Combustion head adjustment

At this point of the installation, the combustion head is fixed to the
boiler as shown in Fig. 13. It is therefore especially easy to adjust,
and this adjustment depends only on the maximum output of the
burner.
In the diagram (Fig. 17) find the notch at which to adjust both air
and central gas/air.
NOTE:
the diagram (Fig. 17) indicates the optimum adjustment for a
type of boiler according to Fig. 3 on page 9.
20171664
Installation
6
4
5
(R1)RS 200
Max burner output
18
External air R1 adjustment
 Rotate the screw 4)(Fig. 16) until the notch you have found
corresponds with the front surface 5) of the flange.
To facilitate adjustment, loosen the screw 6),
adjust and then lock.
WARNING
20186050
The adjustments indicated can be modified during
the initial start-up.