3.3

Burner categories

Country of destination
AT - CH - CZ - DK - EE - ES - FI - FR - GB - GR - HU - IE
IT - LT - LV - NL - NO - PT - RO - SE - SI - SK
DE - LU - PL - RO
3.4

Technical data

Model
Output
(1)
Fuel
Gas pressure at max. output
- Gas: G20
Operation
Standard applications
Ambient temperature
Combustion air temperature
Noise levels
Sound pressure
(3)
Sound power
Weight
(1) Reference conditions: Room temperature 20°C - Gas temperature 15°C - Barometric pressure 1013 mbar - Altitude 0 m above sea level.
(2) Pressure on the pressure switch socket (Fig. 28 on page 26) with zero pressure in the combustion chamber and at maximum burner output.
(3) Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum rated output.
The sound power is measured with the "Free Field" method, as per EN 15036, and according to an "Accuracy: Category 3" measuring accuracy,
as set out in EN ISO 3746.
3.5

Electrical data

Model
Main electrical supply
Control circuit power supply
Fan motor IE3
Ignition transformer
Absorbed electrical power
Protection level
Technical description of the burner
Max.
kW
Mcal/h
Min.
kW
Mcal/h
mbar
(2)
°C
°C max
dB(A)
kg
rpm
V
kW
A
V1 - V2
I1 - I2
kW max
Natural gas: G20 (methane gas)
Intermittent (min. 1 stop in 24 hours)
Modulating
Boilers: water, steam, diathermic oil
3 ~ 400V +/-10% 50Hz
1N ~ 230V +/-10% 50Hz
7
GB
Gas category
I2H
I2E
RS 200/E FGR
1400 ÷ 2200
1204 ÷ 1892
400
344
12.0
0 - 40
60
83.0
94.0
101
RS 200/E FGR
2935
400
5.5
10.2
230 V - 2 x 5 kV
1.9 A - 35 mA
6.5
IP 44
Tab. B
Tab. C
Tab. D
20171664