Emerson Rosemount 2051CF Series Quick Start Manual page 22

Pressure transmitter and flow meter with 4–20 ma hart and 1–5 vdc low power hart protocol (revision 5 and 7)
Hide thumbs Also See for Rosemount 2051CF Series:

Advertisement

Quick Start Guide
Figure 6-2: LOI menu
6.3 
Switch HART
If the HART configuration tool is not capable of communicating with
HART Revision 7, the Rosemount 2051 will load a generic menu
with limited capability. To switch the HART Revision mode from the
generic menu:
Procedure
Navigate to Manual Setup → Device Information → Identification → 
Message.
a) To change to HART Revision 5, enter
field.
b) To change to HART Revision 7, enter
field.
22
Revision mode
®
Assign PV
HART Revision
in the Message
HART5
in the Message
HART7
Emerson.com/Rosemount
May 2023