Riello RS 200/E FGR Installation, Use And Maintenance Instructions page 35

Forced draught gas burner
Table of Contents

Advertisement

 The air pressure switch test is carried out.
 The burner moves to the pre-purging position, the air
servomotor opens the damper at 90°.
 Factory pre-set pre-purging time starts.
 Burner goes to ignition position.
The ignition step starts; spark lights up.
 The gas valves open (the safety time count starts).
 Verify if the flame is present through the special window and
if combustion parameters are correct.
 If the control box locks out, the display shows the lockout
code.
E-display control
 Solve the problem, referring to paragraph "Ignition failure"
on page 39.
To unlock, refer to "Unlock procedure" on page 32.
 After ignition, the burner goes to the minimum point.
Continue with the calibration of ignition point and modulation
curve.