE CHECK (829) ⁄ FRONT VIEW ELECTRIC HEAT ⁄ (19) (2089) 82 ACCESS ⁄ “ PVC FEMALE COND.
  • Page 8: Electric Heaters

    530.26-N1YI FIG. 6 - ENTHALPY SET POINT ADJUSTMENT ELECTRIC HEATERS The heaters are wired for a single point power supply. Power supply need only be brought into the single point terminal block and thermostat wiring to the low voltage terminal strip located Electric heaters are available as field-installed accessories.
  • Page 9 530.26-N1YI TABLE 3 - SUPPLY AIR PERFORMANCE D*CE 036 & 048 w/Direct-Drive Blower @ 380/415 Volts - Side Duct Connections Available External Static Pressure - Pa * MODEL MOTOR SPEED Watts Watts Watts Watts Watts 0.80 0.78 0.74 0.79 0.77 0.75 0.72 0.67...
  • Page 10 530.26-N1YI TABLE 4 - SUPPLY AIR BLOWER PERFORMANCE D*CE060 & 076 w/Belt-Drive Blower @ 380/415 Volts - Side Duct Connections Available External Static Pressure - Pa* MODEL AIR FLOW Watts Watts Watts Watts Watts Watts Watts 1.18 1059 1560 1077 1590 1095 1630...
  • Page 11 530.26-N1YI TABLE 4 - SUPPLY AIR BLOWER PERFORMANCE D*CE060 & 076 w/Belt-Driven Blower (continued) @ 380/415 Volts - Side Duct Connections Available External Static Pressure - IWG* MODEL AIR FLOW 0.20 0.30 0.40 0.50 0.60 0.70 0.80 Watts Watts Watts Watts Watts Watts...
  • Page 12: Operation

    530.26-N1YI TABLE 5 - STATIC RESISTANCES EXTERNAL STATIC PRESSURE DROP RESISTANCE, PA DESCRIPTION 0.47 0.57 0.66 0.75 0.85 0.94 1.03 1.13 1.23 1.32 1.42 1, 3 Economizer/Motorized Damper 17.4 20.0 22.3 27.3 32.2 37.2 42.2 49.6 57.0 64.5 74.4 5 - 15 KW 10.0 12.4 15.0...
  • Page 13: Safety Controls

    530.26-N1YI Two-Stage Cooling: HEAT ANTICIPATOR SETPOINTS A two-stage cooling thermostat may be used if the unit has an It is important that the anticipator setpoint be correct. Too high economizer. First-stage cooling is provided by the economizer a setting results in longer heat cycles and a greater if the outdoor air enthalpy is acceptable, and second-stage temperature swing in the conditioned space.
  • Page 14: Secure Owner's Approval

    530.26-N1YI NOTE: The tubes must be inserted and held in a position NOMINAL M perpendicular to the air flow so that velocity pres- sure does not affect the static pressure readings. 0.38 0.52 0.66 0.80 1.23 0.94 1.08 DCE060,076 3. Using an inclined manometer, determine the pressure drop DCE048 across a dry indoor coil.