Mitsubishi Electric FR-A862-05450-E Instruction Manual page 27

Separated converter type

Advertisement

Main circuit terminals
2.5
Main circuit terminals
2.5.1
Details on the main circuit terminals of the
inverter
Terminal
Terminal name
symbol
U, V, W
Inverter output
R1/L11,
Power supply for the control
S1/L21
circuit
P/+, N/-
Converter unit connection
Earth (ground)
2.5.2
Details on the main circuit terminals of the
converter unit (FR-CC2)
Terminal
Terminal name
symbol
R/L1,
S/L2,
AC power input
T/L3
R1/L11,
Power supply for the control
S1/L21
circuit
P/+, N/-
Inverter connection
Earth (ground)
26
INSTALLATION AND WIRING
Terminal function description
Connect these terminals to a three-phase squirrel cage motor or an PM
motor.
Connected to terminals P/+ and N/-. To retain the fault display and fault
output, or to use the converter unit (FR-CC2), remove the jumpers installed in
terminals R1/L11 and S1/L21, and apply external power supply to these
terminals.
When using a separate power supply from R1/L11 and S1/L21, the
necessary power capacity of the separate power supply is 80 VA.
Connect the converter unit (FR-CC2).
For earthing (grounding) the inverter chassis. This must be earthed
(grounded).
Terminal function description
Connect these terminals to the commercial power supply.
Connected to the AC power supply terminals R/L1 and S/L2. To retain the
fault display and fault output, remove the jumpers across terminals R/L1 and
R1/L11 and across S/L2 and S1/L21, and supply external power to these
terminals.
When using a separate power supply from R1/L11 and S1/L21, the
necessary power capacity of the separate power supply is 80 VA.
Connect to terminals P/+ and N/- of the inverter.
For earthing (grounding) the converter unit chassis. This must be earthed
(grounded).
Refer
to page
-
40
24
30
Refer
to page
-
40
24
30