Positioning Electrode; Securing The Burner To The Boiler - Riello RS 200/E FGR Installation, Use And Maintenance Instructions

Forced draught gas burner
Table of Contents

Advertisement

4.6

Positioning electrode

Before fixing the burner to the boiler, check the
correct positioning of the electrodes as in Fig. 14.
WARNING
The following is required to perform the check:
 remove the screw 1)(Fig. 13);
 extract the inner part 2) of the head, and adjust them.
1
2
4.7

Securing the burner to the boiler

Provide an adequate lifting system of the burner.
Separate the combustion head from the rest of the burner, as in
Fig. 15; proceed as follows:
 loosen the 4 screws 3) and remove the hood 1);
 remove the screws 2) from the two guides 5);
 disconnect the plug 14);
 disconnect the socket from the maximum gas pressure
switch;
 remove the two screws 4);
20186164
Fig. 13
5
2
1
20186165
Installation
4 . 5
m m
 pull back the burner on the guides 5) by about 100 mm;
 disconnect the electrode lead, then unthread the burner
completely from the guides.
 Fix the flange 9) to the boiler plate, interposing the insulating
gasket 8) supplied.
 Use the 4 screws supplied, with a tightening torque of 35 -
40 Nm, after protecting their thread with anti-seize products.
The seal between burner and boiler must be air-
tight; after the start-up, check there is no leakage
of flue gases into the external environment.
WARNING
9
4
3
17
GB
20187924
13
12
11
13
10
8
14
3
1 6
m m
Fig. 14
Fig. 15
20171664

Advertisement

Table of Contents
loading

This manual is also suitable for:

20171518

Table of Contents