Accessories; Technical Data - Window Master WCC 103 BT Installation Instruction

Motorcontroller
Table of Contents

Advertisement

Available languages

Available languages

Actuator type
WMB 801/802
WMB 811 / 812 / 815 / 816 / 817 / 818*
*with 2 locking actuators on the same motor line use: 1 x WMB 811 and 1 x WMB 812. 1 x WMB 815 and 1 x WMB 816 or 1 x WMB 817 and 1 x
WMB 818

Accessories

3
Accessories
Rain sensor
Rain / windspeed sensor
Comfort keypad, 1 window or 1 window group
Comfort keypad, model FUGA, surface mounting (CH version)
Comfort keypad, model FUGA, surface mounting
Room thermostat: temperature

Technical data

4
Technical data
Output current
Secondary voltage
AUX
Motor groups / Motor lines
Primary voltage
Power consumption
Leakage current
Inrush current on primary side
±24V
LED signalling
Connection cable
Operation range between
MotorController and remote control
Operating conditions
Max actuator activation duration (duty
cycle)
Material
Colour
Size
Weight
Max number ± 24V actuators that may be connected to WCC 103 BT
3A incl. load on X7 (max 0.5A)
Voltage
Resting potential with 230V AC without load
Ripple with full load
24V DC, 500mA
1 motor group with 1 motor line for ±24V standard actuators
MotorController: 100-240 VAC 0.85A 50/60Hz
Remote Control: 2 x AAA alkaline batteries (1.5V)
Idling < 0.5W
Full load 77 W
Max 0.75mA @ 240VAC
65A < 5ms w. 230V
Max. 6 x WCC 103 BT per 10A power supply group.
Circuit breaker "C" type.
Min. 500ms
2 green LEDs and 1 yellow indicate via blinking sequences failure and/or status of the
system and motor line. See paragraph on "Status and troubleshooting via LED" for a
detailed description and blinking sequences.
Actuators
Other components
The used Bluetooth technology (Bluetooth 4) has the following operation range:
-
Outside: up to 50m in radius
-
Inside: up to 10m in radius
Physical barriers such as walls, cabinets etc. will reduce the range.
-5°C - +45°C, for indoor mounting, the MotorController must not be covered
ED 40% (4 min. per 10 min.)
Plastic
White (RAL 9016)
MotorController: 215 x 206 x 37mm (W x H x D)
Remote control: 41 x 18 x 144mm (W x H x L)
MotorController: 0.92kg
Remote control: 61g
5
3
2
WLA 331
WLA 330
WSK 110 0A0B
WSK 300
WSK 103
WLA 110
24V DC (±15%)
24V DC @ 20°C
150mVp-p
flexible max. 6mm² / solid max. 10 mm²
min 0.2mm² / max. 1.5mm²

Advertisement

Table of Contents
loading

Table of Contents